Home / Tools / Inverse-time curves

IEC and IEEE inverse-time curves

Calculate the operating time of a 51 element with the standard curves, see it on a log-log plot and compare it with the backup relay to check the coordination margin over the whole current range.

IEC 60255-151dependent-time characteristicIEEE C37.112inverse curves and reset

Example cases
IEC and IEEE inverse-time curves
E1Fault and criterion
A
s

Use the same side of the CT for everything: primary amperes, or secondary amperes of the same ratio.

E2Relay A, downstream
A
E3Relay B, upstream backup
A

Use a decimal point. The calculation runs in your browser and updates as you type.

Relay A time

— s

Relay B time

— s

Margin B − A

— s

Relay A multiple I/Is

—

Relay B multiple I/Is

—

Relay A reset

— s

Time-current curves
  • Relay A
  • Relay B
  • Maximum fault and margin
Time (s) against current (A), both on logarithmic scales. Each curve starts at 1.1 times its pickup. The dots mark each relay's time at the maximum fault and the yellow dimension, the margin between them.
Margin over the whole range
  • Margin B − A
  • Required margin and maximum fault
Time difference from 1.1 times the higher pickup up to the maximum fault, with current on a logarithmic scale. Below the horizontal yellow line the margin is not met; below zero, the backup operates first. Close to pickup the margin grows sharply and the trace leaves the scale.

Step-by-step calculation

What it means for coordination

    What it is for

    The 51 overcurrent element operates with a time that drops as current rises. For the relay closest to the fault to clear first, the backup curve has to stay above it with enough margin over the whole current range both relays see. Use this tool to check existing settings, prepare the points of a secondary injection test or verify by hand a result from coordination software.

    How it is calculated

    IEC 60255-151dependent-time characteristic

    t = TMS · (k / ((I / Is)α − 1) + c)

    For IEC curves, c = 0. I is the measured current, Is the pickup setting and TMS the time multiplier setting.

    IEEE C37.112inverse curves and reset

    t = TD · (A / (Mp − 1) + B) · tr = TD · tr / (1 − M²) for M < 1

    M = I / Is and TD is the time dial. The second equation is the reset, which emulates the return of the electromechanical disk and matters for intermittent faults: with M = 0 it equals TD · tr. IEC curves have no standard reset; each relay makes it instantaneous or definite-time.

    CurveStandardConstants
    IEC standard inverse (SI)IEC 60255-151k = 0.14; α = 0.02
    IEC very inverse (VI)IEC 60255-151k = 13.5; α = 1
    IEC extremely inverse (EI)IEC 60255-151k = 80; α = 2
    IEC long-time inverse (LTI)IEC 60255-151k = 120; α = 1
    IEEE moderately inverse (MI)IEEE C37.112A = 0.0515; B = 0.114; p = 0.02; tr = 4.85
    IEEE very inverse (VI)IEEE C37.112A = 19.61; B = 0.491; p = 2; tr = 21.6
    IEEE extremely inverse (EI)IEEE C37.112A = 28.2; B = 0.1217; p = 2; tr = 29.1

    Coordination margin

    Δt(I) = tB(I) − tA(I) ≥ required margin

    It is checked at the maximum fault both relays see and also over the whole range from pickup, because two curves of different shape can come close at low currents. The indicator is green if Δt meets the margin, yellow if the backup operates later but without the margin, and red if it operates first.

    Limits of the calculation

    • IEC 60255-151 sets the accuracy of the characteristic between 2 and 20 times pickup. Outside that range the tool warns: above 20 times many relays limit the curve, and near 1 times the actual pickup (around 1.05 to 1.1 times Is) makes the time undefined or very long.
    • It assumes constant current during the fault, no minimum time, no instantaneous element and no CT saturation.
    • Some manufacturers scale the dial differently or add a fixed time to the curve: always confirm with the relay manual before setting.
    • The required margin is set by the coordination study according to the breaker, the relay type and the measurement errors; the preloaded value is only an example.

    Frequently asked questions

    How is the operating time of an IEC standard inverse curve calculated?

    With the IEC 60255-151 equation (IEEE C37.112 uses its own form): t = TMS · 0.14 / ((I/Is)^0.02 − 1). For example, with a current of 10 times pickup and TMS = 0.1, the relay operates in 0.1 · 0.14 / (10^0.02 − 1) = 0.297 s. The other IEC curves change only the constants k and α.

    What coordination time interval is used between two overcurrent relays?

    The interval between the backup relay and the one closest to the fault must cover the breaker interrupting time, relay overtravel and the CT and relay errors. Common references use 0.2 to 0.4 s depending on the technology; the value for each case is set by the protection coordination study, checked over the whole current range both relays see.

    What is the difference between IEC and IEEE curves?

    Both are inverse-time characteristics, but with different equations: IEEE C37.112 adds a constant B and defines a reset that emulates the electromechanical disk, t = TD · tr / (1 − M²). Also, the IEC TMS and the IEEE TD are not on the same scale, so the same dial number does not give the same time.

    We do your protection coordination study

    We model the system, calculate the short circuit and set the curves of every relay so the one closest to the fault clears first. Then we load the settings into the relays, remotely as well.

    Related guides

    Other tools

    COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Relay coordinationUp to six relays, reclosers and fuses on a log-log plot, with the IEEE C57.109 damage curve, inrush and the coordination margin of each pair.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Per-unit base conversionBase current and impedance, conversion between %, pu and ohms, and change of base for transformers, generators and lines.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Symmetrical componentsPhase quantities to zero, positive and negative sequence and back (Fortescue), with phasor diagrams and what they mean for 46, 67Q and 51N.Vector group compensation (87T)TAP of each winding, phase compensation matrix, zero-sequence removal and the HV-to-LV clock diagram.Primary and secondary impedance (21)Primary to secondary ohms with the CT and VT ratios, line Z1, Z0 and k0, and zone reaches on the R-X plane.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.