Busbar mechanical stresses
Enter the tube, span, climate and short-circuit current: the tool calculates the tube stress and deflection, the post insulator load, the aeolian vibration risk, the expansion, and the sag and tension of a strung conductor.
IEC 60909-0§ 8.1peak currentCIGREwind, ice and vibration
Results
— MPa
— N/m
— MPa
— %
—
— m
Charts
- Deflected tube (exaggerated)
- Loads
- Stress
- Yield strength
- Instantaneous force
- Static maximum
- Wind
- Vortices
- Natural frequency
- Twice the band
- Set-up
- Design condition
How it was calculated and standards
Step-by-step calculation
What it is for
It checks a rigid tube busbar and a strung conductor of the same bay: tube stress and deflection under weight, ice and wind, short-circuit force, post insulator load, aeolian vibration risk, expansion, and conductor sag and tension at the design condition.
How it is calculated
CIGRE§ Green Bookwind
Wind on the tube
Fw = ½·ρ·V²·Cx·G·DIEC 60909-0§ 8.1eq. 55
Short-circuit force
F′ = (√3/2)·μ0·ip² / (2π·a) · ip = κ·√2·I″k · κ = 1.02 + 0.98·e−3R/XEuler-Bernoullibeam
Bending and deflection
σ scCIGRE§ Green Bookaeolian vibration
Aeolian vibration
fa = 51.75·Vw/d · fc = (γ/ℓ²)·√(E·J/m)Vw in km/h and d in mm. There is a risk when fc is below twice fa.
Limits of the calculation
- Static short circuit: without the dynamic factors or the plasticity factor of IEC 60865-1, without conductor swing or pinch effect.
- A single-span load that is uniform; it does not include point loads (disconnectors, connectors) or wind on the insulators.
- Earthquake, installation loads and loading-standard combinations are not calculated.
- Strung conductor with supports at the same level and parabolic approximation (sag less than 10 % of the span).
Frequently asked questions
Why is the short circuit an estimate?
The electromagnetic force comes from Ampère's law, but the response of the tube and insulators depends on the ratio between their natural frequency and the network frequency. IEC 60865-1 gives those dynamic factors; this tool does not use it and leaves them as your own data, with 1 by default (static response). The tube stress is usually on the safe side; the insulator load may fall below the real one.
When does a tube need damping?
When its first natural frequency falls within the band of vortex frequencies produced by the site's laminar wind. A long, flexible tube resonates with light winds; a short, stiff one stays out of the wind's reach.
Which insulator carries more?
The intermediate post of a continuous bus takes the load of half a span on each side, twice that of an end post. The center post of two continuous spans reaches 5/4 of the load of one span.
We design your substation busbar
We calculate the mechanical stresses, spans and insulators of your yard with your site data.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws