Choose the scheme and the medium, and type the equipment times. The tool draws the path of the command between the two substations, adds up each segment and compares it with the time the scheme allows.

Example cases
Teleprotection channel time
ALearn

E1Scheme and medium
km
ms

Criterion of your protection study.

E2Equipment
ms

From the fault to the command; relay figure.

ms
ms
ms

From the input to the trip command; relay figure.

E3Transport
µs

Estimate: use the manufacturer's figure.

ms

Estimate: it depends on the payload of the service.

ms

Estimate: equipment configuration.

µs

Estimate: use the manufacturer's figure.

E487L
ms
Hz
°

Relay figure or criterion of your study.

Use a decimal point. The calculation runs in your browser and updates as you type.

End-to-end time

—

Channel time

—

87L angle error

—

Propagation

—

From one relay to the other: each segment and its time
Above, the path of the command: control wiring in white and communications in yellow. Below, each segment as a bar; the red line is the time the scheme allows.

Time budget

What it is for

In a teleprotection scheme the command must reach the remote end before the scheme loses its speed advantage. This tool adds up the time of each device and of the medium, from the sending relay to the output of the receiving relay, and shows which segment weighs most.

The setting of POTT and blocking schemes is in the distance 21 setting tool; the optical margin of the link, in the link budget tool.

How it is calculated

Source: own derivation

Sum of segments

t = trelay + tTX + transport + L · ng / c + tRX + toutput

The transport is the sum of the SDH nodes, or the packetization plus the nodes plus the jitter buffer in IP/MPLS, or one transmitter and one receiver per radio hop.

Source: G652D cable data sheet

Propagation

fibre: L · 1.468 / c ≈ 4.9 µs/km; radio: L / c ≈ 3.34 µs/km

Source: own derivation

Asymmetry in the 87L

angle error = 360° · f · Δ / 2

The relay estimates the delay as half the round trip. If go and return differ by Δ, the remote current is compared shifted by that angle.

Limits of the calculation

  • The equipment times are the ones you type: each manufacturer declares its own.
  • It does not model the security or dependability of the channel, nor the noise of an analogue channel.
  • It does not replace the end-to-end test of the scheme. The example cases are illustrative.

Frequently asked questions

How long does light take in 100 km of fibre?

About 0.49 ms with a group index of 1.468. The time of the equipment almost always weighs more than the distance.

Why is an IP/MPLS network a concern for teleprotection?

Because it adds the time to build each packet and the buffer that absorbs the delay variation, and because go and return may take different paths. For the 87L that asymmetry becomes an angle error.

How much asymmetry can an 87L take?

It depends on the relay. Each millisecond of difference between go and return shifts the remote current 10.8° at 60 Hz and 9° at 50 Hz. Check your relay manual or use GPS synchronisation.