Home / Tools / Transformer control
Transformer control simulator
Simulate power transformer control: on-load tap changer with motor drive, regulator 90, master–follower parallel, staged cooling fans and Buchholz.
IEC 61850-7-4 Ed. 2ATCC, YLTC and YPTRIEC 60076-1:1993+A1:1999Rated power by cooling methodIEC 60076-7:2005Oil and hot-spot temperatures with the loadIEEE C37.2Device numbers 26, 49, 63, 71, 86 and 90
Results
—
—
—
—
Charts
- Rating
- Control wiring
- Live
- Rating
- Control wiring
- Live
- Rating
- Control wiring
- Live
How it was calculated and standards
Event log server
| t (s) | Signal or command | Status |
|---|
Functional tests of the control circuit
| # | Test | Acceptance criterion |
|---|---|---|
| 1 | Motor drive: raise and lower from the drive and from the SCADA, with the selector in each position | One step per command, correct direction and the command only from whoever has the authority. |
| 2 | Electrical limit switches at the highest and lowest taps | The contactor of the blocked direction does not energize and the signal reaches the regulator. |
| 3 | Running-through protection | If the step does not finish, the drive stops and alarms. |
| 4 | Regulator 90 with secondary injection: band, linear and inverse delay and blocks | It commands only outside the band, after the set delay, and does not command with the blocks active. |
| 5 | Master–follower parallel: following, tap discrepancy and coupler opening | The follower copies the tap; the discrepancy blocks and alarms; with the coupler open the follower stops copying. |
| 6 | Cooling: each temperature contact up to its contactor, and the manual selector | Each stage starts at its setting and stops with the hysteresis. |
| 7 | Buchholz, pressure relief valve, flow relay, 26, 49 and level with their test device | Each contact gives the alarm or the trip to the 86 defined by the protection philosophy. |
Replay them in the simulator with the “Test” field and with the live controls.
What it is for
The control of a power transformer brings several things together: the tap changer with its motor drive, the voltage regulator that commands it, the cooling that starts on temperature and the own protections that take it out of service.
This simulator draws them with the transformer, its motor drive and its regulator, and lets them run live: lower the network voltage, change the band, put two transformers in parallel, trip a fan or the Buchholz, and see which contact opens and which command goes out.
How it operates
- The regulator 90 compares the bus voltage with the set point. Inside the band it does nothing; outside it waits for the delay and commands one step. If the voltage returns to the band earlier, the delay restarts. With inverse delay, more deviation means less waiting.
- Each command moves a single tap: the step-in-progress contact holds the contactor until the step ends, and a held command does not give a second step. The limit switches open the contactor of the blocked direction at the highest and lowest taps.
- If the step does not finish, the running-through relay trips the drive motor protective switch. The regulator does not raise with the voltage below its undervoltage limit, does not operate on overcurrent and stays blocked if the 86 tripped.
- In master–follower, the follower copies the master tap after each step. If the taps stay different for longer than the discrepancy timer, the regulator blocks automatic control and alarms. With the coupler open the follower stops copying the master; with the coupler closed and no parallel logic the regulator blocks automatic control and alarms.
- The winding indicator contacts start the fan groups as the temperature rises and stop them with a hysteresis as it falls. Buchholz surge, pressure relief valve, tap changer flow relay and the 26 and 49 trips go to the lockout relay 86; the Buchholz gas and low level only alarm.
Limits of the calculation
- It is a principle circuit, not a manufacturer's drawing. Your motor drive, regulator and panel may have other contacts and other interlocks: compare with your drawings.
- All times, thresholds and taps are example settings. Use those of the manufacturer and the study.
- The thermal model is first order, with simplified exponents and time constants compressed to seconds. It cannot be used to calculate the permissible load.
- The parallel scheme is master–follower with two identical transformers. The circulating current and power factor methods are not simulated.
- A step already started always finishes, even if F1 opens or the motor protective switch trips; in a real drive it may stop between positions. Step-by-step operation comes from contact S13, which holds the contactor only during the step, and from the new command each step requires.
- The pressure relief valve and the tap changer flow relay trip to the 86 as usual practice; their destination is set by the protection philosophy. Some schemes also trip on very low oil level; here the level only alarms.
Frequently asked questions
Why must the band be larger than the step?
Because each step moves the voltage by a fixed amount. If the band is narrower, after the step the voltage ends outside on the other side and the regulator commands the opposite step: the tap changer hunts between two taps.
Does a held command move several taps?
No. The drive gives one step per command: the step-in-progress contact holds the contactor until the step ends, and the next one needs a new command.
What happens if the follower does not copy the tap?
A circulating current remains between the two transformers. When the discrepancy timer expires, the regulator blocks automatic control of the group and alarms.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws