Tiza Group

Home / Tools / Function 47 phase sequence

Function 47: phase-sequence voltage

Negative-sequence voltage and phase reversal: V2, V1, pickup, reset, inside the relay and a test plan for the injection kit.

IEEE C37.2§ 3.1.47function numbersIEEE C37.96§ 7.2.747 relayGE F60 1601-0093-AB2§ 5.7.10.5negative-sequence overvoltage

Example cases
Function 47: phase-sequence voltage

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings
% of phase voltage

IEEE C37.96-2000, §7.2.7, cites 5% as a common setting for a negative-sequence voltage relay.

s
s
% of phase voltage

Example model setting: the reversal is declared if V2 exceeds V1 and this value.

E3Simulation
% of nominal
% of nominal
% of nominal
E4Installation and test set
V
V

Example value: enter that of your test set.

E5Relay tolerances
%
V

The cited manual does not state an absolute minimum: enter your relay's value.

%
ms
ms
ms

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Negative sequence

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 47 checks that all three voltages arrive complete and in the right order. It trips or blocks when negative-sequence voltage appears above a value, for example with a dropped phase, or when the sequence is reversed.

It is used to avoid starting motors with a missing phase or turning backwards, and to detect an unbalanced supply on busbars and feeders.

How it operates

  • The relay calculates V1 and V2 with the symmetrical components of the three voltages, using the set rotation. With a healthy network V2 is almost zero.
  • If only phase A drops, V2 rises by a third of what that phase dropped. If two phases arrive swapped, the whole set is negative sequence: V2 equals the phase voltage and V1 is zero.
  • The reversal stage requires V2 to exceed V1; the V2 stage compares V2 with its pickup and resets below its reset ratio.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The plan looks for the V2 pickup by lowering only the phase A voltage: every volt it drops adds a third of a volt to V2. It measures the time with V2 at twice the pickup.

The reversal is tested by swapping phases B and C of the injection kit; if the V2 stage operates first, the plan asks you to block it. At the end, a healthy set must not make the reversal operate.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • Phase voltages are simulated with ideal 120° phase shifts; harmonics and VT saturation are not modeled.
  • Some relays also detect the reversal with currents; here only with voltages.
  • The minimum V2 that confirms the reversal is an example setting: the internal criterion depends on each manufacturer.

Frequently asked questions

Why does V2 rise only a third of what a phase drops?

Because V2 is the vector sum of the three rotated voltages divided by three. If only phase A changes, its change enters the sum in full and is divided by three.

What happens if the relay has the rotation set wrongly?

It sees the healthy network as reversed: V2 equals the phase voltage and the 47 trips. That is why the relay rotation must match the network's before you enable the function.

What setting is used in the V2 stage?

IEEE C37.96-2000 mentions 5% of the voltage as a common setting. It must stay above the normal network unbalance and the VT error.