Function 27TN: neutral third harmonic

The stator next to the neutral: third-harmonic undervoltage, voltage and power supervision, the relay inside and a test-set test plan.

IEEE C37.102§ 4.3.3.1.1third harmonicSEL-700G§ p. 44tolerancesIEEE C37.2§ 2008function numbers

Example cases
Function 27TN: neutral third harmonic

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings
V

Secondary third-harmonic voltage at the neutral below which it picks up. It must stay below the lowest value measured in healthy service.

s

Example value.

V

Line to line. Without excitation there is no third harmonic: the supervision prevents a trip with the machine stopped or de-excited.

In many machines the third harmonic drops at low load: the function is enabled only above a given power.

% of Sn
A
E2Settings, part two
V

Measured on your machine at the simulated load. Example value.

Estimate: fraction of the third-harmonic electromotive force that appears at the neutral with the machine healthy; the rest appears at the terminals.

%

The one the 64G tool gives; it is used to see whether the two functions overlap.

E3Simulation
%
V
% of Sn
E4Installation and test set
V
A

Only to show the primary values.

A

Example value: enter that of your test set. Points that exceed it are marked.

V

Example value: enter that of your test set.

E5Relay tolerances
%
V
%
V
%
cycles
cycles

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Coverage

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 59GN does not see ground faults next to the generator neutral, because the neutral voltage there is almost zero. The 27TN covers that part with another signal: the third harmonic the machine itself generates.

In healthy service part of the third harmonic appears at the neutral. A ground fault near the neutral short-circuits it and that voltage falls: the 27TN trips on third-harmonic undervoltage.

How it operates

  • The relay filters the third harmonic of the neutral voltage and compares it with the pickup. The closer the fault is to the neutral, the lower the voltage.
  • Without excitation there is no third harmonic, so the function is supervised by the terminal voltage; many machines generate little third harmonic at low load and a power supervision is added.
  • With the 59GN covering from the terminals and the 27TN from the neutral, together they reach 100 % of the winding if their zones overlap.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The test set injects nominal voltages at the rated frequency on VA, VB and VC to meet the supervision and a third-harmonic voltage on VX. The plan searches the pickup by lowering VX and measures the time with half the pickup and with zero.

It also searches the supervision voltage by raising the terminal voltage with VX at zero and checks that the function stays blocked at low voltage.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The spread of the third harmonic along the winding is a straight-line estimate; the real coverage comes from measuring your machine.
  • The third harmonic changes with load and reactive power: the tool takes the value you enter for the simulated point.
  • Your test set must generate 3 times the rated frequency on one output and the rated frequency on the others at the same time.

Frequently asked questions

Where does the third harmonic come from?

From the shape of the field in the air gap: the generator does not produce a perfectly sinusoidal voltage. The third harmonic is the same in the three phases, so it does not show between phases but it does between the neutral and ground.

How is the 27TN set?

By measuring the neutral third harmonic over the whole range of load and reactive power, and setting the pickup below the lowest measured value with a margin. IEEE C37.102-2006 §4.3.3.1.1 states that about 1 % of the rated voltage is needed.

Why does it need supervision?

Because with the machine de-excited or stopped there is no third harmonic and the 27TN would see an undervoltage with no fault. The terminal-voltage supervision blocks it in that state.