Type the network, the lightning protection level, the equipment you want to protect and the data of each SPD. The tool checks the Uc, the effective protection level with its leads, the distance to the equipment, the current each stage must carry at its LPZ boundary and the coordination between stages, and simulates where the flash comes in.

IEC 62305-4:2010§ C.2.1effective protection level and distance to the equipmentIEC 62305-4:2010§ C.2.2SPD class by zoneIEC 62305-4:2010§ D.3.2sharing of the lightning currentIEC 62305-1:2010§ E.2expected currents per conductorIEC 61439-1:2011§ G.1withstand voltage by categoryRETIE§ 3.17.14installation and coordination of SPDsRETIE§ 2.3.12.1.2Uc of low-voltage SPDs

Example cases
Surge protective device selection
ALearn

E1Low-voltage network
V

208 for 120/208 V, 480 for 277/480 V, 240 for the single-phase three-wire 120/240 V.

%

How much the voltage of your network may rise in steady state, according to your utility.

E2Lightning and service entrance

With air terminals and down conductors part of the direct lightning current returns through the entrance SPDs.

Power, data, pipes: they share half of the current.

4 for three phases and neutral.

E3Direct flashes (optional)

If the sum is 0.01 or less and there is no LPS, a class II SPD is enough at the entrance.

1/km²·año
m
m
m
m
E4Equipment to protect
kV

Up/f ≤ Uw/2 is required because the wave doubles.

kV

0 with shielded cable or in a metal duct.

E5Installation of the SPDs
µH/m

About 1 µH per metre of conductor.

kA/µs

With 1 µH/m and 1 kA/µs the drop is 1 kV per metre, the IEC 62305-4 value for the entrance.

m

The one the manufacturer asks for to coordinate by energy.

D1SPD 1 · entrance to LPZ 1
V
kV
kA
m
mm²
m
D2SPD 2 · LPZ 1/2 boundary
V
kV
kA
m
mm²
m
D3SPD 3 · LPZ 2/3 boundary
V
kV
kA
m
mm²
m

Use a decimal point. The calculation runs in your browser and updates as you type.

Equipment protected

—

Minimum Uc

—

Current of the entrance SPD

—

Coordination between stages

—

Section of the installation with the LPZ zones and the SPDs
  • Service entrance conductor
  • LPZ zone boundary
  • Simulated flash
Each SPD sits at the boundary of a zone: green if it complies, red if something fails. Below it, its lead a + b and its effective level. The yellow line is the flash you chose to simulate and its current at each stage.
Effective protection level of each stage against the withstand voltage
  • Up/f of the stage
  • Limit by the distance to the equipment
  • Withstand voltage Uw
Each bar is the level a stage lets through, with the drop in its leads. It must stay below its limit line, which falls with the distance to the equipment.

Stages

StageUcUp/fLimitCurrentConnection

What it is for

To choose the low-voltage SPDs of a building, a plant or the auxiliary services of a substation by lightning protection zones, and to check that the set really protects the equipment: with the drop in the leads, the distance to the equipment and the coordination between stages, as RETIE requires.

What is calculated

Source: IEC 62305-4:2010, C.2.1

Effective level and distance

UP/F = UP + L · l · di/dt; UP/F ≤ UW, ≤ 0.8 · UW up to 10 m, ≤ (UW − UI)/2 beyond

In switching SPDs the larger of UP and the drop governs. The drop is only added at the entrance, where lightning current flows; the inner stages carry induced currents.

Source: IEC 62305-1:2010, E.2; IEC 62305-4:2010, D.3.2

Current of the entrance SPD

Iimp ≥ I · 0.5 / (n · n′), and not less than that of a flash to the service entrance

I is the current of the protection level, n the services coming in and n′ the conductors of the service entrance. With level I, one service and three phases plus neutral: 25 kA per pole.

Source: RETIE, 2.3.12.1.2 b

Continuous operating voltage

UC ≥ 1.1 · Umax

Limits of the calculation

  • Energy coordination is defined by IEC 61643-12: here it is checked with the cable length the manufacturer asks for or with its declaration. It does not simulate the curve of each varistor.
  • A circuit of up to 1 m is taken as negligible, a Tiza criterion: the standard gives no figure.
  • Low-voltage AC only. Medium-voltage, data and photovoltaic SPDs have their own standards.
  • It does not replace the risk assessment of IEC 62305-2 or the manufacturer's data. The example cases are illustrative.

Frequently asked questions

Why is the entrance SPD not enough?

Because its protection level plus the drop in its leads, about 1 kV per metre, can exceed the equipment withstand voltage, and because in a long circuit the wave reflects and can double. A second SPD near the equipment lowers that level.

Which Uc do I ask for?

At least 1.1 times the maximum steady-state voltage across the SPD terminals, as RETIE requires: with 120 V and a 10 % tolerance, 145 V. In an IT system count the line-to-line voltage, because after a first earth fault the healthy phases sit at that voltage.

How are two stages coordinated?

By energy: the entrance stage must take most of the current before the next one is overloaded. It is achieved with the impedance of the cable between them or with products the manufacturer declares coordinated. RETIE requires coordinating them by energy and not only by current.