Function 68: power swing blocking

Power swing versus fault: blinders, time between them, slip, zone 1 blocking, inside the relay and a test plan for the injection kit.

IEEE C37.2§ 3.1.68function numbersGE D60 1601-0089-AB2§ 5.7.5power swing

Example cases
Function 68: power swing blocking

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings
secondary Ω
secondary Ω

It must leave out the zone you want to block and sit inside the outer blinder.

ms
pu of In
E2Settings, part two
secondary Ω
°
E3Simulation
Hz

How fast the angle between the two sources turns: 1 Hz is one turn per second.

secondary Ω
secondary Ω

Source behind + line + source at the other end.

E4Installation and test set
V
A

Example value: enter that of your test set. Points that exceed it are marked.

V

Example value: enter that of your test set.

E5Relay tolerances
%
%
cycles
%

Estimate: the GE D60 manual does not state the accuracy of the current supervision. Enter your relay's value.

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Zone 1

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

After a cleared fault or a large switching operation, the generators swing against each other and the impedance seen by a distance relay moves. If it enters a zone, the 21 would trip a healthy line.

The 68 recognizes the swing because the impedance moves slowly, and it blocks the zones while it lasts. A fault, on the other hand, makes the impedance jump at once and is not blocked.

How it operates

  • Two resistive blinders are set around the zones. The relay measures how long the impedance takes to go from the outer to the inner one.
  • If it takes longer than ΔT it is a swing: the block is issued and held while the impedance stays inside the outer one. If it takes less, it is treated as a fault.
  • The speed depends on the slip between the sources: the angle turns 360 degrees per hertz, so with more slip it crosses faster.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The plan finds each blinder by lowering the resistance with the reactance fixed, measures ΔT by jumping from the load to between the blinders, and finds the current supervision.

With the kit's state sequence, or its two-source simulation, it reproduces a slow swing in which zone 1 must not trip and a fast one in which the 68 must not block.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The impedance locus is calculated with equal sources and a purely reactive network; with different sources it is a circle, not a line.
  • The blinders are drawn as vertical lines and zone 1 as a mho; each relay has its own shape.
  • The out-of-step trip (78) and the unblocking on a fault during the swing are not simulated.

Frequently asked questions

How is ΔT chosen?

With the fastest slip you want to block: the time between blinders at that slip must be greater than ΔT. The tool shows the maximum slip that is blocked with your settings.

Why is a fault not blocked?

Because the impedance jumps from the load to the fault in one cycle, much less than ΔT. The relay sees no time between the blinders and does not declare a swing.

How is it tested with an injection kit?

With a state sequence that moves the impedance step by step at the desired speed, or with the kit's two-source simulation module. For the blinders an impedance search is enough.