Overcurrent relay coordination

Put up to six relays, reclosers and fuses in series on the same time-current plot, referred to a common voltage, with the transformer damage curve, the inrush and the faults at each bus, and check the margin between each pair over the whole fault range.

IEC 60255-151dependent-time curvesIEEE C37.112inverse curvesIEEE C57.109through-fault damage curve

Example cases
Overcurrent relay coordination
E1System and criterion
kV
s
s

D1 is the closest to the load and the last one, the furthest upstream. The preloaded CTIs are Tiza's convention; adjust them to your criteria.

D1Device 1, downstream
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

D2Device 2
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

D3Device 3
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

D4Device 4
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

D5Device 5
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

D6Device 6
kV
A
kA
kA

For definite time, in s.

A

In the same unit as Is.

s

From the manufacturer, according to the reclosing interval and the fast operations.

A and s, separated by spaces: 130:300 400:2 1000:0.2. Take them from the manufacturer's curve.

T1Protected transformer
MVA
%
%

On the transformer base; categories III and IV only.

s

Use a decimal point. The calculation runs in your browser and updates as you type.

Coordination

—

Worst margin

— s

Pairs that pass

—

Sensitivity

—

Damage curve

—

Inrush

— s

Time-current curves
  • Damage, inrush and faults F1…F6
    Time (s) against current (A) referred to the reference voltage, both on logarithmic scales. Relay curves start at 1.1 times their pickup; the fuse shows minimum melting dashed and total clearing solid; the recloser, its fast curve as a thin line. The yellow bars at the bottom are the fault range of each zone, from minimum to maximum.
    Headroom against the criterion
    • Criterion just met (headroom 0)
      For each pair, the time difference minus the CTI (or, between fuses, 75 % of the upstream melting time minus the downstream clearing time), over the fault range of the downstream zone. Above zero it passes; below, it does not. Values off the scale are not drawn.

      Operating times at each fault level

      Times in s. Recloser: fast / slow. Fuse: melting / clearing. «—»: does not operate at that current. Currents referred to the reference voltage.

      Pair-by-pair check

      What it means for coordination

        What it is for

        In a radial system, each fault must be cleared by the closest device, and the upstream one only acts if that device fails. This tool puts the relays, reclosers and fuses of one path on a single plot, from the lateral up to the substation main, with the transformer damage curve and its energization current. Use it to review existing settings before changing them, to prepare a settings proposal or to verify by hand what the coordination software gives.

        How it is calculated

        IEC 60255-151dependent-time characteristicIEEE C37.112inverse curves

        IEC: t = TMS · k / (Mα − 1) · IEEE: t = TD · (A / (Mp − 1) + B) · M = I / Is

        The same constants as the inverse-time curve calculator. The curve starts at 1.1 times Is; the instantaneous 50 operates at its time from its pickup. For definite time, the dial is the time. If the pickup is entered in secondary amperes, it is converted to primary with the CT ratio: Iprim = Isec · CTprim / CTsec.

        Referral to a common voltage

        Iref = Idevice · kVdevice / kVref

        All currents, pickups, faults and fuse points are referred to the reference voltage with the voltage ratio, as for a three-phase fault through an ideal transformer.

        Coordination criterion per pair

        Δt(I) = tup(I) − tdown(I) ≥ CTI, for Imin ≤ I ≤ Imax of the downstream zone

        IEEE 242 tabulates minimum intervals by relay technology, because the CTI must cover the breaker time, relay overtravel and a safety margin. The tool defaults to 0.3 s between relays and 0.2 s when a fuse is involved (Tiza's convention, labelled as such). A downstream fuse enters with its total clearing curve; an upstream fuse, with its minimum melting curve.

        • Between fuses: total clearing of the downstream fuse ≤ 75 % of the minimum melting of the upstream fuse, the usual rule of thumb for expulsion fuses, which covers preloading, tolerances and predamage.
        • Recloser and fuse (fuse saving): k · tfast ≤ tmelt, and the slow curve above the fuse total clearing with the fuse CTI. When fuse saving is lost only at high currents, the status is a warning and the tool shows up to which current it holds.

        Each pair is green if it passes over the whole range, yellow if the upstream device operates later but without the margin, and red if it operates first (or if the downstream fuse clearing exceeds the upstream fuse melting).

        IEEE C57.109through-fault damage curve

        Thermal: 2 pu → 1800 s · 3 pu → 300 s · 4.75 pu → 60 s · 6.3 pu → 30 s · 11.3 pu → 10 s · 25 pu → 2 s · Mechanical: I²t = K, K = 2 · (1/Z)²

        Categories of three-phase liquid-immersed transformers: I up to 500 kVA, II up to 5000 kVA, III up to 30,000 kVA and IV above. Category I follows the thermal curve, with I²t = 1250 up to 35 times (up to 300 kVA) or 40 times (up to 75 kVA). In categories II and III with frequent faults, and always in IV, the curve drops from 0.7/Z (category II, 4.08 s) or 0.5/Z (III and IV, 8 s) following I²t = K down to 1/Z at 2 s. For III and IV, Z = ZT + ZS. The points come from the tables of the SKM application guide on C57.109. With a Dyn transformer and a phase-to-ground fault on the secondary, the primary relay sees 0.58 times the per-unit current and the curve is shifted by that factor.

        The transformer protection must stay below the damage curve where it operates, and above the inrush point: common practice places it at 8 to 12 times In for 0.1 s; use your transformer's value if you know it.

        Limits of the calculation

        • It checks one radial path with three-phase faults. It does not calculate the short circuit: you enter the maximum and minimum fault of each zone. It does not cover ground faults (51N), directional relays or contributions from distributed generation.
        • The voltage referral assumes ideal transformers. For unbalanced faults through a Dyn the current seen on the primary changes; here that effect is only applied to the damage curve with the shift factor.
        • Fuse points are joined with straight lines on log-log scales; below the first point the fuse is taken as not operating and above the last one the curve is extended with constant I²t. Use points from the manufacturer's curve, with its tolerance and preloading.
        • The recloser k factor comes from its manufacturer according to the reclosing interval and the number of fast operations; the preloaded value of 1 compares the curves as they are.
        • It does not include the minimum response time of the relays, CT saturation or curve limits above 20 times pickup. Confirm each setting with the device manual.
        • The preloaded CTIs are Tiza's convention, not a value from a standard; the coordination study sets the value for each case.

        Frequently asked questions

        How is coordination between two overcurrent relays checked?

        Plot both time-current curves referred to the same voltage and compare the backup relay time with the time of the relay closest to the fault, for every fault current in the zone of the latter, from minimum to maximum. The difference must be equal to or greater than the chosen coordination time interval (CTI) over that whole range, not only at the maximum fault.

        What is the IEEE C57.109 transformer damage curve?

        It is the through-fault withstand curve of the transformer: the time it can carry each multiple of its rated current without thermal or mechanical damage. It has a thermal part (for example, 2 times rated for 1800 s and 25 times for 2 s) and, for category II to IV transformers with frequent faults, a mechanical part I²t = K calculated from the impedance. The transformer protection must stay below that curve and above the energization (inrush) point.

        How does fuse saving with a recloser work?

        The recloser opens first on its fast curve, before the lateral fuse can melt, and recloses: if the fault was temporary, service returns without replacing the fuse. If the fault persists, the recloser slow curve waits for the fuse to clear the lateral. It works as long as the fast curve, multiplied by the manufacturer's k factor, stays below the fuse minimum melting curve; at high currents that margin is lost.

        We do your protection coordination study

        We model the system, calculate the short circuit at each bus and set relays, reclosers and fuses so the one closest to the fault clears first. Then we load the settings into the relays, remotely as well.

        Other tools

        COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Inverse-time curvesCalculator and log-log plot of the IEC 60255-151 and IEEE C37.112 curves, with the coordination margin.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Per-unit base conversionBase current and impedance, conversion between %, pu and ohms, and change of base for transformers, generators and lines.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Symmetrical componentsPhase quantities to zero, positive and negative sequence and back (Fortescue), with phasor diagrams and what they mean for 46, 67Q and 51N.Vector group compensation (87T)TAP of each winding, phase compensation matrix, zero-sequence removal and the HV-to-LV clock diagram.Primary and secondary impedance (21)Primary to secondary ohms with the CT and VT ratios, line Z1, Z0 and k0, and zone reaches on the R-X plane.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.