Short-circuit current at the secondary of a transformer
Estimate the bolted three-phase fault at the secondary terminals with IEC 60909-0 or with the simple estimate, with or without the upstream source, and see the peak current with full asymmetry. It does not replace a short-circuit study.
IEC 60909-0§ 6.3.3transformer KT correctionIEC 60909-0voltage factor c, table 1IEC 60909-0peak current, factor κ
Results
— kA
— kA
— MVA
— A
—
— %
Want an engineer to review this case? Our team reviews your data and results and quotes the study or the settings work you need.
Charts
- IEC 60909-0
- Simple estimate
- Infinite bus, IEC
- Selected source
- i(t) with DC component
- Symmetrical
- Peak ip
Calculation and details
Step-by-step calculation
What it means for your equipment
What it is for
The three-phase fault at the secondary terminals is the first figure you need to choose the interrupting rating of a switchboard, check an instantaneous setting or size busbars. This tool gives a quick estimate with the IEC 60909-0 method and compares it with the simple estimate many engineers use from memory, so you can see how far short it falls.
How it is calculated
Rated current
In = Sn / (√3 · Un)IEC 60909-0§ 6.3.3KT correctionIEC 60909-0factor c, table 1
IEC 60909-0 method (maximum initial symmetrical current)
I″k = cmax · In / (KT · uk + zQ) · KT = 0.95 · cmax / (1 + 0.6 · xT)With uk = uk% / 100. The voltage factor cmax is 1.05 or 1.10 at low voltage depending on the system tolerance, and 1.10 above 1 kV. Here xT = uk, which gives the highest current. The upstream source is modelled as ZQ = cQ · UnQ² / S″kQ, which in per unit on the transformer base becomes zQ = cQ · Sn / S″kQ, with cQ = 1.10. With an infinite bus, zQ = 0. Since cmax / KT = (1 + 0.6 · xT) / 0.95, on an infinite bus the result does not depend on cmax.
Simple estimate
Ik = In / (uk + Sn / S″kQ)Without the c factor or KT, it gives 5 % to 10 % less than IEC 60909, so it is not suitable for choosing the interrupting rating. The short-circuit power is S″k = √3 · Un · I″k in both methods.
IEC 60909-0peak current
ip = κ · √2 · I″k · κ = 1.02 + 0.98 · e−3R/XThe waveform on the screen is i(t) = √2 · I″k · (e−t/T − cos ωt), with T = (X/R) / ω: the fault that starts at the voltage zero crossing, which has the largest asymmetry.
Limits of the calculation
- Bolted three-phase fault at the secondary terminals, with the transformer on the nominal tap.
- Impedances added in magnitude, without separating resistance and reactance; the X/R is used only for the peak current.
- No contribution from motors, generators or inverters on the low-voltage side, and no cable or busbar impedance up to the fault, so the value is on the high side at the terminals.
- A study per IEC 60909-0 (or IEEE 551) models the whole network, separates R and X, adds the contributions of rotating machines and converter-based generation, and also calculates the unbalanced faults. That is the result to use for specifying equipment and setting protection.
Frequently asked questions
How is the short-circuit current at a transformer secondary calculated?
The simple estimate divides the rated current by the per-unit impedance: Ik = In / (uk% / 100). IEC 60909-0 adds the voltage factor c and the K_T correction of the transformer impedance, which gives a higher value. For example, 1000 kVA, 440 V and 5.75 % give 22.8 kA with the simple estimate and 24.9 kA with IEC 60909 on an infinite bus.
What is the IEC 60909 K_T factor?
It is the impedance correction of a network transformer for the maximum-current calculation: K_T = 0.95 · c_max / (1 + 0.6 · x_T), with x_T the relative reactance. Since K_T is below 1 for usual transformers, it lowers the impedance and raises the calculated fault current.
What is the peak current ip and what is it used for?
It is the maximum instantaneous value of the fault current, DC component included: ip = κ · √2 · I″k, with κ = 1.02 + 0.98 · e^(−3R/X) per IEC 60909-0. It is used to check the making capacity of circuit breakers and the dynamic forces on busbars and supports.
We carry out your short-circuit study
We model your system with the utility data and your equipment nameplates, calculate the faults per IEC 60909 or IEEE 551, and deliver the interrupting-rating check and the protection coordination.