Enter the line, reactor and fault data: the tool calculates the secondary arc current and the recovery voltage of the open phase, the optimal neutral reactor, the estimated dead time and whether high-speed earthing switches are needed.

Geszti y Déri§ 1981secondary arc on long linesKimbark§ 1964neutral reactorIEC 60076-6§ A.4neutral reactor

Example cases
Secondary arc and single-pole reclosing
ALearn

E1Fault and reclosing
km
s

From your study or test. Leave empty if you do not have it.

E2Line
kV
km
µS/km
µS/km
Ω/km
Ω/km
A
m
E3Reactors
Mvar

0 if there is none.

Mvar
Ω

The same value in both banks. 0 equals a solidly earthed neutral.

E4Criteria
A

Indicative reference: Geszti and Déri cite 10 to 20 A at lower voltages and usual lengths. It is not a self-extinction criterion.

kV/m

Indicative reference: the highest gradient of the Hydro-Québec tests at 330 kV (7 to 18 kV/m with 10 to 40 A).

Use a decimal point. The calculation runs in your browser and updates as you type.

Secondary arc current

— A

Recovery voltage

— kV

Gradient on the insulator

— kV/m

Optimal neutral reactor

— Ω

Estimated dead time

— s

High-speed switches

—

Line with phase A open at both ends
  • Healthy phases
  • Coupling and arc
  • Open phase
Choose the moment in «Fault and reclosing» and move the fault along the line: the current fed by the healthy phases and the voltage left on phase A change.
Secondary arc and recovery voltage during the dead time
  • Arc current
  • Recovery voltage
  • Reclose
Illustrative lossless shape. With reactors, the recovery voltage beats between the power frequency and the natural frequency of the open phase.

Step-by-step calculation

What it is for

It estimates whether a single-pole reclosure will work: how much current feeds the secondary arc, what voltage remains on the open phase when the arc goes out and what gradient the insulator string sees. It calculates the neutral reactor that cancels the capacitive coupling and tells you when high-speed earthing switches are needed.

How it is calculated

Geszti y Déri§ 1981capacitor divider

Capacitive component

Ic = |ym|·V · Vr = V·|ym| / |2ym + yg| · ym = (B1 − B0)·l/3 − 1/Xpp · yg = B0·l − 1/Xpe

Circuit theoryinductive coupling

Inductive component

e = I·(X0 − X1)/3 · Ii = e·|B'·(b² − a²)/2 − b·yR + a·yS| · B' = (2B1 + B0)/3

a and b are the distances from the fault to each end; yS and yR, the admittance of each bank seen by the open phase.

Kimbark§ 1964neutral reactor

Optimal neutral reactor

Xn = Xp² / (1/Bm − 3·Xp) · Bm = (B1 − B0)·l/3

Empirical ruleestimate

Dead time

tdead ≥ textinction + (10.5 + kV/34.5)/60 s

Limits of the calculation

  • Transposed single-circuit line with lumped parameters: lines over 30 electrical degrees or double-circuit lines need an EMTP study.
  • The capacitive and inductive components are added in the worst case; their real angle depends on the load flow.
  • The arc extinction time is not calculated: it comes from a study or tests. Wind, arc length and the primary fault current change it.
  • The duties the high-speed earthing switch must withstand are calculated with circuit theory; its class comes from the manufacturer.

Frequently asked questions

What is the secondary arc?

It is the arc that remains at the fault after opening the phase at both ends. The healthy phases feed it through the phase-to-phase capacitance and the mutual inductance. If it does not go out before reclosing, the breaker recloses onto the fault.

Why does the neutral reactor reduce the secondary arc?

Because the reactor bank with a neutral reactor is equivalent to phase-to-phase reactors that cancel the phase-to-phase capacitance. Without that coupling, the capacitive component of the current and of the recovery voltage almost disappears.

When are high-speed earthing switches needed?

When, even with the best possible compensation, the arc current or the recovery voltage gradient stays high. The switches earth the open phase at both ends, the arc loses its current and goes out; then they open and the breaker recloses.

We study the reclosing of your line

We calculate the secondary arc and set the single-pole reclosing with the data of your line.