Transformer winding resistance
Enter the readings of each tap and of the LV: the tool draws where the four test set leads go, corrects to the factory temperature, calculates each delta winding and compares between phases, against factory, against a sister unit and between taps.
IEC 60076-1:1993+A1:1999§ 10.1, 10.2reference temperature and measurementUSBR FIST 3-31:2003§ 15.1, 15.2, T8field criterion
Results
—
—
—
—
Charts
- Pair 1
- Pair 2
- Pair 3
- Factory
How it was calculated and standards
Test planPro
Results sheetPro
Step-by-step calculation
What it measures
The test measures the DC resistance of each winding at each tap of the tap changer. It finds loose connections at the bushings or the tap changer, broken strands and tap changer contacts with extra resistance.
A value on its own does not say whether the winding is sound. It is compared between phases, against the factory values corrected to their temperature, or against a sister unit measured at the same temperature.
How it is connected
The test set (a micro-ohmmeter or winding ohmmeter) has two current leads, I+ and I−, and two voltage leads, V+ and V−. All four go to the same two terminals: I+ and V+ to one, I− and V− to the other, with the voltage clips inside the current clips. That way the voltage drop in the current leads does not enter the reading.
In a wye with neutral, each reading goes from the phase bushing to the neutral. In a delta, between each pair of bushings. A wye without a neutral bushing is measured between pairs, like a delta. The other terminals are left floating and the tank is grounded. The first reading is taken with the tap changer in the position it was found.
Corrections
To compare with the factory, the reading is taken to the reference temperature: Rs = Rm·(Ts + Tk)/(Tm + Tk), with Tk = 234.5 °C for copper and 225 °C for aluminium. IEC 60076-1 uses 75 °C for oil-immersed transformers.
The winding temperature (Tm) is taken as the mean of the top and bottom oil temperatures, with the transformer de-energized for at least 3 h. If you have the winding temperature, enter it and the tool uses it instead of the oil.
In a delta, each reading is one winding in parallel with the other two in series. The tool calculates the resistance of each winding from the three readings (equivalent wye); if they are equal, R = 1.5 × reading.
How to interpret it
USBR FIST 3-31 accepts a difference of up to 5 % between phases, from the factory or from a sister unit. Its Table 8 lowers the transformer's condition score between 5 % and 7 % and between 7 % and 10 %, and above 10 % asks for an evaluation before energizing.
The difference between phases is calculated as (highest reading − lowest reading)/lowest reading, among the three readings of the same tap.
A defect that shows at every tap of one phase points to the bushing, its connection or the winding. One that shows at a single tap points to the tap changer contact at that position: that is why the tool also checks that the tap step is regular (Tiza convention, 25 % of the median step).
After this test the core is left magnetized by the direct current. FIST 3-31 warns that this spoils the excitation current test: run it first, or demagnetize the core before measuring it.
Tool limits
- Two-winding transformers in wye or delta with five taps on the HV side; zigzag windings and autotransformers are out of scope.
- The factory value is entered in the same quantity as the reading (between the same terminals) and at the reference temperature; one per tap, for the three pairs.
- The tap-step criterion is a Tiza convention for a linear tapped winding; with a reversing selector or uneven tap steps, check the result against the factory test report.
- IEC 60076-1 edition 1993+A1:1999 was used; the edition in force is 2011.
Frequently asked questions
How much difference between phases is acceptable in winding resistance?
The USBR FIST 3-31 manual accepts a difference of up to 5 % between phases, from the factory or from a sister unit. Between 5 % and 10 % it lowers the transformer's condition score, and above 10 % there may be a serious problem that is evaluated before energizing.
Why is the reading between two bushings of a delta not the resistance of one winding?
Because between two bushings there is one winding in parallel with the other two in series. If the three are equal, the reading is 2/3 of one winding; the tool calculates each winding from the three readings.
Does the resistance need a temperature correction?
Only to compare it with the factory, which gives it at its reference temperature (75 °C for oil-immersed transformers per IEC 60076-1). To compare phases with each other, all are at the same temperature and no correction is needed.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws