Home / Tools / CT and VT selector
Protection CT and VT selector and checker
Choose CT or VT. For the CT, enter the function, the fault current, the X/R and the CT and cable data: the tool calculates the saturation voltage needed, proposes the class, checks the effective ALF and the time to saturate with offset and remanence, and gives you the longest cable. For the VT it checks the burden and the cable.
IEC 61869-2:2012§ 5.6.202P and PX protection CT classesIEEE C37.110-2007§ 3.21, 7.1CT application in protectionIEC 61869-3:2011§ 5.6.302.3Protective VTsIEC 60044-1:1996+A1:2000§ 12, 13, 14old classes P, PR and PXAlstom NPAG§ 6CT and VTSiemens 7UT6x§ D.1Ktd of its differential
Results
—
—
—
—
Charts
- Actual current
- Ideal current
- Excitation curve (illustrative shape)
- Characteristic voltages
How it was calculated and standards
Step-by-step calculation
Loading these settings into a relay? We configure it remotely.
What it is for
Every protection setting depends on the CT delivering a faithful current while the function makes its decision. This tool starts from the fault current, the X/R and the real secondary burden (winding, cable and relay) and calculates the saturation voltage the CT needs. With that value it proposes the class, verifies the CT you already have and gives you the maximum cable length.
It extends the “CT saturation” and “CT burden” tools, whose engines it uses without copying them: the voltage each class delivers, the time to saturation and the burden per connection. For the voltage transformer, it checks that the connected burden, including cable loss, is within the range where the class is guaranteed.
How it is calculated
Alstom NPAG§ 6.4.10.1transient factor SEL CPRE 2021Eq. 14
Required saturation voltage
Vsat ≥ K · Krem · (If/N) · (RCT + Rb)If/N is the secondary fault current, RCT the winding resistance and Rb the external burden (leads according to the connection, relay and others). K is 1 without offset (the overcurrent criterion of IEEE C37.110-2007, 7.1, together with the time-to-saturate check), 1 + X/R to never saturate with a fully offset current (NPAG and SEL), or the Siemens 7UT6x Ktd: 3 for transformers, busbars and lines and 5 for generators and motors. Krem = 1/(1 − remanence), the criterion of the saturation tool; it is not applied with the Siemens Ktd. It is a saturation voltage (EALF for class P, Vx for class C), not the knee-point voltage.
IEC 61869-2:2012§ 5.6.202ALF voltage SEL BKPclass C
Voltage each class delivers
P: EALF = ALF · In · |RCT + Zb| · C: 20 · In · |RCT + Zstd∠60°| · PX: EkThe rated ALF and the rated burden on the nameplate give the accuracy limit voltage. The effective ALF with the real burden is that voltage divided by In·(RCT + Rb). The tool looks for the lowest standard ALF (5, 10, 15, 20, 30) or the lowest class C that reaches the required voltage; if none does, it asks for a PX CT with Ek equal or higher, which is on the safe side because the knee point lies below saturation.
IEEE C37.110-2007§ 4.5.2time to saturation
Time to saturation with DC offset
ts = −T · ln(1 − (Ks(1 − λ) − 1)/(X/R)) · T = (X/R)/ωKs is the ratio between the available voltage and the voltage that the symmetrical current produces, and λ the remanence. If Ks(1 − λ) exceeds 1 + X/R, the CT never saturates; if it is below 1, it saturates with symmetrical current. Modern differential relays need a short time without saturation.
Alstom NPAG§ 6.4.8cable burden SEL BKPout and back
Cable burden and maximum length
Lmax = (Vd/(K·Krem·If,s) − RCT − Rrelay − Rothers) / (kL · rkm)kL is 2 for a phase-to-ground fault with wye-connected CTs (the cable is traversed out and back) and 1 for a three-phase fault; rkm is the copper resistance at the conductor temperature. SEL recommends limiting cable resistance to 0.5 Ω or less.
CT and VT classes
For class 5P, the NPAG gives a current error of ±1 % and a phase displacement of ±60 minutes at rated current, and a composite error of 5 % at the accuracy limit; for 10P, ±3 % and 10 %. The standard ALF values are 5, 10, 15, 20 and 30. Class PX is defined by knee-point voltage, excitation current and winding resistance; in the IEC definition, a 10 % increase in voltage requires 50 % more excitation current.
For a CT already installed, the «Plate of an existing CT» panel translates its plate into IEC 61869-2:2012. A 5P or 10P plate of IEC 60044-1 keeps its designation, except below 5 VA: the old standard allowed the composite error to be proven at a power factor between 0.8 and 1 and the new one requires 1 below 5 VA, so the guaranteed voltage may fall to a lower ALF. A PX stays PX; it is PXR only if a remanence of 10 % or less was proven, and it is equivalent to 5P or 10P at a given burden when the limiting voltage does not exceed Ek and its exciting current meets the indirect test. A class C is converted with its voltage Vx at 20 times In and an estimated knee: that conversion is an estimate.
For protective voltage transformers, the NPAG gives class 3P with ±3.0 % and ±120 minutes and class 6P with ±6.0 % and ±240 minutes, with the burden between 25 % and 100 % of rated and power factor 0.8. IEC 61869-3:2011 (5.6.302.3) adds burden range I, from 0 to 100 % at power factor 1, and its clause 5.302 sets the voltage factor: 1.2 continuous between phases; 1.5 for 30 s phase to earth with an effectively earthed neutral; 1.9 for 30 s with a non-effectively earthed neutral and automatic tripping; 1.9 for 8 h with an isolated or resonant neutral without tripping.
Limits of the calculation
- The distance-function factors of each manufacturer could not be verified: the conservative full DC offset criterion is used and the result is labeled an estimate. No formula was consulted for ABB RET, REL and REB670.
- The limits of the TPX, TPY and TPZ classes (peak error, remanence, time constant) were not consulted: the tool does not calculate them. Request them with the data from the stability study and the reclosing cycle.
- Remanence is handled with the 1/(1 − λ) factor from the saturation tool. In generators, avoiding asymmetric saturation is usually impossible, even with large CTs (SEL): use identical CTs and a relay with saturation detection.
- The rated burden of class P CTs combines vectorially at a 0.8 power factor; class C, at 0.5. Nameplate and test-report data take precedence over any typical value.
- For VTs the tool checks the burden against its range, the cable and the voltage factor. The cable voltage drop is compared with 0.5 %, a criterion of this tool.
- The equivalences of IEC 185, BS 3938 and the IEEE C, K, H and L classes are estimates: those standards were not consulted, and the IEEE classes are defined by the ratio error and the terminal voltage, not by the composite error and the e.m.f. The shape of the drawn excitation curve is illustrative, anchored at the plate points; the measured curve prevails.
- It does not replace the CT manufacturer's calculation or the relay manufacturer's sizing program (for example, Siemens CTDIM).
Frequently asked questions
How is the saturation voltage a CT needs calculated?
Multiply the secondary fault current by the total circuit resistance (CT winding, leads and relay) and by a factor. For overcurrent, IEEE C37.110-2007 (7.1) uses the symmetrical current and asks to check the time to saturate of instantaneous elements. To never saturate with a fully offset current the factor is 1 + X/R (NPAG and SEL), and with remanence it is also divided by (1 − remanence). Siemens, for its 7UT6x differential, uses a Ktd of 3 for transformers, busbars and lines and of 5 for generators and motors. The result is a saturation voltage, not the knee-point voltage: IEEE C37.110-2007 (3.21) tells them apart.
Is a 5P20 CT enough for protection?
It depends on the fault current, the X/R and the real burden. A 5P20 guarantees a 5 % composite error up to 20 times rated current with its rated burden; with more burden or with DC offset the CT saturates earlier. The tool calculates the effective ALF with your real burden and tells you which ALF or knee point you need; if not even ALF 30 is enough, you need a class PX CT: the tool asks for a knee point equal to the calculated saturation voltage, which is on the safe side.
What IEC class is a C400 CT equivalent to?
There is no exact equivalence, because IEEE defines class C by a 10 % ratio error and the terminal voltage at 20 times rated current, and IEC by the composite error and the e.m.f. As an estimate, a 5 A C400 gives its saturation voltage with 20 times In into 4 Ω, which the tool compares with a 10P at the burden you choose; for the 5P it uses an estimated knee, because IEEE C37.110-2007 (4.5.3) states that the knee is usually between 50 % and 75 % of the class voltage. If you use a tap, the class drops in proportion to the turns.
How does the secondary cable affect it?
The cable adds its resistance to the CT burden. In a phase-to-ground fault with wye-connected CTs, the current goes out and back through the cable, so twice the length counts; in a three-phase fault, once. At 1 A the cable burden is 25 times lower than at 5 A for the same resistance. The tool calculates the maximum cable length that keeps the CT from saturating.
We review the sizing of your CTs
We calculate the saturation voltage and burden for each function, check saturation with your fault current and set your protection remotely, with no travel.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws