Tiza Group

Home / Tools / 87T compensation

Vector group compensation for the 87T

Choose the transformer vector group, its rating, its voltages and the CTs on each side. You get the TAPs, the compensation matrix of each winding, whether zero sequence must be removed, and a check that through load leaves no differential current.

IEC 60076-1vector group, clock notationIEEE C37.91phase and zero-sequence compensation

Example cases
Vector group compensation for the 87T
E1Transformer
MVA
kV
kV
E2HV side, winding 1
A
E3LV side, winding 2
A

Phase-to-phase voltages. The path to ground follows the vector group automatically (YN, yn or zn); also mark it if there is a grounding transformer between the transformer and its CTs.

Use a decimal point. The calculation runs in your browser and updates as you type.

Relay matrices, HV and LV

—

HV TAP

— A

LV TAP

— A

TAP ratio

—

LV phase shift

— °

Zero sequence

—

Clock diagram of the voltages
  • HV (A at 12 o'clock)
  • LV
Phase-to-neutral voltages in clock notation, ABC rotation. LV phase a points to the clock number of the group.
Compensated currents, through load
  • Compensated HV
  • Compensated LV, inverted
Rated through load in per unit of TAP. With the right compensation the two stars match and the differential current is zero.

Compensation matrices

Step-by-step calculation

What it means for the settings

    What it is for

    The 87T differential compares what goes into the transformer with what comes out. Before subtracting, the relay must correct three things that are not faults: the magnitude difference between HV and LV currents, the phase shift of the vector group and the zero sequence that exists on only one side. This tool reproduces those three corrections so you can check relay settings, prepare a stability test or find out why an 87T tripped on an external fault.

    How it is calculated

    Rated current and TAP

    In = S / (√3 · U) · TAP = S[MVA] · 1000 / (√3 · U[kV] · CTR) · C

    CTR is the CT ratio (primary / secondary) and C = 1 for wye-connected CTs or √3 for delta-connected CTs. This is the form used by SEL manuals, among others. The TAP is the secondary current the relay sees at rated power; it is also shown in per unit of the CT rated current. The factor In,CT / In,obj is the same idea expressed the way other manufacturers ask for it.

    IEC 60076-1clock notationIEEE C37.91numerical compensation

    Compensation matrix

    Mij = (2/3) · cos(m · 30° + (j − i) · 120°), with i, j = 1, 2, 3

    The group number is the clock position of the LV voltage when the HV voltage is at 12 o'clock: LV lags by h · 30°. Matrix m rotates the positive sequence by m · 30° counterclockwise and removes zero sequence. For m = 1 it is 1/√3 · [1 −1 0; 0 1 −1; −1 0 1]; for m = 11, 1/√3 · [1 0 −1; −1 1 0; 0 −1 1]; for m = 12, 1/3 · [2 −1 −1; −1 2 −1; −1 −1 2], which does not rotate but removes I0. Matrix 0 is the identity and lets zero sequence through. IEEE C37.91 describes this compensation; the actual matrices are those of the manufacturers' manuals (SEL calls them CTC(m)).

    Compensated side

    If LV is compensated, its matrix is m = h and HV stays at 0; if HV is compensated, its matrix is m = 12 − h and LV stays at 0. A side that does not rotate but has a path to ground gets m = 12. In automatic mode the side with a path to ground is compensated, or the wye side if neither has one, which is the practice SEL recommends, because any matrix with m ≠ 0 also removes zero sequence.

    Check

    The tool simulates rated through load with positive and negative sequence, compensates it with the chosen matrices and checks that the HV plus LV sum is zero in all three phases. The TAP indicators turn yellow if the TAP ratio exceeds 7.5 or if a TAP falls outside 0.1 to 6.2 times the CT rated current: these are Tiza reference limits for an SEL-387 type relay; confirm the limits of your relay in its manual.

    Limits of the calculation

    • It assumes ABC phase rotation, CTs with polarity toward the transformer on both sides and a two-winding transformer. With ACB rotation the direction of the shifts is reversed.
    • The TAP is calculated at rated voltage; with a tap changer, the error at the extreme tap is covered by the relay slope.
    • With delta-connected CTs the wiring does the compensation and the relay must stay at 0: check that the delta (DAB or DAC) matches the vector group, because the wrong delta leaves a 60° error.
    • The rotation convention is SEL's. GE and Siemens ask for the vector group directly, and some relays number clockwise: check the numbering of your relay.
    • It does not replace the relay manual or the settings study, which sets the slopes, minimum pickup and harmonic blocking.

    Frequently asked questions

    Which compensation matrix does the 87T use for a Dyn1 transformer?

    With the usual practice of compensating the grounded-wye side: the delta side has no compensation (identity matrix) and the wye LV side gets the matrix that advances 30° and removes zero sequence, which SEL calls CTC(1): 1/√3 · [1 −1 0; 0 1 −1; −1 0 1]. Other manufacturers ask for the vector group directly and build the equivalent matrix internally.

    Why must zero sequence be removed in a transformer differential?

    Because on the side with a grounded neutral, an external ground fault drives zero-sequence current that does not appear on the other side of the transformer (for example, it circulates inside the delta). The 87T would see that current as differential and trip for a fault outside its zone. That is why I0 is subtracted on the side with a path to ground.

    How is the TAP of a transformer differential calculated?

    It is the secondary current that reaches the relay at rated power: TAP = MVA · 1000 / (√3 · kV · CTR), multiplied by √3 if the CTs on that side are delta-connected. With the two TAPs the relay brings the currents of both sides to the same base; many relays calculate it themselves from the rating, the voltages and the CT ratios.

    We set up your transformer differential

    We review the vector group, the CTs and the 87T settings and load the configuration into the relay remotely. If you need it, we also do the stability test and commissioning on site, in Colombia or elsewhere on request.

    Related guides

    Other tools

    COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Relay coordinationUp to six relays, reclosers and fuses on a log-log plot, with the IEEE C57.109 damage curve, inrush and the coordination margin of each pair.Inverse-time curvesCalculator and log-log plot of the IEC 60255-151 and IEEE C37.112 curves, with the coordination margin.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Per-unit base conversionBase current and impedance, conversion between %, pu and ohms, and change of base for transformers, generators and lines.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Symmetrical componentsPhase quantities to zero, positive and negative sequence and back (Fortescue), with phasor diagrams and what they mean for 46, 67Q and 51N.Primary and secondary impedance (21)Primary to secondary ohms with the CT and VT ratios, line Z1, Z0 and k0, and zone reaches on the R-X plane.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.