Home / Tools / P-Q capability test
P-Q capability test
Enter the points measured in the test, with the target and measured reactive power, the voltage and the time held, and the data of the measurement chain. The tool draws the plant with the test signals, compares each point with the declared and the reference curves, and checks the coverage, the 90 % of Pn rule and the content of the report.
CNO Agreement 2153 of 2026§ art. 4 to 6, Annex 1test on the STN and STRCNO Agreement 1910 of 2024§ art. 4 to 6, Annex 1test on the SDLCREG 060 of 2019§ art. 14 breference curve
Results
—
—
—
—
—
—
Charts
- Declared
- Band
- CREG 060 (art. 14 b)
How it was calculated and standards
Point-by-point evaluation
| # | Region | P | Q target | Q meas. ± error | Band from | CREG 060 | V | t | Result |
|---|
Test report checklist
| Content | Status | Source |
|---|
What it is for
Before entering operation, a solar or wind plant shows the CND, or the grid operator on the SDL, that it delivers and absorbs the reactive power of the curve it declared. An auditor reviews the test and its report. This tool runs that review with your data: each measured point against the declared value and the reference curve, the error of the measurement chain, the coverage of the test and what the report must contain.
Use it to plan the points before the test, to read the results on the day and to review the auditor's report before sending it.
How it is calculated
CNO Agreement 2153 of 2026§ Annex 3 §5measurement error
Measurement chain error
Emr = √(ECT² + EVT² + ER²) · Ema = √3 · Emr · Iprim · VprimEach error is taken equal to the accuracy class of the device; the recorder's as the sum of its reading error and its range error, the most conservative reading. Ema is the absolute error of the reactive power in Mvar.
CNO Agreement 2153 of 2026§ art. 6, Annex 1 §5tolerances
When a point passes
|Qmeas| + Ema ≥ |Qtarget| · (1 − 1 %)The measurement rectangle, the average reactive power plus or minus the error, must touch the 1 % band of the declared curve. If it falls short, the point still passes when it goes beyond the reference curve, and the curve to declare is adjusted. A point the grid did not let the plant reach, once the set points are exhausted, is declared compliant. Each point is held at least one minute.
CREG 060 of 2019§ art. 14 breference curve
Reference curve on the STN and STR
Qref(P) through (0.1; 0.1), (0.2; 0.33), (0.95; 0.33) and (1.0; 0.228) in multiples of PnBelow 10 % of Pn there is no reactive power requirement, but the plant must not exceed 5 % of Pn. That is why the minimum-output point, when it is below 10 %, is tested with a 10 % of Pn set point and must stay limited to 5 %.
CNO Agreement 2153 of 2026§ art. 5 and 6coverage
Coverage and the 90 % rule
3 + 3 points · Pmax ≥ 0.9 · PnAt least three points per region, at the minimum stable output, at an intermediate value and at rated power. If the plant reaches 90 % of Pn but not Pn, the test succeeds with operation records above 90 %, or with the manufacturer data sheet and the model; in that case there are 12 months to send the pending points.
Limits of the calculation
- On the SDL the reference curve is the one of CNO Agreement 1531 of 2022, which is not in the tool: points that fall short of the declared value stay pending. The CREG 060 curve is drawn for comparison only.
- The alternative of a P-Q curve adjusted with the Q-V curve of CNO Agreement 1546 is not calculated: it stays pending.
- The measured reactive power must already be averaged and corrected to the test voltage with the declared Q(V) family of curves. The tool does not have that family; it only warns when the voltage leaves 0.9 to 1.1 p.u.
- The agreements do not say what the 1 % band is taken from. It is taken from the reactive power of each declared point, the narrowest choice; change it in Advanced mode. A measured reactive power beyond the declared value counts as reaching it.
- The level of each point (minimum stable output, intermediate or rated) is set by its power: rated from 90 % of Pn, and minimum up to 5 % of Pn above the minimum stable output.
- CREG 101 104 of 2026 (art. 8) rewrote numeral 7.7 of the Código de Operación: before commercial operation, STN and STR plants send the CND the results of the capability curve test of literal b of numeral 5.7, the same CREG 060 curve the tool uses.
- On the SDL, CREG 101 104 of 2026 modified numeral 11.3.7 of CREG 070: the capability curve test is run when the CNO agreement identifies it as necessary, the results go to the CND and the OR, and an independent third party runs it and delivers a detailed report. CNO Agreement 1910 predates that change.
- The tool warns when a point's voltage leaves the normal range: 0.9 to 1.1 p.u. (1.05 p.u. at 500 kV) per numeral 5.1 of the Código de Operación for 110 to 500 kV buses, and numeral 6.2.1.1 of CREG 070 for the SDL and STR buses below 110 kV. CNO Agreement 1214 of 2019, which sets the range for reporting the curve, is not in the tool.
- Resolutions CREG 229 of 2021 and 101 098 of 2026 are not in the tool: self-generators without surplus export and embedded generators have their own rules, not checked here.
- The target Q of each row is compared at the measured P, as if it were the planned P. If the plant settled at another P, enter the declared Q interpolated at that P.
- As of 10 November 2026 CNO Agreement 1910 applies; check whether the CNO updated it after CREG 101 104.
Frequently asked questions
How many points must be tested on the capability curve?
At least three delivering reactive power and three absorbing it, at the minimum stable output, at an intermediate value and at rated power. If the curve has more vertices, testing all of them is recommended. Each point is held at least one minute in voltage control and then in reactive power and power factor control.
What if the plant does not reach rated power on the test day?
If it reaches 90 % of Pn or more, the test can succeed: with operation records showing the reactive power above 90 %, or with the manufacturer data sheet and the plant model; in the latter case there are 12 months to send the missing points. Below 90 % it is not successful, and the agent has six attempts.
How is a measured point judged to pass?
The held reactive power is averaged, corrected to the test voltage, and the absolute error of the measurement chain (CT, VT and recorder) is added and subtracted. If that rectangle touches the 1 % band of the declared curve, the point passes. It also passes when it lies between the declared value and the reference curve, and then the curve to declare is adjusted.
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codePPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws