Home / Tools / Disconnector and switchgear tests
Disconnector and GIS switchgear tests
Choose the equipment, outdoor disconnector or GIS compartment, and the test. Each sheet draws the equipment with the test-kit connection. Type your readings: the tool corrects them, compares them with the criterion and its source, and builds the plan with the results sheet.
USBR FIST 3-16§ 2.4contact resistanceUSBR FIST 4-1B§ 29.0disconnect switches
Results
—
—
—
—
—
—
Charts
- Current
- Measured
- High voltage
- Ground
Test plan and results sheet
| Test | Point | Criterion | Measured | Status | Against previous | Source |
|---|
How it was calculated and standards
What it is for
To prepare and review the field tests of an outdoor disconnector or of a GIS compartment. Each test opens on the drawing of the equipment with the test kit connected, so you see which lead goes to which terminal, what is energized and what is measured.
With your readings, the tool corrects for temperature, compares with the criterion and its source, follows the trend against the previous test and builds the test plan with the results sheet for the report.
What each test measures
USBR FIST 3-16§ 2.4contact resistance
Contact resistance
R = UP1−P2 / IC1−C2 · Rref = R · (k + Tref)/(k + T), k = 234.5 copper, 225 aluminiumIt is the resistance of the current path of the pole: pads, blade, hinge and fixed and moving contacts. A high value points to worn, dirty or low-pressure contacts, and heats the pole under load.
Resistance of a joint
That of a bolted joint, for example the line connector on the terminal pad. It is compared with your specification, with the other similar joints and with the previous test measured at the same place.
Applied voltage
It checks that the insulation withstands the test voltage for the set time without disruptive discharge. In a GIS it reveals particles, transport damage and assembly errors before energizing.
SF6 gas
p20 = p(ρ, 20 °C) with ρ = ρ(pread, Tgas), real gasGas pressure changes with temperature, but the insulation depends on the density. That is why the reading is taken to 20 °C at constant density, as a compensated density monitor does, and compared with the nameplate alarm and lockout. Moisture and purity complete the check.
USBR FIST 4-1B§ 29.0disconnect switches
Disconnector mechanism
The closing and opening times are compared with the manufacturer's range. It also checks that the three blades close together, that the travel is complete, that the mechanical latch holds the closed position and that the interlocks work.
Criteria and sources
- Resistance: the manufacturer's maximum governs. Without it, as an estimate, twice the factory value; without either, no pole more than 50 % above the lowest. Test current of at least 100 A. These are the criteria of FIST 3-16, section 2.4, written for circuit breakers.
- Joints: the maximum of your specification. Without it, the tool shows how far each joint is from the lowest and the change against the previous test, with no pass or fail.
- Applied voltage: the voltage and the duration are those of your specification. Without a typed duration, 1 min is used as an estimate, the time Shi et al. (2015) describe for the on-site test of a GIS.
- SF6: the pressure at 20 °C against the manufacturer's alarm and lockout. Moisture and purity: the manufacturer's limit or, as an estimate, those of section 5.2 of SDI 545 (Endeavour Energy, 2014).
- Mechanism: the manufacturer's time range and the checks of section 29.0 of FIST 4-1B.
Tool limits
- It does not use the IEC 62271 or IEEE C37 standards: their values are not in the tool. Type those of your specification when you have them.
- The temperature correction assumes a path of one metal. With silver-plated or mixed contacts it is approximate.
- In a GIS with both earthing switches grounded, the path through the enclosure can end up in parallel with the contact and lower the reading.
- The tool does not replace the site safety procedure or the manufacturer's instructions to connect and remove the grounds.
Frequently asked questions
What contact resistance is acceptable for a disconnector?
The one the manufacturer gives for that model. Without it, the tool uses as an estimate the criterion FIST 3-16 applies to circuit breakers: no more than twice the factory value, or no pole more than 50 % above the lowest. The comparison with the previous test completes the reading.
Why does the micro-ohmmeter have four leads?
Two carry the current and two measure the voltage. The voltage leads go inside, closer to the contact, so the drop in the current clamps and in the leads does not enter the reading.
How is the resistance of a GIS measured if the conductor is inside the enclosure?
Through the earthing switches: both are closed and the ground link of one of them, the one with the insulated terminal, is removed. The current then runs through the conductor and the contacts with no parallel path through the enclosure.
What voltage is applied in the on-site test of a GIS?
The one set by the project specification or the manufacturer, which you type in the tool. The test is done phase by phase, with the other phases to the enclosure, and it passes if there is no disruptive discharge during the test time.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws