Home / Tools / Excitation current
Transformer excitation current
Enter the test voltage and the current of each phase at each tap: the tool draws the UST connection for the vector group, compares the two higher currents with the FIST 3-31 criterion, and checks the centre-leg pattern and the comparison with the previous test.
USBR FIST 3-31:2003§ 8.3rule of the two higher currentsMegger ZM-AH02E:2010§ Table 3.3UST connection
Results
—
—
—
—
Charts
- Phase A
- Phase B
- Phase C
How it was calculated and standards
Test planPro
Results sheetPro
Step-by-step calculation
What it measures
The excitation current is the current an HV winding draws with the other winding open. It is the current that magnetizes the core. Shorted turns, a poor tap changer contact, shorted core laminations or a loose connection raise it.
One phase is measured at a time, at each tap, at rated frequency and with a voltage of up to about 10 kV. The test set gives the current in milliamperes and, if it can, the losses in watts.
How it is connected
The measurement is made in UST: the test set high-voltage lead goes to one end of the HV winding and the red measuring lead to the other. The test set counts only the current returning through the red lead. The tank and the test set chassis go to the substation ground.
On a wye with neutral each line terminal is measured against H0, with the HV neutral disconnected from ground. On a delta each winding is measured between its two terminals and the third terminal is grounded. The LV side is left floating, except its wye neutral, which stays grounded as in service.
On an HV wye without a neutral bushing there is no access to a single winding: the tool draws the measurement between two line terminals, with the third one floating. Follow your test set manual for that connection.
Corrections
The excitation current is not corrected for temperature. Nor is it proportional to voltage: only readings taken at the same voltage are compared. That is why the tool asks for a single test voltage for every tap and phase.
The test goes before any DC test. The residual magnetism left by the winding resistance test raises the current and changes the pattern between phases.
How to interpret it
USBR FIST 3-31 compares the two higher currents: less than 10 % difference below 50 mA and less than 5 % from 50 mA. The tool uses the higher of the two to pick the limit and does not accept a difference equal to the limit.
On a three-legged core the normal pattern is high, low, high: the centre-leg phase needs less current because its magnetic path is shorter. An outer phase lower than the centre one, or a phase that rises at every tap, is checked with the ratio and winding resistance tests.
Against the previous or factory test, at the same voltage, the tool flags a change of 10 % or more for review. This is a Tiza convention: FIST 3-31 asks for the comparison but gives no number.
Tool limits
- Only two-winding transformers in wye or delta; zigzag windings and autotransformers are out of scope.
- The high, low, high pattern is judged only on three-legged cores. On five-legged, shell-type cores or banks of single-phase units the tool shows the pattern without judging it.
- On a wye without a neutral bushing the tool draws the measurement between two line terminals, with two windings in series. Make that connection as your test set manual says.
Frequently asked questions
What difference is accepted between the phase excitation currents?
The USBR FIST 3-31 manual compares only the two higher currents. Below 50 mA their difference should be under 10 %; from 50 mA, under 5 %. The third phase, on the centre leg, is usually lower.
Why is the excitation current measured before the winding resistance?
Because the direct current of the winding resistance test leaves residual magnetism in the core, and with it the excitation current reads higher and uneven. If a DC test has already been made, the core must be demagnetized first.
What is done with the third terminal of a delta winding?
It is grounded. The second winding that reaches the energized terminal then takes its current to ground without passing through the measurement, and the third is left with no voltage: the test set measures a single winding.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws