Home / Tools / Insulation co-ordination
Insulation co-ordination of a substation
Choose the highest voltage for equipment (Um), the altitude and the earth-fault factor, and enter the data of the arrester, the line and the separation: the tool calculates the required withstand voltages, selects the standard level, checks the arrester Uc and Ur, and gives you the maximum distance to the equipment and the minimum insulator creepage.
IEC 60071-1:2006§ 5.9.1, tabla 2standard levels of range IIEC 60071-2:1996§ 2.3, 3.3, 4.2.2, 4.3.4, anexo Fapplication guideIEC 62271-1:2017§ 4.2.2altitude of switchgearSiemens 2012§ pp. 38, 105metal-oxide surge arresters
Results
— kV
— kV
— kV
— kV
—
— kV
—
— m
— m
— kV
— kV
— kV
— mm
Charts
- Lightning surge
- Chosen level
- Other levels of the Um
- External
- Internal
- Chosen BIL
- Chosen level
- Your insulator
How it was calculated and standards
Step-by-step calculation
Standard levels of the chosen Um
Need it for a real project? We carry out the full study, with its report.
What it is for
When you specify the equipment of a substation you must ask for an insulation level: the voltage it must withstand under lightning impulse (BIL) and at power frequency. That level depends on the network voltage, the site altitude, the surge arrester and how far the equipment is from the arrester. This tool walks through that calculation for a range I bay (Um up to 245 kV) and selects the standard level of IEC 60071-1.
It also checks that the continuous operating voltage and the rated voltage of the arrester cover the temporary overvoltage of an earth fault, gives you the maximum separation between arrester and equipment, and calculates the minimum creepage distance of the insulator for the site pollution.
How it is calculated
IEC 60071-2:1996§ 4.2.2eq. 11 IEC 62271-1:2017§ 4.2.2altitude
Altitude factor
Ka = em·H/8150H is the altitude in metres. For lightning impulse and for air clearances at power frequency m = 1. For a polluted insulator at power frequency m may drop to 0.5 (normal) or 0.8 (anti-fog): the tool shows it as an informative value. Only external insulation is corrected.
IEC 60071-2:1996§ anexo Feq. F.18 and F.19
Lightning co-ordination voltage from the line
Ucw = Upl + (A/n) · L/(Lsp + La) · La = Ra/RkmA depends on the type of line, n is the number of connected lines, L the separation between arrester and equipment, Lsp the span, Ra the acceptable failure rate of the equipment (one every so many years) and Rkm the lightning outage rate of the line. With the wave steepness S the tool uses instead Urp = Upl + 2·S·L/c, with c = 300 m/µs, while Upl ≥ 2·S·T; otherwise 2·Upl (2.3.4.5).
IEC 60071-2:1996§ 3.3.1, 4.3.4safety factors
Required withstand voltages
Internal: Urw = 1.15 · Ucw · External: Urw = 1.05 · Ka · UcwAt power frequency the co-ordination voltage is the temporary overvoltage k·Us/√3, with the same factors. The chosen level is the first standard combination of IEC 60071-1:2006 for that Um that covers the highest required lightning value and the highest power-frequency value. The maximum separation is the L that makes the required value equal to the chosen BIL.
IEC 60071-2:1996§ 2.3.2.1, 2.3.2.7surge arrester Siemens 2012§ p. 385 % allowance
Surge arrester
Uc ≥ Us/√3 (or ≥ k·Us/√3 with a sustained fault) · T · Ur ≥ k·Us/√3T is the temporary overvoltage capability of the arrester for the fault duration, from the manufacturer's curve. With a sustained fault the overvoltage is continuous and the real check is Uc. The Siemens 5 % harmonics allowance is shown as an informative line.
IEC 60071-2:1996§ 3.3.1.1levels I to IV Siemens 2012§ p. 105classes a to e
Minimum creepage distance
Levels I to IV: creepage = fe · Um · Classes a to e: creepage = USCD · Um/√3fe is the minimum specific creepage of the level, in mm per kV of the phase-to-phase voltage, for glass and porcelain insulators. USCD is the unified specific creepage of each class, in mm per kV of the phase-to-earth voltage. No diameter correction is applied.
Limits of the calculation
- Range I only (Um up to 245 kV) and deterministic method. From 123 kV, energizing or reclosing long lines can set the power-frequency voltage: the tool does not convert slow-front overvoltages nor check phase-to-phase insulation.
- The bracketed levels of IEC 60071-1:2006 may not be enough to prove phase-to-phase insulation: if the chosen level is one of them, an additional phase-to-phase test may be needed.
- When the separation is not limited by equation (1), IEC 60071-2:1996 (2.3.4.5) asks for caution with transformers: the tool says exactly that, never «no limit».
- The creepage distance does not include the correction for insulator diameter, shape or altitude. Classes a to e are read in the Siemens publication; IEC TS 60815 was not consulted.
- The arrester data (Upl, Uc, Ur and its temporary overvoltage curve) come from the manufacturer's datasheet. It does not replace the project's insulation co-ordination study or the manufacturer's calculation.
Frequently asked questions
Why does the BIL of equipment rise with altitude?
Because the air is less dense and flashes over at a lower voltage. IEC 60071-2:1996 (4.2.2) multiplies the required withstand of external insulation by Ka = e^(m·H/8150); at 2600 m and with m = 1, Ka is about 1.38. IEC 62271-1:2017 (4.2.2) applies that correction only to external insulation: the oil, paper or SF6 inside the equipment do not change with height. That is why 115 kV equipment that would pass with 450 kV at sea level may need 550 kV on a high plateau such as Bogotá.
How far from the transformer should the surge arrester be?
As close as possible. The lightning wave keeps travelling past the arrester and reflects at the equipment: the voltage at its terminals grows with the separation. The tool calculates that voltage with annex F of IEC 60071-2:1996 (or with the wave steepness, eq. 1 to 3) and gives you the maximum separation for the chosen BIL. Count the whole connection: the incoming lead, the arrester height, its earth down-lead and the distance to the equipment.
How are the Uc and Ur of a surge arrester chosen?
The continuous operating voltage Uc must cover the phase-to-earth voltage of the network (Us/√3) or, if the network keeps operating with a sustained earth fault, the full temporary overvoltage. The rated voltage Ur is chosen with the manufacturer's temporary overvoltage curve: Ur multiplied by the capability T for the fault duration must cover k·Us/√3 (IEC 60071-2:1996, 2.3.2.7). Siemens also recommends a 5 % allowance on the continuous voltage for harmonics.
We carry out the insulation co-ordination of your substation
We calculate the insulation levels with the altitude and pollution of the site, select the surge arresters and check their distances, with the study report.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws