Enter the data for the line, CTs and VTs, the following lines, the load and the channel. The tool calculates the zone reaches, residual compensation and fault resistance to cover, checks load encroachment and the R/X rules, and gives the teleprotection scheme times.

Siemens 7SA§ 6.6.9quadrilateralSiemens 7SA§ 6.6.10mhoSiemens 7SA§ 6.6.13zone settingSiemens 7SA§ 6.9teleprotection

Example cases
Distance 21 setting and teleprotection

Only the basic data; the rest is taken with typical values.

ALearn

E1Protected line
Ω/km
Ω/km
Ω/km
Ω/km
km
kV

For the zone 1 R/X ratio that the Siemens 7SA manual recommends.

E2CT and VT
A
kV
V
E3Zones
Ω

Total reactance, in primary ohms, of the line leaving the remote bus that zone 3 must not overreach.

Ω

Total reactance, in primary ohms, that zone 4 must back up.

%
%
°

Tilts the zone 1 top line downward in the first quadrant so remote infeed does not pick up external faults.

ms
ms
E4Resistive reach, secondary ohms
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
E5Load and fault resistance
A
pu
A
A
m
m
Ω
E6Teleprotection

Bolted fault; the diagram lights the zones that pick up, the channel signal and the trip of each end.

ms
ms
ms
ms

Siemens recommends 20 ms on the 7SA.

ms
Ω

Secondary reactance; if 0, zone 4 is taken as non-directional.

Use a decimal point. The calculation runs in your browser and updates as you type.

Zone 1 reach

—

Load encroachment

—

Fault resistance covered

—

Clearing with teleprotection

—

Signal path and teleprotection
Top: the line with its CTs and VTs, the relay at each end, the channel and the trip coils. Bottom: the trip logic of end A drawn with gates. What lights up in yellow is what acts with the simulated fault.
Zones, line and load on the R-X plane
  • Zones
  • Line
  • Minimum load
Each outline is a zone in secondary ohms. The straight line is the line impedance. The points are the minimum load impedance: no zone should contain them.
Reach and time of each zone
Each step is a zone: its reach in primary reactance and its time. The vertical line marks the end of the protected line.

Step-by-step calculation

Loading these settings into a relay? We configure it remotely.

What it is for

Setting a distance protection means deciding how far each zone sees, how much fault resistance it covers and how fast it trips, without the load entering any zone. This tool does that calculation from your line, adjacent line, CT, VT and load data, and plots it on the R-X plane in secondary ohms, as you enter it in the relay.

It also gives the clearing times with teleprotection: which zone sends, which one trips and whether the blocking delay covers the channel.

How it is calculated

Siemens 7SA§ 6.6.9.2residual compensation

Residual compensation and conversion to secondary

Kr = (R0 − R1)/(3R1) · Kx = (X0 − X1)/(3X1) · Zsec = Zpri · CTR/VTR

Kr and Kx depend only on the line data, not on the fault location. The complex factor k0 = (Z0 − Z1)/(3·Z1) is the other way to set it.

Siemens 7SA§ 6.6.13stepped distance

Zone reaches

XZ1 = 0.8·XL · XZ1B = 1.5·XL · XZ3 = 0.8·(XL + 0.8·Xnext) · XZ4 = 1.2·(XL + Xlong)

These are the factors of the Siemens 7SA manual example and can be changed. With intermediate infeed at the remote bus the relay sees ZL + (1 + I₂/I₁)·Zx, so a zone covers less of the next line.

Siemens 7SA§ 6.6.13.6arc resistance

Fault resistance to cover

Varc = 2500 V/m · 2d · Rff = 1.2·Rarc/2 · Rft = 1.2·(Rarc + (1 + Irem/Iloc)·Rtower)/(1 + Kr)

The arc is taken with the minimum fault current. The phase-phase setting is half the loop resistance; the phase-earth one is divided by 1 + Kr because the setting is positive-sequence.

Siemens 7SA§ 6.6.5.2load cutout

Minimum load impedance

Zload,min = Umin/(√3 · Imax) · φload = arccos(pf)

Siemens recommends setting the load cutout about 10 % below that impedance and with an angle about 5° larger, for phase-phase and earth loops.

Teleprotection

In PUTT, zone 1 sends and the receiving end trips with its zone 1B; no echo is needed. In POTT, zone 1B sends and trips; the weak-infeed end can return an echo so the other end trips. In blocking, a reverse or non-directional zone sends the signal that prevents tripping, and zone 1B trips if no signal arrives after the release delay, which must cover the channel time and the pickup difference between the two relays.

Limits of the calculation

  • The quadrilateral shape is generic: sides parallel to the line angle, a top line tilted from the reach point and a directional boundary perpendicular to the line.
  • The mho characteristic is drawn without polarization; with memory or cross polarization, the circle expands backward according to the source impedance.
  • Mutual coupling of parallel lines, power swing blocking (68) and switch-onto-fault tripping are not calculated.
  • The zone factors and times are those of the Siemens 7SA manual example; adjust them to your coordination study.

Frequently asked questions

How are the zones of a distance protection set?

With the reactance of the line and of the following lines. In the Siemens 7SA manual application example, zone 1 covers 80 % of the line with no delay, zone 1B 150 % for teleprotection only, zone 3 reaches 80 % of the line plus 80 % of the next one with a time step, and zone 4 reaches 120 % of the line plus the longest next line, non-directional. The tool calculates these reaches in primary and secondary ohms and lets you change each percentage.

What resistance must zone 1 cover?

That of the arc and, in earth faults, that of the tower footing. The Siemens manual estimates the arc voltage at 2500 V per metre of arc, with an arc twice the spacing between conductors, and adds a 20 % margin. In the phase-phase loop the setting is half the loop resistance; in phase-earth, the resistance divided by 1 + kr. Infeed from the remote end multiplies the tower footing resistance seen by the relay.

When does load encroach on the distance zone?

When the minimum load impedance point, with minimum voltage and maximum current, falls inside the quadrilateral or the circle. Siemens also asks you to check the earth loops and to set the load cutout about 10 % below that impedance, with an angle about 5° larger than the load angle.

What is the difference between PUTT, POTT and blocking?

In PUTT it sends the underreach zone (Z1) and the receiving end trips with its overreach zone. In POTT the overreach zone (Z1B) sends and trips, and the weak end can return an echo. In blocking, a reverse zone sends the signal that prevents tripping; without a signal, the overreach zone trips after a delay that covers the channel time and the pickup difference.

We set your distance protection remotely

We calculate the zones, compensation and teleprotection from your line data, check the load and load the settings into the relay, without travelling.