Home / Tools / Harmonic emission allocation
Harmonic emission limits of an MV or HV user
Type the bus data, the total capacity and the agreed power of the user: the tool shares the planning levels, works out the voltage and current limit of each order and compares them with the currents you expect from your plant.
IEC TR 61000-3-6:2008§ stages 1 to 3allocation (estimate)IEC 61000-2-12:2003§ 4.3compatibility at MVIEEE Std 519-2022§ 5.3contrast
Results
—
—
—
—
Charts
- Planning
- Global contribution
- User's limit
- Planning
- Compatibility IEC 61000-2-12
How it was calculated and standards
Calculation per order
| h | α | L % | G % | E_U % | Z_h Ω | E_I A | I A | IEEE 519 A | Status |
|---|
What it is for
When a plant with drives, furnaces or rectifiers asks to connect at medium or high voltage, the network operator gives it harmonic emission limits. This tool shares the planning levels of the bus among the users and gives the voltage and current limit of each order.
It helps to prepare the connection request, check whether the plant needs filters and understand why two methods, IEC and IEEE, give different results.
How it is calculated
IEC TR 61000-3-6:2008§ stage 2estimate
Global contribution and share of the user
Gh = (Lhα − (T·Lh,up)α)1/α · EU,h,i = Gh·(Si/St)1/αα is 1 below the 5th, 1.4 from the 5th to the 10th and 2 above. With LV load and coincidence factors, the share uses SMV = St − SLV, FML and FMV.
IEC TR 61000-3-6:2008§ stage 2estimate
From voltage to current
Zsc = U²/Ssc · Zh = kZ·h·Zsc · EI,h,i = EU,h,i·(U/√3)/ZhThe network is taken as inductive. With capacitor banks nearby the real impedance can be much higher at some orders: use the kZ factor from a harmonic study.
IEEE Std 519-2022§ 5.3contrast
The same point with IEEE 519
IL = Si/(√3·U) · Isc/IL → row of Table 2 · limit = % × ILLimits of the calculation
- The whole method is an estimate: we do not hold a licensed copy of IEC TR 61000-3-6 and we implement it from open publications that describe it.
- The indicative planning levels are those published in KIEE 2007, earlier than the 2008 edition of the standard: an estimate to be confirmed. Above order 25 we give no typical value. Use your network operator's.
- Stage 1 only compares S_i/S_sc; the weighted distorting power is not calculated.
- The harmonic impedance is inductive and has no resonances; the IEEE 519 contrast is only made up to 69 kV.
Frequently asked questions
What is a planning level?
It is the internal quality objective that the network operator sets for the harmonic voltage of each order. It sits below the compatibility level to leave a margin, and it is the basis for sharing emission limits among the users.
Why does the limit depend on S_i/S_t?
Because the method shares the network's capacity to absorb harmonics in proportion to each user's agreed power against the total capacity that shares that level. The exponent α accounts for the harmonics of many users not adding in phase.
How does it differ from IEEE 519?
IEEE 519 gives fixed current tables by the Isc/IL ratio. The IEC method shares a planning level with formulas that use the user's power, the total capacity and the harmonic impedance of the point, so the two results need not agree.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws