Function 86: lockout relay

Lockout relay 86: latched trip, local or remote reset, close and 79 blocking, the relay inside and a test plan with the test set.

IEEE C37.2§ 3.1.86function numbersSiemens SIPROTEC 5§ 3.1.9latched outputsSiemens SIPROTEC 5§ 5.5.5.2trip command

Example cases
Function 86: lockout relay

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings

An 86 contact opens the close coil circuit: nobody closes while it is operated.

Many utilities require a reset on site, after checking the equipment: it is a rule of each utility, not of the relay.

E3Simulation

For example a trip of the 87T, the 50BF or the Buchholz that comes in on BI3.

E5Relay tolerances
ms
ms
ms

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Reset

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 86 is the lockout relay: when an important protection trips (the differential of a transformer, breaker failure, the Buchholz), the 86 opens the breakers and stays operated. While it stays operated the equipment cannot be energized again.

In numerical relays the 86 is usually a latched output: it stays active until someone resets it with the front key, a binary input or a remote command, as each utility allows.

How it operates

  • Any trip that reaches the 86 operates it and leaves it latched, even if the trip goes away.
  • The reset only works if the path is allowed and the cause is gone: while the protection keeps tripping, the 86 sets again.
  • With the 86 operated, one of its contacts opens the close circuit and a signal blocks the reclosing, so nobody energizes the equipment before the fault is checked.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The BOUT3 output of the test set energizes the trip input to the 86 and its binary input reads BO1. The operating time is measured and it is checked that the output does not reset when the trip is removed.

Then the reset paths are tested: with the trip still present it must not reset; without the trip, each allowed path resets and each path that is not allowed does not. Finally the close and 79 blocks are checked.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The time between the input and the output is not declared in the manual: the expected value is the sum of the input and output times, plus an editable margin, and it is marked as an estimate.
  • That the reset does not act with the trip present is the behaviour of this model; check the one of your relay.
  • An electromechanical 86 with an electrical reset coil is not simulated.

Frequently asked questions

What is the difference between the 86 and the 94?

The 94 gives the trip command and resets by itself once the fault is cleared. The 86 stays operated and does not allow closing until someone resets it.

Why does the 86 not reset if the trip is still present?

Because the cause is still there: the memory sets again as soon as the reset is released. The trip has to be removed first, for example by resetting the Buchholz alarm.

Can the 86 be reset remotely?

The relay usually allows it through a binary input or the station protocol, but many utilities forbid it so that the equipment is checked on site.