Home / Tools / MV feeder coordination
Medium-voltage feeder coordination
Choose the fuse, the recloser and its sequence, and enter the fault currents of your branch. The tool plots the curves on a time-current chart and checks fuse saving, coordination with the slow curve, the sectionalizer, cable and transformer damage, inrush and cold load.
IEEE C57.109-1993transformer damageIEEE 141-1993§ 5.6.2cable damage
Results
—
—
—
—
Charts
- Active signal
- Signal at rest
- Fast × k (maximum clearing)
- Slow (minimum trip)
- Fuse: melting and clearing
- Damage and fault
- Fast operation
- Slow operation
- Reclosing interval
How it was calculated and standards
Times at the fault currents
Loading these settings into a relay? We configure it remotely.
What it is for
On a medium-voltage feeder the recloser opens and recloses, and the branch fuses must blow only on permanent faults. This tool puts the recloser's fast and slow curves, the fuse, the transformer and the cable on one chart and checks that each device operates in the right order.
To coordinate relays and reclosers in series with IEC or IEEE curves, up to six devices on a full path, use the relay coordination tool. This one deals with the feeder: reclosing sequence, k factor, sectionalizer, cable damage, inrush and cold load.
What is checked
Source: Hosseinzadeh (UWO, 2008), §3.2; k from PDHonline E405
Fuse saving
tmin melting(I) ≥ k · tfast max(I)The minimum melting of the fuse, with the preload you enter, must exceed the fast curve at its maximum clearing multiplied by k, over the whole fault range of the fuse. Applying k to the maximum clearing, which already includes the tolerance and the interrupting time, is more conservative than applying it to the average curve. Where the fast curve crosses the fuse, saving ends: above that current the fuse melts together with the fast operation.
Source: Hosseinzadeh (UWO, 2008), §3.2
The fuse blows on permanent faults
tfuse clearing(I) < tslow min(I) − marginThe total clearing of the fuse must stay below the slow curve with no factor, and the recloser must have two or more slow operations. The slow curve is taken at its minimum trip time.
Source: Hubbell PRS sectionalizer catalog (2016)
Sectionalizer
count ≤ recloser operations − 1 · Imin fault ≥ Iactuating · Iactuating ≤ 0.8 × IpickupThe actuating current must not exceed the recloser pickup, or the sectionalizer does not count the trips between the two. The catalog works with 0.8 times the pickup (160 % against 200 % of the rated currents).
IEEE 141-1993§ 5.6.2copper cable
Cable damage
(I / A)² · t = 0.0297 · log10[(T2 + 234) / (T1 + 234)]A is the cross-section in circular mils (1 mm² = 1,973.5 cmil), T1 the operating temperature and T2 the maximum short-circuit temperature; the equation is valid up to about 10 s. For a #6 AWG copper conductor with thermoplastic insulation from 75 to 150 °C it gives 21,500 A for a quarter cycle and 10,800 A for one cycle. The tool adds up the times of every operation the cable sees with a permanent fault (the fast operations and the fuse clearing) over the whole fault range, ignoring cooling between reclosings: a conservative check.
Source: CIGRE US NC 2017, session 4C, paper 3; FMPA/FMEA 2021
Inrush and cold load
inrush 12 × In at 0.1 s and 25 × In at 0.01 s · cold load 6 × 1 s, 3 × 10 s, 2 × 1,000 sThe fuse minimum melting must stay above those points. If a point falls outside the published curve (current below its first point or time beyond its longest one), the tool does not count it as passing: it flags it for review. The same source warns that default cold-load values should be questioned for lateral reclosers: use them as a reference and replace them with measurements from your feeder.
Where the curves come from
The 6 to 200 A K and T fuses come from the data files that Hubbell Power Systems (Chance) publishes on its product pages. Each curve is reduced to 26 points and interpolated on a logarithmic scale. The published value for a 40T at 2400 A (0.0185 s) matches the curve used. Minimum melting curves start with no load.
The recloser curves are the equations that S&C publishes in its bulletin 461-211, which emulate Cooper and other manufacturers' curves, with the tolerance of ±10 % or ±3 A in current, ±0.0167 s in time and 0.03 s of interruption that S&C declares for its TripSaver II. That tolerance is applied only when both curves are S&C emulations; IEC, IEEE, ABB, SEL and own curves are used as they are. If your recloser uses another curve, enter A, B, C and p from your manufacturer.
Limits of the calculation
- There are no fuses from other manufacturers, no current-limiting fuses, and no N, QR or SloFast types: no published numerical data were found. You can enter I:t points of another fuse.
- The recloser curves are S&C emulations. The curve published by the manufacturer prevails in a real study: compare them at the points that decide the setting.
- The k factor from the manufacturer's full table, the one for other sequences, the cooling factors and the preload are not in open sources: they are your data. A fuse upstream of the recloser is not calculated here.
- The cable equation is the IEEE 141-1993 copper one. Aluminium is not included yet: its constants still have to be checked on the original page. The 250 °C of thermoset insulation comes from a secondary source.
- The transformer damage curve (IEEE C57.109-1993) comes from a secondary source and its categories are those of three-phase transformers. The fuse curves end near 0.01 s: below that time they are extrapolated with constant I²t and the tool says so.
- All currents are at feeder voltage. The transformer connection enters only as the factor that shifts the damage curve. It does not model CT saturation.
- It does not replace the coordination study of your system. The example cases are illustrative.
Frequently asked questions
What is fuse saving?
It means letting the recloser open on its fast curve before the fuse of a branch melts, so that a temporary fault does not leave the branch without supply. It holds if the minimum melting of the fuse is above the fast curve multiplied by a factor k, which covers the accumulated heating of the fuse in each operation.
What is the value of the k factor?
It depends on the sequence and the reclosing time, and the recloser manufacturer gives it. One open source gives 1.25 with one fast operation, and 1.35 or 1.8 with two fast operations depending on whether the reclose time is 60 cycles or longer, or shorter. For other sequences the tool asks for the manufacturer's value.
How many counts do I set on the sectionalizer?
At most one less than the operations of the recloser that backs it up: with a 4-shot recloser, a count of 3 at most. Also, the minimum fault current at its location must exceed the actuating current of the sectionalizer.
We do your protection coordination study
We gather the short-circuit data of your feeder and the curves of each recloser and fuse, and deliver the settings with their coordination chart, without travelling.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21Motor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws