Split factor Sf and grid current

Enter the earth fault, the grid and what leaves the substation: lines with earth wire, feeders with neutral and cables with sheath. The tool calculates the reduction factor of each, the impedance of its chain, how much of the fault really enters the grid and the current IG for the grid design.

IEC 60909-3:2009§ 3.11, 3.12, 6.2, 7, 8.2.1, 8.3.1reduction factor and tower chainIEEE Std 80-2013§ 15.9, 15.10, C.2split factor and grid current

Example cases
Split factor Sf and grid current

Only the basic data; the rest is taken with typical values.

ALearn

E1Fault and grid
kA

Earth fault current at the substation busbar, from the short-circuit study.

%

Part of 3I0 that arrives through the lines. The rest is supplied by the substation's own transformers and returns to their neutral without passing through the ground.

Ω
Ω·m

Sets the equivalent depth of the earth return.

s

Clearing time of the backup protection.

E2Lines with earth wire

Lines arriving with a contribution from the network. They are taken as identical.

km
m
Ω

ACSR conductors from the Prysmian Colombia datasheet; for steel or OPGW choose "Other conductor".

Ω/km
mm

IEC 60909-3, clause 7: steel around 75, multilayer ACSR around 1, single-layer aluminium ACSR 5 to 10.

m

Geometric mean of the distances from the earth wire to the three phases, in the plane of the structure.

m
Ω
E3Feeders with neutral

Outgoing circuits without contribution whose neutral or guard cable is bonded to the grid.

km
m
Ω
Ω/km
mm
E4Cables with sheath

Cable circuits with the sheath earthed at both ends.

km
mm²
mm

From the cable datasheet: half the diameter over the sheath minus half its thickness.

mm
Ω

Use a decimal point. The calculation runs in your browser and updates as you type.

Split factor Sf

—

Grid current IG

—

Ground potential rise

—

Reduction factor r

—

Where the fault current returns
The width of each arrow is proportional to its current. The busbar fault receives the contribution of the lines; part returns through the earth wire, part through the ground, and only what goes down through the grid raises its potential.
Current through each tower
The current the grid pushes through the earth wire goes down to the ground tower by tower and drops in each one by the factor k = 1 + Z<sub>P</sub>/R<sub>T</sub>.
Split factor against grid resistance
  • IEC 60909-3
  • IEEE 80
The lower the grid resistance, the more current it takes. The IEEE 80 curve ignores the coupling of the wire with the phases and sits above.

Step-by-step calculation

What it is for

A substation grid is designed for the current that enters the ground, not for the whole earth fault. Earth wires, neutrals and cable sheaths carry part of it back to the sources. This tool calculates that split with IEC 60909-3:2009 and compares it with the IEEE 80 method.

The result is the grid current I<sub>G</sub> that the earthing resistance tool uses for touch and step voltages.

How it is calculated

IEC 60909-3:2009§ 7reduction factor

Earth wire reduction factor

r = 1 − Z′QL/Z′Q · Z′Q = R′Q/ν + ωμ0/8 + j(ωμ0/2π)(μr/4ν + ln δ/rQQ) · δ = 1.851/√(ωμ0/ρ)

IEC 60909-3:2009§ 3.11, 3.12tower chain

Tower chain impedance

ZP = 0.5·ZQ + √(0.25·ZQ² + RT·ZQ) · ZQ = Z′Q·dT · DF = 3√(RT·dT)/Re√Z′Q

The finite chain is solved span by span from the remote station, which is the same as equation 2 of the standard.

IEC 60909-3:2009§ 8.2.1, 8.3.1sheaths

Sheath reduction factor

r1 = R′S/Z′S · r3 = R′S/(R′S + 3ωμ0/8 + j3(ωμ0/2π)·ln δ/∛(rSd²))

For a cable of length l to another grid ZE, the part returning through the ground is r′ = (Z′S − Z′SL)·l/(Z′S·l + ZE), which tends to r1 or r3 for a long cable.

IEC 60909-3:2009§ 6.2split at the station

Current entering the grid

U = Σ ri·3I0,i / (1/Rg + Σ 1/ZP,i + Σ 1/ZU,j) · Ig = U/Rg · Sf = |Ig|/3I0

IEEE Std 80-2013§ 15.9, 15.10grid current

Comparison with IEEE 80 and the design current

Zeq = 0.5·Zs + √(Zs·Rtg) per circuit · Sf = Zeq/(Zeq + Rg) on the remote contribution · IG = Df·Sf·3I0

Limits of the calculation

  • The fault is at the substation busbar. A fault at a nearby tower can give more current to the grid; IEC 60909-3 covers it in its clause 6.4 and it is not calculated here.
  • The contributions are added in phase. With the real angles from the short-circuit study the grid current is equal or lower.
  • Buried pipes and other conductors bonded to the grid are not included, nor are double-circuit lines with coupling between them.
  • For cables with steel armour the reduction factor is given by the manufacturer.
  • The IEEE 80 method is the ladder reduction of its clause 15.9; the curves of its annex C are not reproduced.

Frequently asked questions

What is the split factor Sf?

It is the part of the earth fault current that actually enters the ground through the substation grid. The rest returns to the sources through earth wires, neutrals and cable sheaths, or through the local transformer neutral. With Sf you get the grid current IG = Df·Sf·3I0, which sets the touch and step voltages.

Why do IEC 60909-3 and IEEE 80 give different values?

IEEE 80 reduces each earth wire to a ladder impedance and splits the current between that impedance and the grid, without the coupling with the phases. IEC 60909-3 adds the reduction factor r: the phase current induces a return current in the wire, and only the part r·3I0 is left for the ground. That is why IEC gives a lower Sf and IEEE stays on the safe side.

What is the far distance DF?

It is the distance from the station beyond which the split between the wire and the ground no longer changes. IEC 60909-3 gives it in its equation 19 using the tower footing resistance, the span and the wire impedance. If the line is shorter than twice DF, use the finite chain with the remote station resistance.