Function 51V: voltage-restrained overcurrent

Generator backup: voltage-restrained or voltage-controlled overcurrent, pickup that follows the voltage, the relay inside and a test-set test plan.

IEEE C37.102§ 4.6.1.2backup with 51VSEL-700G§ p. 44tolerancesIEEE C37.2§ 2008function numbers

Example cases
Function 51V: voltage-restrained overcurrent

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings
A

Above the emergency overload; at low voltage the pickup drops in proportion.

Below this voltage the pickup stops dropping. IEEE C37.102-2006 §4.6.1.2 mentions a relay with 25 %.

A

Below the sustained fault current of the generator.

V

Line to line: below it the sensitive 51 is enabled. It must not enable at the lowest emergency voltage.

A
E3Simulation
A

External three-phase fault or overload: the same current in the three phases.

V

The loss-of-potential logic (60) blocks the 51V: with no voltage the pickup would drop and it would trip on load.

E4Installation and test set
V
A

Only to show the primary values.

A

Example value: enter that of your test set. Points that exceed it are marked.

V

Example value: enter that of your test set.

E5Relay tolerances
%
% of In
%
cycles
%
V

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Effective pickup

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 51V is the generator backup for phase faults in the grid that nobody cleared. A plain overcurrent does not work: its pickup must be above the emergency overload, and the fault current of a generator falls in less than a second to a value near or below its rating.

The answer is to use the voltage: in a close-in fault the voltage drops a lot, in an overload it does not. The 51V becomes sensitive only when the voltage is low.

How it operates

  • With voltage restraint (51VR) the pickup drops in proportion to the voltage, from the setting at full voltage down to a minimum, for example one quarter.
  • With voltage control (51VC) a sensitive 51 stays blocked while the voltage is above the control threshold and is enabled when the voltage falls.
  • A blown VT fuse would drop the measured voltage with no fault: the loss-of-potential logic (60) blocks the 51V.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The plan searches the pickup at three different voltages: full, half and a very low one, and checks that the pickup follows the restraint line. Times are measured at half voltage at 2 and 5 times the pickup.

In the controlled mode it also searches the control voltage by lowering the voltage with twice the pickup. Finally it checks that it does not operate on the emergency overload and that test-set output 3 on BI3 blocks it.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The fault is simulated three-phase, with the same current and voltage in the three phases; the per-phase restraint of each relay is in its manual.
  • The decrement of the generator fault current is not calculated: enter the sustained current from your study.
  • The tolerances are those of the cited data sheet: enter the ones of your relay.

Frequently asked questions

Why does a normal 51 not work as generator backup?

Because its pickup must be 1.5 to 2 times the rated current so it does not trip on an emergency overload, and after half a second the generator fault current falls toward that of its synchronous reactance, which may be below the rating (IEEE C37.102-2006 §4.6.1.2).

What is the difference between voltage restraint and voltage control?

With restraint the pickup changes continuously with the voltage; with control there is a fixed, sensitive pickup that is enabled only when the voltage falls below the threshold.

How is the effective pickup calculated?

With linear restraint it is the setting times the measured voltage over the rated one, without going below the minimum. With a 6.3 A setting and 30 V of 115 V the pickup is 6.3 × 0.26 = 1.64 A.