On-load tap changer dynamic resistance
Simulate the current the test set records while the diverter changes tap, see where each lead goes on the leg's winding and evaluate your measurements: transition time against the manufacturer, ripple, interruptions and differences between phases and operations.
Plath y Pütter, O Setor Elétrico, 2017§ —measurement methodTap changer manufacturer§ —transition time
Results
—
—
—
—
Charts
- Simulated current
- Stage change
- Current before the operation
How it was calculated and standards
Test planPro
Results sheetPro
Step-by-step calculation
What it measures
The test records the direct current flowing through the HV winding while the on-load tap changer changes position. The trace shows the diverter switch sequence: the main contact opens, the current flows through the transition resistors and the contact closes on the new tap.
From the trace you measure the transition time, the current dip (ripple) and whether the current reached zero. An interruption means the path opened: a broken transition resistor, a loose connection or a contact that did not close.
How it is connected
It is the same four-wire connection as winding resistance: I+ and V+ on one end of the leg's HV winding, I− and V− on the other, with the voltage clips inside. The tank is grounded and the other terminals are left floating. The tap changer is operated with its drive while the test set records.
Which terminal pair is the winding of each leg depends on the vector group: in a Dyn11 leg A is H1-H2; in a YNd1, H1-H0. The drawing works it out and highlights the tap changer.
Corrections
The shape of the trace depends on the test set and the setup: the test current, the source voltage limit and the inductance it sees. If the LV is short-circuited, the inductance drops and the ripple grows. That is why a trace is only compared with another taken with the same setup.
The simulator lets you adjust the inductance, the source and the time of each stage until the simulated trace looks like the measured one. It is for understanding what changes the shape of the trace, not for deriving tap changer values.
How to interpret it
If the current reaches zero in any phase or operation, the result is Fail: in service the tap changer would interrupt the load current and arc.
The transition time is compared with the tap changer manufacturer's range. As a reference, Plath and Pütter quote typical switching times of 40 to 60 ms, but the criterion is always the one of your tap changer's manufacturer.
Differences between phases of the same operation and between operations of the same phase are flagged for review with the Tiza convention (10 % in time, 50 % in ripple). They point to contact wear or misadjustment and call for comparison with the equipment's history.
Tool limits
- The simulator models a resistor-type diverter switch with two equal transition resistors. Reactor-type tap changers and vacuum ones with other sequences are not simulated; their measurements can still be evaluated.
- The winding inductance is taken as constant during the operation; in reality it changes with core saturation and with the number of turns of the tap.
- On a delta HV winding, part of the test current flows through the windings of the other two legs and through their diverters: the trace mixes the switchings of the three phases. If the test set allows it, inject phase by phase to separate them.
- On an HV wye without a neutral bushing (Yd1, Yd11, Yy0, Yyn0) the current enters through one bushing and leaves through the next: there are two arms of the wye and two diverters in the path.
- There is no ripple limit taken from a standard: only the differences between phases are flagged with the Tiza convention.
Frequently asked questions
What is the dynamic resistance of a tap changer?
It is the record of the direct current flowing through the winding while the on-load tap changer moves from one tap to another. The shape of the trace shows when the main contact opens, when the transition resistors come in and when the contact closes on the new tap.
When is a dynamic resistance trace bad?
Whenever the current reaches zero: the path opened and in service the tap changer would interrupt the load current. The transition time is judged against the manufacturer's range, and the differences between phases and between operations show what to review.
Why does the ripple change from one test to another?
Because it depends on the inductance the source sees and on its voltage limit. If the LV is short-circuited, the inductance drops and the ripple grows. Always compare traces taken with the same setup, the same test set and the same current.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws