Home / Tools / MMS control sequence
MMS control sequence: SBO, Operate and AddCause
Choose the control model, the command and what happens in the bay. The tool builds the sequence between the client, the IED and the breaker with every service, its MMS write or read, the time and the cause of the rejection. Click a step to see it on the drawing.
Results
—
—
—
—
Charts
How it was calculated
MMS messages of the sequence
| # | Time | Service | MMS |
|---|
What it is for
An IEC 61850 command from the HMI or the control centre is not a single write: depending on the control model there is selection, operation, confirmation of the end and, if something fails, a report with the cause. This tool builds that sequence to read a Wireshark capture, understand a rejection during commissioning or test the gateway.
How the sequence is built
Source: IEC 61850-7-2:2003, cl. 17; IEC 61850-8-1:2004, cl. 20
Selection
normal security: Read SBO (empty = rejection); enhanced: Write SBOw with ctlVal, origin and ctlNumAt selection the IED checks the control hierarchy, whether another command is running and its own health. The selection lasts sboTimeout.
Source: IEC 61850-8-1:2004, cl. 20, tables 69, 76 and 77
Operate and rejection
Write Oper; rejection with enhanced security = InformationReport LastApplError { CntrlObj, Error, Origin, ctlNum, AddCause } then Write.response failure; with normal security, only Write.response failureOn operate, the selection, the position and the interlocking are checked. AddCause gives the cause: 2 hierarchy, 4 invalid position, 5 position reached, 10 interlocking, 18 object not selected.
Source: IEC 61850-8-1:2004, cl. 20.9
End of the operation
enhanced security: CommandTermination+ (InformationReport of Oper) or − (LastApplError and Oper)With normal security only the report of the new state arrives; if the breaker does not move, the client receives no cause.
Limits of the simulation
- What is checked at selection and what at operate depends on the manufacturer; the tool uses a typical split.
- It does not model TimeActivatedOperate, the operate-many class or the test bit.
- The MMS variables follow the name CSWI1.Pos of the logical device you type; your SCD may use another.
- It does not replace the control tests in your substation. The example cases are illustrative.
Frequently asked questions
What changes between normal and enhanced security?
With enhanced security the IED confirms the end of the operation with CommandTermination and, if it fails, sends LastApplError with the cause. With normal security the client only knows that the command was accepted; if the breaker does not move, it finds out because the change of state does not arrive.
What does AddCause 10 mean?
Blocked-by-interlocking: the interlocking (CILO) does not allow the operation. It is the most common rejection during commissioning, together with the control hierarchy (AddCause 2) and the position already reached (AddCause 5).
Why does Operate fail if I already selected?
Because the selection expires with sboTimeout. If the operator takes longer than that time between selecting and operating, the IED answers Object-not-selected (AddCause 18).
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws