Auxiliary services control simulator

Simulate the automatic transfer between the station-service transformer and the diesel set, and the DC charger and battery with their alarms.

IEEE 946-2004DC auxiliary systems: charger, alarms and ground detectionIEC 60947-6-1Low-voltage transfer switching equipment (cited in the guide)IEEE C37.2Device numbers 27, 43, 47, 52, 64, 72 and 83

Example cases
Auxiliary services control simulator

Only the basic data; the rest is taken with typical values.

ALearn

MLive controls
E1Test
E2AC and transfer

It happens after maintenance: the 47 relay gives no permissive.

The mechanical interlock between the two breakers remains.

E3DC system

Some designs disconnect the battery at the minimum voltage: this protects it, but the bus is left dead.

kΩ
A
Ah
%
E4Transfer settings
%
%
s
s
s
s
s
s
s
s
s
E5Battery and charger settings
V
V
V
V
s
s
A
h
kΩ
s

Use a decimal point. The calculation runs in your browser and updates as you type.

Source in service

—

Last command

—

DC bus

—

Alarms

—

Closing and start
  • Rating
  • Control wiring
  • Live
Contacts are drawn in their current state: closed is a straight line. The live wire from the positive rail lights up in yellow; a lit coil is energized. Click the selector or the pushbuttons in the drawing to operate them.
Opening of the sources
  • Rating
  • Control wiring
  • Live
Contacts are drawn in their current state: closed is a straight line. The live wire from the positive rail lights up in yellow; a lit coil is energized. Click the selector or the pushbuttons in the drawing to operate them.
DC system and alarms
  • Rating
  • Control wiring
  • Live
Contacts are drawn in their current state: closed is a straight line. The live wire from the positive rail lights up in yellow; a lit coil is energized. Click the selector or the pushbuttons in the drawing to operate them.
The same logic with gates
A series contact is an input of an “&” gate; two parallel branches, a “≥1” gate; a normally closed contact, a negated input. They are drawn with the same equations the simulator runs.

Event log server

t (s)Signal or commandStatus

Functional tests of the control circuit

#TestAcceptance criterion
1Real loss of the normal source with the load connectedIt transfers after the loss delay, starts and stabilizes the set, and the two sources are never closed together.
2Dip shorter than the loss delayNo transfer and no start of the set.
3Return of the normal sourceIt retransfers only when the normal source stays within limits for its delay; the set cools down and stops.
4Selector in manual and hand closing of the open sourceThe controller does not act; the interlock prevents closing with the other source closed.
5Failure of the charger and of its AC supplyThe battery takes the load without interruption; the failure alarm and the bus undervoltage alarm reach the RTU.
6Simulated ground on each polarityThe 64 alarms at the set resistance and shows the polarity.

Replay them in the simulator with the “Test” field and with the live controls.

What it is for

A substation lives on its auxiliary services: AC runs chargers, motors and ventilation, and DC keeps protection and control working. This simulator draws both parts and their logic, and lets you operate them live.

Remove the normal source, keep the set from starting, put the selector in manual, fail the charger or apply a ground, and see which contact opens, which alarm comes up and why an order does not reach the coil.

How it operates

  • Controller 83 supervises each source with a 27 relay. If the normal source is out of limits for longer than the loss delay, it starts the set, waits for its voltage to settle, opens 52-1 and, after the neutral position, closes 52-2.
  • The two breakers never close together: the b contact of each one is in the closing circuit of the other, and there is also a mechanical interlock. With the selector in manual the controller gives no orders and the pushbuttons are in command.
  • When the normal source returns and stays within limits for the return delay, the controller opens 52-2, closes 52-1 and leaves the set running unloaded for the cool-down. If the alternate fails while that delay runs, it returns at once, as commercial controllers do.
  • On the DC side, the charger feeds the load and floats the battery. If the charger fails or loses its AC supply, the battery takes the whole load and the bus voltage drops from float to discharge voltage: the undervoltage alarm, set near the open-circuit voltage, warns at once.
  • If nobody acts, the battery discharges to the minimum system voltage and its alarm comes up. With a minimum-voltage contactor, the battery is disconnected and the DC bus is left dead, with everything that depends on it.

Limits of the calculation

  • This is a principle scheme, not a manufacturer drawing. Your board may have a bus tie, two transformers, closed transition or other conditions: compare with your drawings.
  • The DC bus is drawn as one line for both poles. The discharge curve is a straight line between the starting and the minimum voltage; the real one is the manufacturer's.
  • Equalize and boost charging, temperature compensation and load sharing between two chargers are not simulated.
  • The return and cool-down delays are short so you can see them in the simulator. On site they are usually minutes.

Frequently asked questions

Why does the transfer wait for a delay before acting?

So that it does not transfer on short dips, such as those of a cleared external fault or a network reclose. The delay is set above those times and according to what the loads tolerate.

Why is the DC undervoltage alarm not set at the minimum voltage?

Because it would come too late. IEEE 946 recommends setting it slightly below the open-circuit voltage of the battery: it then warns as soon as the battery starts to deliver energy, with time to correct.

Does a ground on the positive take the DC out of service?

No. The system is ungrounded and the first fault only alarms. The risk is a second ground on the other pole or in the wiring of a coil, which can trip or prevent an operation.