Line differential 87L: dual-slope percentage characteristic, charging current and channel, the relay inside and a test plan with the test set.

IEEE C37.2§ 3.1.87function numbersGE Multilin L90§ 10.1.6percentage characteristicGE Multilin L90§ 9.1.3pickup test

Example cases
Function 87L: line differential

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings
pu

In per unit of the rated primary current of the local CT.

%
%
pu

Remote CT primary over local CT primary: brings the remote current to the local base.

It needs the line voltages in the relay.

E2Settings, part two
ms
ms
E3Simulation
pu
pu

In the base of its own CT; the relay multiplies it by the TAP.

°

Both currents are measured flowing into the line: 0° is an internal fault fed from both ends and 180° a current that passes through the line.

pu

The one the line draws at no load with rated voltage; from your study or from the line capacitance.

E4Installation and test set
A

Only to show the primary values.

A

Example value: enter that of your test set. Points that exceed it are marked.

E5Relay tolerances
%
cycles
cycles
ms

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Channel

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 87L compares the currents of both ends of the line. If what enters at one end leaves at the other, the fault is outside; if the sum of both is not zero, there is a fault inside the line and both ends trip without delay.

Each relay sends its currents to the other over a communication channel, almost always fibre. That is why the 87L depends on the channel: if it fails or is delayed too much, it blocks and the backup protection remains.

How it operates

  • The differential current is the phasor sum of both currents. The restraint grows with the current of each end: with slope 1 up to the breakpoint and with slope 2 above it, because at high currents the CTs make bigger errors.
  • It trips when the square of the differential exceeds twice the square of the pickup plus the restraint of both ends.
  • The line draws charging current even without a fault, and that current appears as differential. With the voltages in the relay it can be compensated; without compensation the pickup has to stay well above it.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

With a single test set and the healthy channel, current is injected at the local end only: the relay sees it as differential and also as restraint, and the measured pickup is higher than the setting. It is repeated on the three phases.

In loop-back, with the channel transmitter tied to the receiver, the local current comes back as the remote one and another pickup is measured. External faults are tested with two test sets synchronized by GPS; finally it is checked that the 87L blocks without the channel.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The adaptive term of the cited manual, which grows with noise and saturation, is taken as zero: it is the case of pure sine waves.
  • A two-terminal line and a single phase are simulated; the ground differential, an in-zone transformer and the direct transfer trip are not modelled.
  • The charging current is split in halves between both ends, 90° ahead.

Frequently asked questions

Why is the pickup measured with local current only higher than the setting?

Because that same current also restrains. With a pickup of 0.20 pu and a slope of 30 %, the relay trips at about 0.31 pu, as the test formula of the cited manual gives.

What does channel asymmetry do?

If the go and return paths take different times, the relay aligns the currents wrongly and the remote one appears rotated. With 3 ms at 60 Hz the rotation is about 32°: a load of 1 pu already shows as 0.56 pu of differential.

When is charging current compensation needed?

On long lines and cables, where the charging current forces a much higher pickup. The cited manual asks for a pickup of at least 2.5 times that current without compensation and 1.5 times with it.