Disconnector and earthing switch: induced, bus transfer and capacitive
Enter the energized line, the geometry of both lines and the earthing-switch operation: the tool calculates the currents and voltages induced by magnetic and capacitive coupling and compares them with the rated values. It also gives the bus-transfer current and voltage and the capacitive current the disconnector breaks.
IEC TR 62271-305:2009§ 4, 5.6, A, Bcapacitive currentLine theory§ Carson, Maxwellcoupling between linesCircuit theory§ Rosa–Groverbus transfer
Results
—
—
—
—
—
—
Charts
- EM I
- EM U
- ES I
- ES U
How it was calculated and standards
Step-by-step calculation
Need it for a real project? We carry out the full study, with its report.
What it is for
When a line is taken out for maintenance and the line next to it stays in service, the dead line picks up voltage and current from its neighbour. The earthing switch has to make and break those induced currents. This tool calculates them from the geometry and compares them with the rated values of the earthing switch.
It also checks two disconnector duties: transferring a feeder from one busbar to the other with the coupler closed, and opening an unloaded busbar, which means breaking a small capacitive current.
How it is calculated
Line theory§ Carsonmagnetic coupling
Electromagnetic voltage and current
Zik = ω·μ0/8 + j·ω·μ0/(2π)·ln(De/dik) · De = 658.5·√(ρ/f) · Ek = −Σ Zkj·Ij·LWith one end open, the voltage at the earthing switch is Ek. With both ends earthed, the three phases and the earth resistances form a system of equations that gives the current of each phase.
Line theory§ Maxwellcapacitive coupling
Electrostatic voltage and current
Pii = ln(2hi/r)/(2πε0) · Pik = ln(D'ik/dik)/(2πε0) · V = P·q · I = ω·q·LWhen isolated, the dead line carries no charge and its voltage follows from that of the neighbouring line. With one end earthed its voltage is zero and the earthing switch carries the current that discharges it.
Circuit theory§ Rosa–Grovertransfer
Transfer current and voltage
It = I·Z2/(Z1 + Z2) · Ut = It·|Zloop| · Lloop of a rectangle with sides Lb and sIEC TR 62271-305:2009§ A.4, Bcapacitive current
Capacitive current and restrike
I = Σ Ibus + ICT + U/√3·ω·(CCVT + Ccable) · UOV ≤ 1 + 2/(1 + CS/CL)Limits of the calculation
- The lines are taken as parallel, at constant height and with balanced load. The shield wire, which reduces the coupling, and transpositions are not modelled.
- Carson's first-order form is used, valid at power frequency with distances much smaller than the earth-return depth.
- It is calculated with the load current of the neighbouring line. A fault on that line induces much higher values, which are covered by the short-time current of the earthing switch, not by its class A or B.
- Each bundled phase is taken as one conductor of equivalent radius; the subconductors sit on a circle.
- The class A and B ratings of IEC 62271-102 are not in the tool: enter those on the nameplate or in the datasheet.
- The transfer uses a single loop per phase and ignores the other two phases and the droppers; it is an order-of-magnitude estimate.
- The busbar and CT currents are the typical values of IEC TR 62271-305 for air-insulated equipment; with manufacturer data the result is better.
Frequently asked questions
Why is there voltage on a de-energized line?
Because it runs next to an energized one. The current of the neighbouring line induces a voltage along the dead line, like the secondary of a transformer, and its voltage charges it like a capacitor. That is why the line is earthed at both ends before work, and the earthing switch must be able to make and break those currents.
What are classes A and B of an earthing switch?
They are two levels of induced-current switching capability defined by IEC 62271-102. Class B is for strong coupling, such as long lines or circuits on the same tower. The rated values are on the nameplate and in the datasheet: enter them and the tool compares them with the case.
How much capacitive current does an air-insulated disconnector break?
Without testing, it has been taken as 0.5 A or less, according to IEC TR 62271-305:2009. That report gives the method to test higher values, which are agreed between the user and the manufacturer.
We review your disconnectors and earthing switches
We calculate the induced currents of your line, review the equipment selection and test the disconnectors on site.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws