Current transformer (CT) tests

Pick the core and the test: the drawing shows the CT with the test-set connection, what is energized and what is measured. Type your readings and the tool calculates the result, applies the corrections and compares it with the criterion and its source.

IS 2705-1:1992§ 3.13, 3.14, C-2.4, D-1error, phase displacement and polarityIS 2705-2:1992§ 3.3, tablas 1A-1C, 7.1.2measuring classesIS 2705-3:1992§ tabla 1, 7.1.2.2protection classesIS 2705-4:1992§ 2.1, 3.1.2, 4, 6knee point and class PSUSBR FIST 3-8 (2011)§ 5.3, 5.5, 6, 7, ap. D y Efield tests

Example cases
Current transformer (CT) tests
ALearn

E1Current transformer
A
VA

Empty for a PX core, which has no rated burden.

Accuracy limit factor (5P20 → 20) or instrument security factor of a measuring core (FS5 → 5).

V
A
Ω
E2Ratio readings
V

Below the knee and never above the class voltage.

mV
°
A
A
min

Positive if the secondary leads the primary.

%

In % of the rated burden.

%
E2Excitation curve
Measured points

One row per point, from lower to higher voltage. «Original» is the factory current or the first test's current at the same voltage.

RowVoltageVCurrentAOriginalARemove

Given by the relay manufacturer or the protection study.

Ω
V
V
E2Burden readings
A
V
°
Ω

0 if you measure at the CT terminals.

m
°C
VA
VA
E2Resistance readings
Ω
°C

The oil or ambient temperature if the CT has been without load for hours.

Ω
°C
%

User value: the manufacturer's or the one in your test procedure.

Ω
Ω
Ω
Ω
Ω
A
A
A
A
%

User value. The resistance per turn must be almost the same on every tap.

E2Insulation readings
V
MΩ
MΩ

User value: the one in your test procedure or from the manufacturer.

MΩ
E2Demagnetization

Winding resistance or polarity with a battery.

V
E3Test set connection
E3Test set connection
E3Test set connection
E3Test set connection
E3Test set connection
E3Test set connection
E4Trend
%

User value. The ratio uses the class limit.

Use a decimal point. The calculation runs in your browser and updates as you type.

Test set connection

—

Test result

—

IEC / IEEE knee

—

Test plan

—

CT with the test-set connection: Ratio
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
CT with the test-set connection: Excitation
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
CT with the test-set connection: Load
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
CT with the test-set connection: Resistance
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
CT with the test-set connection: Insulation
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
CT with the test-set connection: Demagnetization
  • Source
  • Measured
  • Error
Magenta halo: what is energized. Green halo: what is measured. A dashed red lead is connected wrong.
Excitation curve on log-log axes
  • Measured
  • Original
  • Required
Square: IEC knee (+10 % voltage needs +50 % current). Circle: IEEE knee (tangent at 45°).
Test plan and results sheet
Each row uses the same criterion as its sheet. The trend compares with the previous test.

Step-by-step calculation

Test plan and results sheet

TestExpectedMeasuredStatusTrendSource

What it is for

A current transformer that measures wrong makes the protection trip when it should not, or not trip. These tests check that the CT has its rated ratio and polarity, that its core does not saturate too early, that the connected burden fits its class and that the insulation is sound.

Each test has its own sheet. The drawing shows the outdoor CT with its primary P1-P2, its cores, the terminal box and the test-set connection. If a lead goes to the wrong terminal, the tool marks it as a failure and explains why.

How it is calculated

IS 2705-1:1992§ 3.13current error

Ratio error

ε = (Kn·Is − Ip) · 100 / Ip · voltage method: N ≈ Vs/Vp

Kn is the rated ratio. With the current method it is compared with the class table at the test point; the voltage method gives the turns ratio.

IS 2705-4:1992§ 2.1IEC knee

IEC and IEEE knee points

I(1.1·Vk) = 1.5·I(Vk) · IEEE: d(log V)/d(log I) = 1

The measured curve is interpolated on log-log axes. The IEEE knee is where the slope passes through 45° (NPAG, §6.4.13; FIST 3-8, appendix E).

IS 2705-3:1992§ 7.1.2.2indirect composite error

Composite error from the excitation curve

E = ALF·In·|Rct,75 + Zb| · εc ≈ Ie(E)·100 / (ALF·In)

Valid for low-reactance CTs with a toroidal core and an evenly spread winding. A measuring core uses the instrument security factor: the current must reach 10 % (IS 2705-2, 7.1.2).

IS 2705-1:1992§ D-1.1.2copper resistance

Resistance at 75 °C and burden

R75 = RT·(234.5 + 75)/(234.5 + T) · S = (V/I + Rlead)·In2

The burden is measured by injecting current into the burden side with the CT disconnected (FIST 3-8, appendix D).

Limits of the calculation

  • The class limits are those of IS 2705 (1992). For a new CT, confirm them with IEC 61869-2 or with the manufacturer.
  • The primary insulation and the resistance tolerance against the factory value have no published limit in the sources used: you type them.
  • Insulation resistance is not corrected for temperature and the polarization index is not calculated.
  • The drawing is a typical three-core CT. If yours is arranged differently, use the equivalent terminals.
  • The composite error by the indirect method is only valid for low-leakage-reactance CTs.

Frequently asked questions

Which field tests are made on a current transformer?

Ratio and polarity, the excitation curve and its knee point, secondary winding resistance, insulation, connected burden and demagnetization. FIST 3-8 asks for the ratio at commissioning and for the excitation at commissioning and at least every 6 years.

What is the difference between the IEC and the IEEE knee point?

The IEC knee is the voltage from which 10 % more voltage needs 50 % more exciting current. The IEEE knee is the point where a 45° line is tangent to the curve drawn on log-log axes. The IEEE knee sits lower on the curve.

Why does the CT have to be demagnetized?

A DC test, such as the resistance test or the battery polarity check, leaves remanent flux in the core. That flux distorts the excitation and the ratio, and in service it can saturate the CT early. The core is demagnetized with AC voltage that first saturates it and then falls continuously to zero.

What happens if a CT secondary is opened with current in the primary?

The CT tries to keep the current flowing and the secondary voltage rises to very high values. It can break down the insulation, damage the CT and injure anyone nearby. That is why the secondaries not being measured are left shorted and earthed.