Home / Tools / Function 50/51 overcurrent
Function 50/51 and 50N/51N: overcurrent
Phase and ground overcurrent with IEC and IEEE curves: pickup, reset, times with tolerance, the relay inside and an injection test plan.
Siemens SIPROTEC 5§ 11.15curves and tolerancesIEC 60255-151§ 2009curvesIEEE C37.2§ 2008function numbers
Results
—
—
—
—
Charts
- Rating
- Active signal
- Characteristic
- Tolerance band and point
How it was calculated and standards
Test plan with injection test set Pro
| # | Test | Injection | Expected | Minimum | Maximum | Measured | Result |
|---|
What each parameter is
| Parameter | Value | What it does |
|---|
Loading these settings into a relay? We configure it remotely.
What it is for
The 50/51 is the overcurrent protection: it trips when the current exceeds a set value. The 51 waits a time that depends on the current (inverse-time curve) or a fixed time; the 50 trips with no delay or a short one. The 50N/51N does the same with the residual current 3I0, which is almost zero in normal service and appears mainly in ground faults.
This tool shows where each signal comes from: the bay CTs, the relay current inputs, the logic that combines the steps and the output that energizes the breaker trip coil.
How it operates
- Pickup: for the IEC and IEEE curves the Siemens SIPROTEC 5 manual states that the curve runs from 1.1 times the setting and that the stage resets below 1.045 times.
- Time: the inverse-time curve gives the time at the current the relay sees; the definite-time stages wait for their time delay.
- Selectivity: the blocking input lets the downstream relay stop the 50 of this relay while it clears its fault.
- Earth: with the CTs in star, the sum of the three phases enters through the IN input; in a single-phase fault it equals the current of the faulted phase.
The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.
Test plan
The plan looks for pickup with a ramp that starts 5 times the tolerance below and advances in steps of one tenth of the tolerance, for reset with the ramp reversed, and for the times at 2, 5 and 10 times the setting.
The phases are tested with a balanced three-phase set, so the 51N sees no current. Earth is tested with a single phase: block the phase functions with the blocking input, or disable them during that test.
Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.
Limits of the calculation
- The default tolerances are those of the cited manual: enter those of your relay.
- CT saturation, inrush blocking and dynamic pickup are not modeled.
- Definite-time delays do not include the relay's own operating time or that of the output.
Frequently asked questions
Why does the inverse-time curve not pick up exactly at the setting?
Because that is what the manufacturer states: in the Siemens SIPROTEC 5 manual the curve runs from 1.1 times the setting and resets at 1.045 times. Other manufacturers use other factors; look them up in your relay's manual.
At what currents are the 51 times tested?
At 2, 5 and 10 times the setting, within the 2 to 20 times range in which the manufacturer declares the time accuracy. If the 50 operates first at any of these points, the plan flags it so you can block or disable it.
How do you test the 51N without tripping the phases?
Injecting through a single phase and blocking the phase functions with the blocking input, or disabling them while ground is tested. The plan flags the points where the ground current exceeds the phase pickup.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws