Power cable tests

Pick the test, check on the drawing how the test kit is connected and type your results: the tool compares them with the open criteria of NEETRAC (CDFI) and Horizon Power, locates the partial discharge along the cable and builds the plan with the results sheet.

NEETRAC CDFI II§ 6VLF tan δNEETRAC CDFI II§ 7.3.2discharge locationNEETRAC CDFI II§ 9VLF withstand testHorizon Power HPC-4DL-07-0005-2014§ 5, 8oversheath and VLF

Example cases
Power cable tests

Only the basic data; the rest is taken with typical values.

ALearn

E1Cable
kV

U0 = U/√3 is the voltage between conductor and screen.

m
years

Horizon Power lowers the VLF voltage to 60 % for cables over 30 years old.

E2Test-kit connection

High voltage output (VLF) or positive of the DC source (oversheath).

Divider or PD coupler. The oversheath test does not use it.

E3VLF withstand test

Sinusoidal: rms value. Cosine-rectangular: peak value, equal to the rms.

kV
Hz
min
kV
min
E4Tan delta

For a new cable the provisional new-cable criterion is used.

×10⁻³
×10⁻³
×10⁻³
×10⁻³

From the readings taken at U0: it measures stability over time.

×10⁻³
×10⁻³
E5Partial discharges
kV
kV
kV
pC
pC

Your data or your provider's: there is no public limit for cables in the field.

% of c

Measure it with the reflectometer on the same cable; MV cables range from 42 % to 59 %.

µs
kV
E6Oversheath
mm
kV
min
MΩ
MΩ
E7Trend
%

From your procedure. Empty: the change against the previous test is only reported.

Use a decimal point. The calculation runs in your browser and updates as you type.

Findings

—

Connection errors

—

Applied voltage in times U0

—

Required voltage and duration

— kV

Mean tan δ at U0

— ×10⁻³

Tip-up (1.5 U0 − 0.5 U0)

— ×10⁻³

Cable class

—

Discharge inception in times U0

—

Discharge location

— m

Required oversheath voltage

— kV

Oversheath resistance

— MΩ

Plan points

—

Points without a result

—

The cable and the test-kit connection
  • Source
  • Measuring
  • Earth
Magenta: the source and what is energized. Green: the measuring lead and what is measured. Grey: earth. A wrong lead or bond is drawn in red.
Tan δ at 0.5 U0, U0 and 1.5 U0
  • This test
  • Previous test
The horizontal lines are the limits of the mean at U0 for the chosen insulation: below the first, no action required; above the second, action required.
Test plan and results sheet
The plan gathers the four tests of the chosen phase with the expected value and its source. Print it with the report.

Plan and results

TestPointExpectedMeasuredStatusChangeSource

Step-by-step calculation

What it is for

A shielded medium or high voltage cable is tested in the field with four tests: VLF withstand, VLF tan delta, partial discharge and the oversheath test. This tool draws the cable with its layers, terminations and screen, shows how the test kit is connected in each test and flags a wrong lead or bond as a failure. It then compares your results with published criteria and builds the test plan with the results sheet.

How it is calculated

NEETRAC CDFI II§ 9withstand test

VLF withstand test

U0 = U / √3 · times U0 = Uapplied / U0 · cycles = f × t

Voltage and duration are compared with the chosen reference. It passes if the cable withstands without breakdown and without signs of distress: excessive power to energize, audible arcing or discharge, or any other unusual observation (CDFI phase II, table 6 of ch. 9). For a sine wave the peak is √2 times the rms value; for cosine-rectangular they are equal.

NEETRAC CDFI II§ 6tan δ

VLF tan delta

tip-up = TD1.5U0 − TD0.5U0 · TuTu = (TD1.5U0 − TDU0) − (TDU0 − TD0.5U0)

Each feature (stability at U0, tip-up, tip-up of the tip-up and mean at U0) falls in one of three classes set by the 80th and 95th percentiles of the cables measured by CDFI. The cable's class is the worst one. In paper (PILC) the tip-up can be negative and has a band on each side.

NEETRAC CDFI II§ 7.3.2.1location

Location of the discharge

v = VoP × c · x = L − v · Δt / 2

The direct pulse reaches the near end first; the one travelling to the open far end is reflected and arrives Δt later. x is the distance from the near end.

Horizon Power HPC-4DL-07-0005-2014§ 5oversheath

Oversheath test

UDC = min(4 kV/mm × e; 10 kV) · Rmin = R1000 m × 1000 / L

The DC voltage per millimetre of oversheath is the IEC 60229 value quoted by Prysmian (estimate). The minimum resistance at 1 kV is Horizon Power's for new HDPE oversheaths on 22 and 33 kV cables, which falls in inverse proportion to the length; for PVC it is 1 MΩ.

Limits of the calculation

  • IEEE 400, 400.2 and 400.3, IEC 60270, IEC 60229, IEC 60840 and IEC 62067 are paid standards and were not consulted. Values that the CDFI report or an open paper attributes to them are marked as estimates.
  • The CDFI tan δ criteria come from the population of cables measured in North America: they are a guide to set priorities, not an approval. Those for new cable are provisional.
  • There is no public picocoulomb limit for medium voltage cables in the field: the magnitude is only judged against the limit you type. Inception and extinction voltages are reported against U0.
  • The minimum oversheath resistance applies to new 22 and 33 kV cables; otherwise it is only a reference. The duration of the DC oversheath test is your data.
  • The drawing shows one phase. It is an aid to interpretation and does not replace the test-set manufacturer's procedure or the judgement of the person responsible for the cable.

Frequently asked questions

What voltage is applied in a maintenance VLF test?

For 5 to 35 kV cables, NEETRAC's CDFI report gives the values it attributes to IEEE 400.2-2013 (cl. 5.1): for example 16 kV rms sine for a 15 kV cable, for 30 min. The tool marks them as estimates because the standard was not consulted. If your specification gives another value, type it as your own data.

When does a tan δ result call for action?

CDFI grades four features (stability, tip-up, tip-up of the tip-up and mean at U0) in three classes based on the population of cables measured: no action required, further study advised and action required. The cable's class is the worst of the four.

Is there a picocoulomb limit for a medium voltage cable in the field?

There is no public one. CDFI explains that partial discharge providers' criteria are proprietary and that magnitude and inception voltage alone do not predict failure well. Type the limit of your specification or provider and the tool judges it.

Why are the screen bonds removed in the oversheath test?

Because the voltage is applied between the metallic screen and earth: with the screen earthed the source would be shorted and the oversheath would not be tested.