Home / Tools / Ground fault and neutral
Ground fault and neutral grounding
Enter your source, the capacitive current of the network and the neutral type: the tool calculates the single line-to-earth fault current, the neutral voltage and the voltage of the healthy phases and the coil tuning, and checks whether 50N, 67N, 59N and 64S see the fault.
IEC 60909-0§ 7.5single line-to-earth fault currentIEC 60071-2earth-fault factor, annex BIEEE 242§ 8.2grounding methodsIEEE C37.102§ 3.2generator grounding
Results
— A
— A
— V
—
— %
Charts
- Active signal
- Power circuit
- Faulted phase
- Healthy phases
- Displaced neutral
- Chosen method
- Faulted feeder
- 50N and 67N pickups
How it was calculated and standards
Step-by-step calculation
Sensitivity of the protections
The methods side by side
Need it for a real project? We carry out the full study, with its report.
What it is for
The way the neutral is connected to earth decides how much current flows in a single line-to-earth fault, how much the voltages of the healthy phases rise, whether the fault can be kept or must be cleared, and which function detects it. This tool compares the five methods on the same network: solid neutral, low or high resistance, reactance, Petersen coil and isolated neutral.
With the capacitive current of your network and the source data it calculates the fault current, the neutral current and voltage, the earth-fault factor, the tuning of the coil and the resistor, and checks whether 50N/51N, 67N, 59N and 64S see the fault with the margin you choose.
How it is calculated
IEC 60909-0§ 7.5formula (54)
Single line-to-earth fault current
IF = 3·E / |Z1 + Z2 + Z0 + 3·RF|The three sequence networks are connected in series. E is the phase voltage (with the IEC 60909-0:2016 c factor for the current), Z1 and Z2 come from the short-circuit power of the source and Z0 is the zero-sequence impedance seen from the fault.
A. Eberle§ IL 21zero-sequence circuit
Zero-sequence impedance
Z0 = 1 / [ 1/(Z0s + 3·Zn) + G + j·ω·C ]Z0s is the zero-sequence impedance of the source, Zn that of the neutral (the resistor, reactance or coil, three times in the zero-sequence circuit), C the capacitance of one phase to earth and G the losses of the network. In an isolated neutral there is no path through the neutral and only the capacitance remains.
Schneider CT 203§ p. 14tuned coil
Tuning and residual current
L·3C·ω² = 1 · v = (IC − IL)/IC · Ires ≈ IC·√(v² + d²)v is the detuning and d the damping (the loss current over IC). With exact tuning and no losses the fault current would be zero: what remains is the detuning and resistive current.
IEC 60071-2§ Anexo Bearth-fault factor
Earth-fault factor
k = max(|Vb|, |Vc|) / (E)It is the highest voltage of the healthy phases during the fault divided by the phase voltage without the fault. It is calculated with the sequence voltages and Fortescue. It is 1 with Z0 = Z1 and tends to √3 in isolated or resonant networks.
What changes with each neutral
- Solid: the fault current is high, close to the three-phase one or larger when Z0 is smaller than Z1 (IEC 60909-0:2016, §7.5); the healthy phases hardly rise. It should be cleared quickly (Schneider CT 203, p. 16).
- Low resistance: the current is limited to a few hundred amperes and the fault is cleared with a 50N/51N. The resistor is sized for about 10 s (IEEE 242-2001, §8.2.3).
- High resistance: the current is equal to or slightly larger than the capacitive one, a few amperes, and it reduces transients. The fault can be kept until a convenient time if the cable withstands the phase-to-phase voltage (IEEE 242-2001, §8.2.4).
- Reactance: it limits the current to a fraction of the three-phase one. With X0/X1 of 3 or less the system is still effectively grounded (IEEE C37.102-2006, §3.2.3).
- Petersen coil: it compensates the capacitive current and leaves about 2 to 20 A (Schneider CT 203, p. 14). Locating the fault needs a directional residual overcurrent or residual power protection (p. 15), which uses the active component.
- Isolated: the current is only the capacitive one and the two healthy phases rise to the phase-to-phase voltage. Keeping the fault exposes the network to a second fault (Schneider CT 203, pp. 13-14; IEEE 242-2001, §8.2.5).
Protections
The tool evaluates the settings you enter; it does not propose settings. The 50N/51N compares the pickup with the fault current (with the fault resistance you choose) and with the capacitive current of the biggest healthy feeder, which must not trip it. The 67N uses the component of the residual current that the method allows to tell apart. The 59N compares its pickup with the zero-sequence voltage and with the natural neutral displacement.
For a generator with high resistance, the 59N with about 5 V on the secondary of the distribution transformer leaves 2 to 5 % of the winding near the neutral uncovered (IEEE C37.102-2006, §4.3.3.1.1). A low-frequency injection 64S or a third-harmonic one covers that zone; their settings depend on the manufacturer and are not calculated here.
Limits of the calculation
- Fault model at the source bus, with the feeder represented by its capacitance: it does not calculate the voltage along a feeder or the touch and step voltages. For that, see the grounding resistance tool.
- The single line-to-earth fault current of an isolated or resonant-earthed system is not a short-circuit current in the sense of IEC 60909-0:2016: here it is calculated with the capacitive circuit of A. Eberle's letter 21.
- The damping, the natural neutral displacement, the split of the capacitance among feeders, the sensitivity margins and the relay settings have no typical value with a source: they are data of your network.
- It does not model ferroresonance, intermittent faults with restriking or the harmonic current of the coil. The R0/X1 ≤ 1 value of IEEE C62.92 was not consulted: the «effectively grounded» check uses only X0/X1 ≤ 3.
- It does not replace the network study, the design of the resistor or the coil, or the setting of the protections.
Frequently asked questions
What current flows in an earth fault with an isolated neutral?
Only the capacitive current of the cables and lines of the whole connected network, which leads the voltage by 90°. It is usually a few amperes in a plant and can exceed 10 A in a network of long cables. The faulted phase goes to zero and the two healthy ones rise to the phase-to-phase voltage, a factor of √3.
What does a Petersen coil do?
It is connected between the neutral and earth and its inductance is tuned to the network capacitance (L·3C·ω² = 1). In a fault, the inductive current of the coil cancels almost all the capacitive one and the current that remains, a few amperes, is the one due to detuning and losses. Many arcs extinguish themselves.
When is a system said to be effectively grounded?
The IEEE C37.102-2006 guide recommends keeping the X0/X1 ratio at 3 or less. With X0/X1 = 3 and no fault resistance, the earth-fault factor of the healthy phases is 1.25 (calculation with symmetrical components) and the single line-to-earth fault current is a large part of the three-phase one.
We study the grounding of your network
We calculate the capacitive current of your network, compare the neutral methods, size the resistor or the coil and set the earth-fault protections.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws