Function 94: trip logic

Trip logic 94: minimum trip command time, reset criterion and close blocking, the relay inside and a test plan with the test set.

IEEE C37.2§ 3.1.94function numbersSiemens SIPROTEC 5§ 5.5.4trip logicSiemens SIPROTEC 5§ 5.5.5.6command duration

Example cases
Function 94: trip logic

Only the basic data; the rest is taken with typical values.

ALearn

E1Settings

The cited manual recommends «with I<»: the command is withdrawn when the function has reset and no current flows any more.

s
A

Below this current the relay considers the pole open.

E3Simulation
s

Example value: write the one of your breaker.

s

From the moment the fault disappears until the function withdraws its trip; it is in the manual of each function.

A

For example the load current in parallel during a test with the bay in service.

E4Installation and test set
A

Only to show the primary values.

A

Example value: enter that of your test set. Points that exceed it are marked.

A

Above the pickup of the function that trips in your relay.

E5Relay tolerances
%
% of In
%
ms
ms

Use a decimal point. The calculation runs in your browser and updates as you type.

Function status

—

Operating time

—

Trip command

—

Test plan

—

From the primary to the relay and the trip coil
  • Rating
  • Active signal
Magenta lines are the primary; light lines are the protection and control wiring; dashed yellow lines are the communications. What lights up in yellow is what changes in the simulation.
Function characteristic with its tolerance
  • Characteristic
  • Tolerance band and point
The curve or the steps are the settings; the yellow band is the declared tolerance; the point is the simulation.
Test set connected to the relay
Select a point in the “Test plan” tab: the drawing shows what the test set injects at each terminal. Before connecting, short-circuit the CTs and open the VTs and the trip circuit at the test block.

Test plan with injection test set Pro

#TestInjectionExpectedMinimumMaximumMeasuredResult

What each parameter is

ParameterValueWhat it does

Loading these settings into a relay? We configure it remotely.

What it is for

The 94 is the logic that gathers the trips of all functions and gives the command to the trip coil. It decides how long that command lasts: long enough for the breaker to open fully, and not so long that it stays stuck afterwards.

It is also a trip-free relay: while there is a trip command, a close command does not act, so the breaker does not close and open again and again onto the fault.

How it operates

  • The command lasts at least the minimum time set, even if the fault is cleared earlier.
  • Then it is withdrawn according to the criterion: when the function that tripped resets, when the current also drops below the open breaker threshold, or when the 52a also shows the breaker open.
  • If the breaker does not open, the current goes on and the command is held: this is what the breaker failure protection relies on.

The relay drawing is the same in all Tiza protection functions: a generic numerical relay, not a specific brand. Its terminals, blocks and inputs light up according to the function.

Test plan

The test set injects the fault and its binary input reads BO1. First the minimum duration is measured with a very short fault, then the duration with a long fault.

Then the reset criterion is tested: with load current after the fault, with the 52a held closed by an output of the test set and with a current ramp to read the threshold. Finally it is checked that a close command does not act during the trip.

Before connecting the test set: short-circuit the CT secondaries at the test block, open the VT secondaries on the yard side, and open the trip links to the breaker and to other relays. The results sheet is printed or downloaded as CSV with the measured values and the result of each point.

Limits of the calculation

  • The cited manual declares no tolerances for the minimum duration or for the open breaker threshold: the bands use those of the relay timers and current and are marked as estimates.
  • The reset of each function depends on that function: write it from its manual.
  • A three-pole trip is simulated; single-pole tripping and pole discrepancy are not modelled.
  • The close block during the trip follows the definition of device 94; the cited manual does not describe it and it depends on the configuration of each relay.

Frequently asked questions

Why does the trip command have a minimum duration?

So that the breaker reaches its end position and the relay contact does not open while the coil current is still flowing, which would burn it.

Which reset criterion is best?

The cited manual recommends «with I<». «With reset» is useful for tests with the load in service, because the test current adds to the load current and never drops below the threshold.

What does trip-free mean?

That the trip rules: if a close command arrives while there is a trip command, the close does not act. This keeps the breaker from closing and opening repeatedly onto a fault.