Home / Tools / Equipment harmonic emission
Harmonic emission of equipment up to 16 A (IEC 61000-3-2)
Choose the type of equipment and simulate its input stage or type the measured spectrum: the tool classifies it, works out the limits of its class and marks order by order whether it complies, is disregarded or exceeds, with the reconstructed current wave.
IEC 61000-3-2:2014§ 5classificationIEC 61000-3-2:2014§ 6.2.3.4, 7limits per class
Results
—
—
—
—
Charts
- Class A
- Class B
- Class D
- Class C
How it was calculated and standards
Result per order
| Order | Current | Limit | Ratio | Status |
|---|
What it is for
Before taking equipment to a test, or when choosing it, it pays to know whether its harmonic current fits the limits of IEC 61000-3-2. The tool classifies the equipment, works out the limits of its class and compares them order by order with the spectrum you measure or simulate.
The rectifier simulator shows why a power supply without a filter fails and how much an input choke helps, before going to an active power factor corrector.
How it is calculated
IEC 61000-3-2:2014§ 5, 7classes and limits
Limit of each order by class
A: Table 1 · B: 1.5 × Table 1 · C (> 25 W): % of I1, with 30·λ % for the 3rd · D: min(mA/W × P; Table 1)In class D and in discharge lighting of 25 W or less the limit is proportional to the measured active power. Small discharge lighting also complies if the 3rd stays within 86 % and the 5th within 61 % of the fundamental and the wave meets the 60°, 65° and 90° angles.
IEC 61000-3-2:2014§ 6.2.3.4application of the limits
Harmonics that are disregarded and allowance of the high orders
In < max(0.006·Iinput; 5 mA) → disregarded · IPOHC = √(Σ In², n = 21, 23 … 39)If the partial odd harmonic current you measure stays within the one calculated from the limits, each odd order 21 to 39 may reach 150 % of its limit.
Reconstructed wave and rectifier model
i(θ) = Σ √2·In·sin(nθ + φn) · THD = √(Σ In², n = 2 … 40)/I1The model solves the diode bridge with its capacitor and input choke in time until the cycle repeats, and takes the harmonics from the Fourier series.
Limits of the calculation
- The 2014 edition of IEC 61000-3-2 is used. The 2017 amendment and the 2018 edition were not reviewed.
- The standard compares averages over the whole observation period and limits each 1.5 s value to 150 % of the limit. With a single spectrum the tool compares that spectrum as if it were the average.
- The waveform test is checked on the wave reconstructed with the phases you type; without phases the wave is only a guide.
- For lighting of 25 W or less that is not discharge lighting, the 2014 edition gives no rule in 7.3 b): the tool warns and gives no verdict.
- Below 220 V line-to-neutral, as in 120 V networks, the standard does not set limits yet: the comparison is only a guide.
Frequently asked questions
Which equipment does IEC 61000-3-2 cover?
Electrical and electronic equipment up to 16 A per phase connected to the public low-voltage network. Above 16 A, IEC 61000-3-12 applies. The 2014 edition does not set limits yet for networks below 220 V line-to-neutral.
How do I know whether my equipment is class A, B, C or D?
By its type. Class B is for portable tools and non-professional welders, C for lighting and D for computers, monitors, TV sets and refrigerators with drives up to 600 W. Anything not in B, C or D is class A.
Which harmonics are disregarded?
Those below 0.6 % of the input current or below 5 mA, whichever is greater. Also, for odd orders 21 to 39 the average may exceed the limit by up to 50 % if the partial odd harmonic current you measure stays within the one calculated from the limits.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsGrounding system testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws