Home / Tools / Grounding system tests
Substation grounding system tests
Choose the test, connect the leads of the earth tester or the micro-ohmmeter on the drawing and type your readings: the tool checks the connection, places the potential probe, judges the plateau, scales the step and touch voltages to the fault and compares each result with its source.
MIL-HDBK-419A§ 2.7.2fall of potentialMIL-HDBK-419A§ 2.4.2.2resistivityMIL-HDBK-419A§ 7.3jointsTM 5-690§ 3-3 egrounding system tests
Results
—
—
—
—
—
—
Charts
- Readings
- Hemisphere model
- Measured
- Two layers
- Scaled to IG
- Tolerable
- Measured
- Limit
- Result
How it was calculated and standards
Test plan and results sheet
Each row is a point of the plan with its expected value, its source, the result of this test and the change from the previous one. It prints with the report.
| Test | Point | Expected | Measured | Result | Change | Source |
|---|
What it is for
After a grid is built, and every so often, it is measured to know whether it protects people. This tool brings together the four field measurements of a substation grounding system and draws, for each one, where every lead of the test set goes.
You type your readings. The tool checks the connection, applies the corrections, compares with the criterion and its source and builds the plan with the results sheet.
What each test measures
MIL-HDBK-419A§ 2.7.2fall of potential
Grid resistance by fall of potential
R(x) = VP1-P2/IC1-C2 · xright = 0.618·DIt is the resistance between the grid and remote earth. The current flows between the grid and probe C2; the voltage is taken between the grid and probe P2. Moving P2 gives a curve; with uniform soil, the reading at 61.8 % of the distance is the true resistance.
MIL-HDBK-419A§ 2.4.2.2four probes
Soil resistivity
Wenner: ρ = 2πaR · Schlumberger: ρ = π·[(AB/2)² − (MN/2)²]/MN · RIt is the resistance of a cube of soil one metre on a side, in Ω·m. If it changes with spacing, the soil has layers: the tool fits a two-layer model to the Wenner curve.
Metrelstep and touch
Step and touch voltages
Vfault = Vmeasured · IG/ItTouch: between a structure and the ground 1 m from it. Step: between two points of the ground 1 m apart. A known current is injected into the grid and the voltage is measured; the result is scaled to the fault current.
MIL-HDBK-419A§ 7.3joints
Continuity between equipment and grid
R = UU+ U−/II+ I−, in mΩIt is the resistance of the copper path between the ground connection of a piece of equipment and a reference point of the grid. A high value reveals a broken ground lead or a loose or corroded connector.
Corrections
- Connection point away from the centre: the potential probe goes to 0.618·(D + X) − X from the connection point (MIL-HDBK-419A, equation 2-50).
- Plateau: with readings at ±10 % of the distance that agree within your tolerance, the result is the average of the three (AEMC note).
- Wenner probe depth: with b not negligible against a, the full four-probe formula is used (MIL-HDBK-419A, equation 2-12).
- Step and touch scaling: each reading is multiplied by I<sub>G</sub>/I<sub>t</sub>. With a 1 kΩ resistor across the terminals it is compared with the body voltage, 1000 Ω times the tolerable current.
- Season and rain: compare with the test from the same month of the year and measure at least two full days after the last rain (TM 5-690, 3-3 e).
Criteria and sources
| Test | Criterion | Source |
|---|---|---|
| Fall of potential | Current probe at 5 diagonals or more (90 % accuracy) | MIL-HDBK-419A, table 2-6 |
| Fall of potential | Readings at ±10 % within your tolerance | AEMC; user's tolerance |
| Fall of potential | Resistance less than or equal to the project value | User data |
| Resistivity | Close to uniform if max/min ≤ 1.5 | Tiza Group convention |
| Step and touch | Scaled voltage less than or equal to the tolerable one | Grounding tool (Dalziel) |
| Step and touch | Remote electrode at 5 diagonals or more | Metrel |
| Continuity | 5 mΩ to the reference, unless you type another value (estimate) | MIL-HDBK-419A, vol. 2, 1.13.3 f |
| Continuity | Above 0.5 Ω: open or loose connection (estimate) | TM 5-690, 3-3 e(6) and (7) |
Limits
- The 61.8 % rule assumes uniform soil and a grid that behaves like a hemisphere. With layers, or with shield wires and neutrals connected, the plateau may not appear.
- Very large grids: the intersecting-curves method is not solved here; the tool warns when the probe is less than five diagonals away.
- The tool does not filter 60 Hz noise or stray currents: the instrument does that.
- There is no universal grid resistance value: it depends on the design and on the step and touch voltages. Type the one for your project.
Frequently asked questions
Where does the potential probe go in the fall-of-potential test?
At 61.8 % of the distance between the grid centre and the current probe, if the soil is uniform. If you connect at a point X metres from the electrical centre, the position from that point is 0.618·(D + X) − X, per MIL-HDBK-419A (2.7.2.2).
How do I know the 62 % reading is valid?
Also measure 10 % of the distance before and after that point. If the three readings are close, the result is their average; if they change a lot, the current probe is too close and must be moved farther. Type the tolerance of your procedure: the tool uses it to judge the plateau.
How far does the current probe go?
MIL-HDBK-419A estimates about 90 % accuracy with the probe at five times the grid diagonal, 95 % at ten times and 98 % at twenty-five. For very large grids it recommends measuring several curves with the probe at one to two times the longest side and finding where they intersect.
Why are step and touch voltages scaled?
Because with the same geometry the soil responds linearly: the voltage measured with a small test current grows in the same proportion up to the grid current of the fault. The tool multiplies each reading by IG/It and compares it with the tolerable voltage.
Related guides
Other tools
All tools
Solar energy
PV system sizingPV production and energy costPV I-V curveAGPE classifier and connection proceduresCable voltage dropSolar plants and the grid codeP-Q capability testPPC control testsPlant model validationCND supervision indicatorsPMU tests and commissioningRenewable energy tax incentives (Colombia)
Protection
Function 50/51 overcurrentFunction 27/59 voltageFunction 81 frequencyFunction 67/67N directionalFunction 46 negative sequenceFunction 49 thermal overloadFunction 25 synchronism checkFunction 32 reverse powerFunction 51V voltage overcurrentFunction 64G stator groundFunction 27TN third harmonicFunction 64F rotor groundFunction 78 out-of-stepFunction 50/27 inadvertent energizationFunction 37 undercurrentFunction 38 bearingsFunction 48 incomplete sequenceFunction 66 starts per hourFunction 51LR locked rotorFunction 14 underspeedFunction 47 phase sequenceFunction 59N residual overvoltageFunction 60 fuse failureFunction 55 power factorFunction 46BC broken conductorFunction 68 power swing blockingFunction 87N restricted earth faultFunction 63 Buchholz and pressureFunction 26 oil temperatureFunction 71 oil levelFunction 87B bus differentialFunction 60C bank unbalanceFunction 51G neutral groundFunction 79 reclosingFunction 86 lockoutFunction 94 tripFunction 74 trip supervisionFunction 87L line differentialPhasor diagramRelay coordinationCurrent transformer: burden and saturationVector group compensation (87T)Frequency df/dt rampBreaker failure 50BF87 differential settingCT and VT selectorDistance setting 21MV feeder coordinationMotor protectionBoundary meteringGenerator protectionLoad shedding 81 and UVLSShunt reactorSynchronizing and closing 25/78Secondary arc and single-pole reclosing
Analysis and communications
COMTRADE records: viewer and generatorOscillography analysisIEC 61850 SCL viewerIEC 61850 SCL auditorIEC 61850 network: GOOSE/SV addresses and process busIEC 60870-5-104 APDU decoderIEC 61850 to IEC 60870-5-104 and 101 mappingICCP bilateral table checkerIP and VLAN planDNP3 and Modbus decoderTeleprotection channel timeOptical and radio link budgetTime synchronisationMMS control sequenceGOOSE simulatorIEC 61850 station networkInterlocking table and CILO equationsCause-and-effect matrix and logic checkerZones and conduits (IEC 62443-3-2)Zone firewall rule reviewerRoles and permissions (IEC 62351-8)IED X.509 certificate verifierDevice hardening baselineIncident response exercise (CNO 2188)Cybersecurity gap: CNO and IEC 62443
Equipment testing and diagnostics
Commissioning checklistCurrent transformer testsDisconnector and GIS switchgear testsPower cable testsVoltage transformer testsInsulation diagnosis: dissolved gases (DGA) and temperature correctionTransformer TTR testTransformer winding resistanceTransformer insulation, PI and DARTransformer power factor and capacitanceTransformer excitation currentTransformer SFRATransformer leakage reactanceTap changer dynamic resistanceCalibration and uncertaintyPCB equipment: classification and deadlinesRETIE pre-inspectionTransformer test interpreterCircuit breaker testsTest budgetMaintenance plan and health indexSF6 inventory and leakage
Electrical studies
Lightning protectionShort circuit and per-unit systemGround fault and neutralShort-circuit checkerPower transformerTransformer noiseSafety clearancesArc flashGrounding resistancePower-frequency electric and magnetic fieldsCurrent split factor SfApproach boundariesSubstation configuration selectorBusbar stressesInsulation co-ordinationTRV and short-line faultGenerator circuit-breakerInductive load switchingSwitch-fuse combinationDisconnector and earthing switchMV switchgear and GIS specifierMV cable insulation levelInsulator strings: mechanical checkSeismic qualification of substation equipmentSurge protective device selectionElectric vehicle charging station
Yard equipment control
Circuit breaker controlDisconnector controlTransformer controlMV switchgear controlCapacitor bank controlAuxiliary services controlIEC 61850 bay controllerRecloser control
Industry and power quality
Motor startingHarmonic distortion THD and TDDEquipment harmonic emissionHarmonic emission allocationCapacitor bankBattery sizingRegulatory quality indicatorsCapacitor bank protectionSubstation DC systemsPower qualityGenerating sets to ISO 8528Lighting design to RETILAPControl valve Cv and Kv and affinity laws