Which software each relay brand uses (QuickSet, DIGSI, PCM600, Easergy Studio, EnerVista), what it does, which files it produces and what to check.

By Shadai García, electrical engineer, founder and CEO of Tiza Group. Reviewed by the Tiza Group engineering team · .

system toolIED toolIED toolSSDSCDICDICDSCDSCDCIDCID21BCUrelaycontrollerMUSSDyard and functionsICD / IIDeach IEDSCDwhole systemCIDeach IED1. the SSD describes the yard and its functions2. each vendor supplies its ICD or IID3. the system tool builds the SCD4. the SCD goes back to each IED tool5. each tool generates and loads the CIDthe SCD gathers IEDs, datasets, GOOSE, SV and reportsan inconsistent SCD holds up commissioningWorkflowSSDICDSCDCIDIED© tizagrp.comsystem toolIED toolIED toolSSDSCDICDICDSCDSCDCIDCID21BCUrelaycontrollerMUSSDyard and functionsICD / IIDeach IEDSCDwhole systemCIDeach IED1. the SSD describes the yard and its functions2. each vendor supplies its ICD or IID3. the system tool builds the SCD4. the SCD goes back to each IED tool5. each tool generates and loads the CIDthe SCD gathers IEDs, datasets, GOOSE, SV and reportsan inconsistent SCD holds up commissioningWorkflowSSDICDSCDCIDIED© tizagrp.com
IEC 61850 SCL files: SSD, ICD, SCD and CID in the engineering workflow. Location in the system, operating principle and IEC 61850. Illustrative: actual values come from the nameplate and the manufacturer's manual.
Short answer

Each relay manufacturer has its own configuration software: AcSELerator QuickSet for SEL, DIGSI for Siemens, PCM600 for ABB and Hitachi Energy, Easergy Studio, Easergy Pro and SFT2841 for Schneider, and EnerVista for GE Vernova. With them you load the settings from the study, program the logic, configure communications and download records. In IEC 61850, a system tool is added that integrates all the devices into the SCD file.

What relay software does

Configuration software is the bridge between the protection coordination study and the relay installed in the panel. It covers four areas:

  • Protection settings: the enabled functions and their values, which come from the study and from the setting criteria.
  • Logic and I/O: which contact trips which breaker, which input blocks which function, interlocks, reclosing, targets and LEDs.
  • Communications: ports, addresses, DNP3 (IEEE 1815), Modbus or IEC 60870-5-103 and 104 maps, and the device’s IEC 61850 configuration.
  • Records and testing: downloading events and oscillography, live metering and commissioning tools.

Each brand’s tool

ManufacturerRelay toolRelays it works withSystem and analysis tool
SELAcSELerator QuickSetSEL relays, meters and controlsArchitect for IEC 61850; Synchrowave Event for records
SiemensDIGSI 4 and DIGSI 5SIPROTEC 4 and SIPROTEC 5IEC 61850 System Configurator; SIGRA for records
ABB and Hitachi EnergyPCM600Relion 670, 650, 615 and 620IET600 for the system; ITT600 for network testing
Schneider ElectricEasergy Studio (formerly MiCOM S1 Studio), Easergy Pro, SFT2841MiCOM, Easergy P3 and SepamThe project’s system tool
GE VernovaEnerVista UR Setup and 8 Series SetupMultilin UR and 8 SeriesLaunchpad for software and document management

Each tool has its own guide, covering what each module does and what is most often looked up:

  • SEL AcSELerator QuickSet, Architect and Grid software
  • Siemens DIGSI 4 and DIGSI 5 software
  • ABB and Hitachi Energy PCM600, IET600 and ITT600 software
  • Schneider Easergy Studio, Easergy Pro and SFT2841 software
  • GE EnerVista UR Setup, 8 Series Setup and Launchpad software

For reclosers, the electronic control has its own software; for example, NOJA CMS for NOJA Power reclosers.

What files it produces

Although each tool has its own format, the work always leaves the same kinds of file:

FileWhat it containsWho uses it
Settings or project fileSettings, logic, I/O and communications of the relay, in the brand’s native formatProtection engineering; the owner’s backup
ICD, CID or IIDIEC 61850 description of the device, in SCLSystem configuration tool
SCDThe whole IEC 61850 substation: devices, GOOSE, reports and networkIntegration and testing
Point listsSignals to SCADA in DNP3, Modbus or IEC 104Gateway and control center
RecordsEvents and oscillography, in native format and in COMTRADETrip analysis
Settings reportReadable listing of the loaded settingsReview, approval and archive

You can review SCL files in your browser with the IEC 61850 SCL viewer, a free tool on our site; the file is not uploaded to any server. What each type of file means is in IEC 61850 SCL files.

Two levels in IEC 61850

In an IEC 61850 substation two tools coexist. The manufacturer’s tool defines each relay and exports its description; the system tool, or system configurator, builds the SCD file with all the devices, their GOOSE messages and their reports, and returns each relay its configuration. If someone changes a relay with its software without updating the SCD, or the other way round, GOOSE messages stop arriving or SCADA stops receiving reports. The editions of the standard also matter; we explain them in IEC 61850 Edition 1, 2 and 2.1.

Versions, firmware and drivers

The rule that prevents the most problems: the version of the software and of its drivers or device packages must support the relay firmware. Therefore:

  • Software older than the firmware does not recognize the relay.
  • A file made for another firmware version may not open, or may open with settings that are renamed or disappear.
  • A firmware upgrade on an in-service relay is an intervention, not a formality: it can change functions, require the settings file to be converted and, in some families, need the manufacturer.

Before any change, read the relay, save the backup and compare it with the project file, because the office file and the field file do not always match.

Common mistakes when configuring a relay

The most frequent problems do not come from the relay but from how the files are handled:

  • Loading a file that is not the approved one. Several versions of the same file circulate among the designer, the contractor and the owner; the wrong one gets loaded.
  • Correct settings with the wrong logic. The protection values match the study, but a trip contact was assigned to another output or a blocking input was inverted. A functional test catches it; a settings review does not.
  • Changing the relay and not the SCD. The relay is fine, but it stops publishing the GOOSE that other bays expected.
  • Unchecked settings groups. The active group is correct, but the alternate one keeps factory values and goes into service with a topology change.
  • No final report. No readable listing of what was loaded is approved and archived, and the next intervention starts without knowing what is in the relay.

Installation and download

  • Official source. Download the software and its packages only from the manufacturer’s website or software manager. Copies of unknown origin are a risk to the substation network.
  • Licenses. Some basic setting tools download without a license and others require one; system and analysis tools usually do.
  • The connection to the relay. Port, driver and firmware version must match; see how to connect to a protective relay.
  • A controlled engineering computer. Many companies dedicate laptops to protection engineering, with the approved software versions and no general use.

We configure your relays with the manufacturer’s software

At Tiza Group we work with the official tools of the main brands. With remote relay configuration we read your relay, compare it with the study, prepare the file and load it with your authorization, without traveling. See the brand pages: SEL, Siemens SIPROTEC, Hitachi Energy and ABB Relion, Schneider Easergy and MiCOM and GE Multilin.

References

  • IEC 61850-6, Configuration description language for communication in power utility automation systems related to IEDs (SCL).
  • SEL, AcSELerator QuickSet (SEL-5030) and Architect (SEL-5032) documentation.
  • Siemens, DIGSI 5, IEC 61850 System Configurator and SIGRA documentation.
  • Hitachi Energy, PCM600 and IET600 documentation.
  • Schneider Electric, Easergy Studio, Easergy Pro and SFT2841 documentation.
  • GE Vernova, EnerVista UR Setup and 8 Series Setup documentation.

Frequently asked questions

Is there software that configures relays of every brand?

Not for protection settings and logic: each brand uses its own tool, because each one implements the functions in its own way. What is common across brands is the IEC 61850 engineering of the substation, which is done by exchanging SCL files with a system configuration tool.

Why won't my settings file open in the software?

It is almost always the version: the file was made for a different firmware, or the installed software lacks the driver or package for that model and version. The fix is to open it with the right version or convert it with the manufacturer's tool, and then check the settings against the study, because conversion does not guarantee equivalence.

Is relay configuration software free?

It depends on the brand and the tool. Some basic setting tools can be downloaded without a license from the manufacturer's website, and others, particularly system engineering, analysis or fleet management tools, require a license. Always download them from the manufacturer's official channels.