Per-unit base conversion

Calculate the base current and base impedance of a three-phase system and bring the nameplate impedance of a transformer, generator or line to the common study base, in %, pu or ohms.

Grainger and Stevensonper-unit system, ch. 2Glover, Sarma and Overbyechange of base, ch. 3

Example cases
Per-unit base conversion
E1Study base
MVA
kV
E2Equipment impedance
MVA
kV

The one on the side that is in the zone of the base voltage.

Use a decimal point. The calculation runs in your browser and updates as you type.

Impedance on the study base

— pu

The same, in percent

— %

In ohms, Vbase zone

— Ω

Base current

— A

Base impedance

— Ω

Three-phase fault behind this impedance

— kA

Step-by-step calculation

How to use the result

    Example: three elements on a common 100 MVA base

    13.8 kV in the generator zone and 115 kV in the line zone.

    ElementNameplate dataCalculationX (pu)
    Generator50 MVA, 13.2 kV, X″d = 18 %0.18 · (13.2 / 13.8)² · (100 / 50)0.3294
    Transformer60 MVA, 13.8/115 kV, X = 10 %0.10 · (100 / 60)0.1667
    Line115 kV, X = 25 Ω25 / (115² / 100)0.189

    What it is for

    To build the impedance diagram of a short-circuit, coordination or load-flow study: each piece of equipment comes with its impedance on its own base (the nameplate) and all of them must be brought to a common base before adding them. It also helps to check a nameplate value quickly, compare the impedance measured in a transformer test with its nameplate, or convert the ohms of a line to per unit.

    How it is calculated

    For a three-phase system, with the three-phase base power and the line-to-line base voltage (Grainger and Stevenson, Power System Analysis, ch. 2; Glover, Sarma and Overbye, Power System Analysis and Design, ch. 3):

    Base quantities

    Ibase = Sbase / (√3 · Vbase)Zbase = Vbase² / Sbase

    With Sbase in MVA and Vbase in kV, Ibase comes out in kA and Zbase in ohms. Per unit and percent: Zpu = ZΩ / Zbase and Z% = 100 · Zpu.

    Change of base

    Znew = Zold · (Vold / Vnew)² · (Snew / Sold)

    With both impedances in pu.

    Ohms to the study base

    Zpu = ZΩ · Sbase / Vzone²

    Vzone is the base voltage of the zone where the ohms are measured, obtained by carrying Vbase through the rated transformer ratios; it is not the rated voltage of the equipment. If that zone differs from the Vbase zone, the formula already refers the ohms with the ratio of the base voltages, so the two voltages do not need to match.

    Three-phase fault behind the impedance

    Isc = Ibase / Zpu

    It is the current with an infinite source behind and only this impedance in series, in the Vbase zone, with 1 pu pre-fault voltage. It is good for comparing orders of magnitude; the actual short circuit needs the source impedance and the IEC 60909 voltage factor.

    The same conversion applies separately to resistance and reactance, and to the positive-, negative- and zero-sequence impedances.

    Limits of the calculation

    • It assumes a balanced three-phase system and voltage bases that follow the rated transformer ratios.
    • It does not account for off-nominal taps, nameplate tolerances or standard-based generator impedance corrections (for example, the IEC 60909 KG factor).
    • In single-phase systems the base current is Sbase / Vbase.
    • A short-circuit or protection coordination study needs the complete network model.

    Frequently asked questions

    How is a transformer impedance changed to another base?

    Multiply the nameplate per-unit impedance by the square of the ratio between the nameplate voltage and the new base voltage, and by the ratio between the new base power and the nameplate power: Znew = Zrated · (Vrated / Vnew)² · (Snew / Srated). A 60 MVA transformer with 10 % becomes 0.1667 pu on a 100 MVA base at the same voltage.

    Why is the per-unit system used in power system studies?

    Because with voltage bases that follow the transformer ratios, the impedance of each element is the same seen from either side and the ideal transformers drop out of the circuit. Also, the impedances of similar equipment fall in known ranges, which helps spot wrong data.

    Which base voltage is used on each side of a transformer?

    A base voltage is chosen in one zone and carried to the others with the rated voltage ratio of the transformer. If the base is 115 kV on the HV side of a 115/13.8 kV transformer, the LV side base is 13.8 kV. The base power is the same throughout the system.

    We do your power system study

    We model the network with the nameplate data of your equipment, calculate the short circuit, coordinate the protection and deliver the calculation report. We do it remotely, with no travel.

    Other tools

    COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Relay coordinationUp to six relays, reclosers and fuses on a log-log plot, with the IEEE C57.109 damage curve, inrush and the coordination margin of each pair.Inverse-time curvesCalculator and log-log plot of the IEC 60255-151 and IEEE C37.112 curves, with the coordination margin.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Symmetrical componentsPhase quantities to zero, positive and negative sequence and back (Fortescue), with phasor diagrams and what they mean for 46, 67Q and 51N.Vector group compensation (87T)TAP of each winding, phase compensation matrix, zero-sequence removal and the HV-to-LV clock diagram.Primary and secondary impedance (21)Primary to secondary ohms with the CT and VT ratios, line Z1, Z0 and k0, and zone reaches on the R-X plane.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.