Primary and secondary impedance for the 21

Calculate the line impedance from its ohms per kilometer, the ground compensation factor k0 in both of its forms, and the reaches of the zones you define, in primary and secondary ohms.

Blackburn and Dominsecondary Z = primary Z · CT ratio / VT ratioDistance relay (21) manualsk0 as magnitude and angle, RE/RL and XE/XL

Example cases
Primary and secondary impedance for the 21
E1Line
km
Ω/km
Ω/km
Ω/km
Ω/km
E2Instrument transformers
A

Enter each voltage with its base: the tool converts both to phase-to-phase before dividing.

E3Zone reaches, % of Z1
%
%
%
%

The preloaded percentages are an example: use the ones from your protection coordination study. Leave a zone empty to skip it.

E4Direct conversion
Ω

Use a decimal point. The calculation runs in your browser and updates as you type.

Line Z1, secondary

— Ω

Line Z1, primary

— Ω

k0 factor

—

k0 by components

—

Zone 1, secondary

— Ω

Direct conversion

— Ω

R-X plane, secondary ohms
  • Line Z1
  • Zone 1
  • Zones 2 to 4
Each zone is drawn as a reference mho circle with its diameter on the line angle, only to show the reach. Both axes use the same scale.

Step-by-step calculation

What it means for the settings

    What it is for

    Studies give the reaches in primary ohms, but many distance relays are set in secondary ohms and ask for ground compensation in their own format. This tool does that conversion without unit errors: use it to enter or review the settings of a 21, prepare the points of a secondary injection test, or check that a relay already set matches the line and the instrument transformers installed.

    How it is calculated

    Line impedance

    Z1 = (R1 + jX1) · L · Z0 = (R0 + jX0) · L

    With |Z| = √(R² + X²) and angle φ = arctan(X / R).

    Blackburn and DominProtective Relaying: Principles and Applications

    Primary to secondary

    Zsec = Zpri · CTR / VTR

    With the CT ratio CTR = Ipri / Isec and the VT ratio VTR = Vpri / Vsec, both voltages on the same base. If one is given phase-to-neutral, the tool multiplies it by √3 before dividing: mixing 115 kV phase-to-phase with 66.4 V phase-to-neutral without correction would give a √3 error. The angle does not change.

    Ground compensation

    k0 = (Z0 − Z1) / (3 · Z1) · RE/RL = (R0 − R1) / (3 · R1) · XE/XL = (X0 − X1) / (3 · X1)

    The first is a complex number given as magnitude and angle (the form used, for example, by SEL and ABB); the second, by components, is the one Siemens uses. In both cases the value is the same in primary and secondary. R0 can be lower than R1, and then RE/RL is negative.

    Reach of each zone

    Zzone = (percentage / 100) · |Z1|

    On the line angle, then converted to secondary with the same ratio. The zone 1 indicator is green below 90 % of the line, yellow between 90 % and 100 % (little margin for CT, VT and line data errors) and red from 100 %, because it would reach the remote bus. This is a Tiza convention; the percentage for each case comes from the study.

    Limits of the calculation

    • This is a conversion, not a setting: the percentages come from the protection coordination study, based on the adjacent line, the transformers at the remote substation, infeed and fault resistance.
    • It assumes a homogeneous line, without zero-sequence mutual coupling to parallel circuits and without series compensation; in those cases the effective k0 and the reaches change.
    • The mho in the chart is illustrative: if your relay uses a quadrilateral characteristic, the resistive reach is a separate setting this tool does not calculate.
    • Check whether your relay expects the reach in per-phase ohms (the usual case) and in which unit it takes the line angle.

    Frequently asked questions

    How are primary ohms converted to secondary ohms for a distance relay?

    Multiply the primary impedance by the CT ratio and divide it by the VT ratio: Zsec = Zpri · CTR / VTR. For example, with a 600/5 CT (CTR = 120) and a 115 kV/115 V VT (VTR = 1000), 10 primary ohms equal 1.2 secondary ohms.

    What is the k0 ground compensation factor?

    It is the ratio k0 = (Z0 − Z1) / (3·Z1) between the zero- and positive-sequence impedances of the line. The relay uses it so that the phase-to-ground loops measure the same positive-sequence impedance as the phase-to-phase loops. Some manufacturers ask for it as magnitude and angle, others as two numbers, RE/RL and XE/XL.

    Does k0 change between primary and secondary?

    No. k0 is a ratio of two impedances of the same line, so the CT and VT ratios cancel out. What does change with the ratios are the zone reaches in ohms.

    We set your distance protection

    We do the protection coordination study of the line, define the reach of each zone and the k0, and load the settings into the relay remotely, in the manufacturer's format.

    Related guides

    Other tools

    COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Relay coordinationUp to six relays, reclosers and fuses on a log-log plot, with the IEEE C57.109 damage curve, inrush and the coordination margin of each pair.Inverse-time curvesCalculator and log-log plot of the IEC 60255-151 and IEEE C37.112 curves, with the coordination margin.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Per-unit base conversionBase current and impedance, conversion between %, pu and ohms, and change of base for transformers, generators and lines.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Symmetrical componentsPhase quantities to zero, positive and negative sequence and back (Fortescue), with phasor diagrams and what they mean for 46, 67Q and 51N.Vector group compensation (87T)TAP of each winding, phase compensation matrix, zero-sequence removal and the HV-to-LV clock diagram.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.