Symmetrical components (Fortescue)

Enter the three phase currents or voltages with magnitude and angle and get the zero, positive and negative sequences, or go the other way. You see the phasor diagrams, the fault pattern and which protection functions respond to each sequence.

Fortescue (1918)symmetrical componentsIEC 60909-0§ 5.3.2symmetrical components, a = 1∠120°IEC 61000-2-2voltage unbalance V2/V1

Example cases
Symmetrical components (Fortescue)

Only the basic data; the rest is taken with typical values.

E1What you enter
E2Phase phasors
A
°
A
°
A
°
E3Sequence components, phase A
A
°
A
°
A
°

The fields on the calculated side fill in automatically. Negative angles and angles above 360° are accepted.

Use a decimal point. The calculation runs in your browser and updates as you type.

Positive sequence

— A

Negative sequence

— A

Zero sequence

— A

Unbalance I2/I1

— %

Ratio I0/I1

— %

Ideal pattern

—

Sequence systems
  • a
  • b
  • c
The three systems on the same scale. Phase a of each one is the calculated component; the other two rotate according to the chosen phase rotation.
Phase phasors
  • A
  • B
  • C
Angles measured from the horizontal axis, positive counterclockwise. The dashed ring marks half scale.

Values in polar and rectangular form

PhasorPolarRectangular

What the protection sees

    What it is for

    Numerical relays do not look only at the phase currents: they compute the symmetrical components and decide with them. Use this tool to check an oscillography or event report by hand, understand why a sequence element operated (or did not), prepare the values for a secondary injection test, or show a crew what the relay sees for each fault type.

    • Positive sequence (1): present in normal load and in every fault. Distance protection 21 and most metering use it.
    • Negative sequence (2): appears with any unbalance: asymmetrical faults, an open phase, unbalanced loads. It is used by 46 (unbalance and broken conductor, with I2/I1), directional 67Q and voltage element 47.
    • Zero sequence (0): exists only with a path to ground or a neutral. It is measured by 50N/51N as residual 3I0, by 67N (polarized with 3V0 or with neutral current) and by 59N as 3V0.

    How it is calculated

    Fortescue (1918)IEC 60909-0§ 5.3.2symmetrical components

    I0 = (Ia + Ib + Ic) / 3I1 = (Ia + a·Ib + a²·Ic) / 3I2 = (Ia + a²·Ib + a·Ic) / 3

    With the operator a = 1∠120° = −½ + j·√3/2 and ABC phase rotation (Anderson, Analysis of Faulted Power Systems; Blackburn, Symmetrical Components for Power Systems Engineering). For ACB rotation, b and c are swapped.

    Inverse transformation

    Ia = I0 + I1 + I2 · Ib = I0 + a²·I1 + a·I2 · Ic = I0 + a·I1 + a²·I2

    The same equations apply to voltages. The residual current measured by a relay with the three CTs in wye is Ia + Ib + Ic = 3I0.

    Fault patterns (no pre-fault load, referred to phase A)

    • Single-phase A-ground: I0 = I1 = I2. For B-ground, I1 = a·I0 and I2 = a²·I0; for C-ground, the other way round. The tool compares phasors, not only magnitudes.
    • Phase-to-phase B-C without ground: I0 = 0 and I2 = −I1. For C-A, I2 = −a·I1; for A-B, I2 = −a²·I1. An open phase with a load and no neutral gives the same pattern as a phase-to-phase fault on the other two phases.
    • Phase-to-phase-to-ground: the healthy phase carries no fault current (for example, Ia = 0 for B-C-ground) and there are I0 and I2.

    IEC 61000-2-2compatibility level of unbalance

    For voltages, the tool compares V2/V1 with the 2 % compatibility level of public low-voltage networks. Some networks with many single-phase loads reach 3 %, so between 2 and 3 % the indicator shows a warning.

    Limits of the calculation

    • This is the mathematical transformation, exact for the phasors you enter, but not a short-circuit study: it does not calculate how much current a real fault will draw, which depends on the sequence impedances of the network.
    • The fault patterns are the ideal ones, without pre-fault load current. With load, the current in the healthy phase is not zero and the relations hold only in part.
    • The phasors must be fundamental-frequency values, taken at the same instant and with the same angle reference. For an oscillography with DC offset or harmonics, use the filtered values from the relay software.
    • Some manufacturers refer the sequences to another phase or measure 3I0 with a neutral CT: check the relay manual before comparing values.

    Frequently asked questions

    How are the symmetrical components of three currents calculated?

    With the Fortescue equations: I0 = (Ia + Ib + Ic) / 3, I1 = (Ia + a·Ib + a²·Ic) / 3 and I2 = (Ia + a²·Ib + a·Ic) / 3, where a = 1∠120°. The sums are phasor sums: magnitude and angle of each phase matter, and so does the phase rotation of the system (ABC; for ACB, b and c are swapped).

    What is the difference between I0 and 3I0?

    I0 is the zero-sequence component of one phase. The sum of the three phase currents, which is what flows in the neutral or what a residually connected relay measures, equals 3I0. That is why 50N/51N and 67N are set in 3I0 on most relays; check in the manual which one yours uses.

    Why does an open phase produce so much negative-sequence current?

    With one phase open, the other two carry currents that no longer form a balanced set. In a load with no path to ground they become equal and opposite, which gives I2 equal to I1 in magnitude and no I0. That is why the I2/I1 ratio is the basis of broken-conductor detection (46BC) and of the 46 unbalance protection on motors and generators.

    We analyze your relay trip

    Send us the oscillography and the relay event report. Our team analyzes the sequences, the directionality and the settings, and tells you whether the protection operated correctly. If settings need correcting, we load them remotely.

    Related guides

    Other tools

    COMTRADE generatorCreate a COMTRADE fault record (.cfg/.dat or .cff) for your test set: fault, DC offset and breaker opening.ANSI / IEEE C37.2 device numbersDevice function numbers 1 to 94, common suffixes and their IEC 61850 logical node, with search.Relay coordinationUp to six relays, reclosers and fuses on a log-log plot, with the IEEE C57.109 damage curve, inrush and the coordination margin of each pair.Inverse-time curvesCalculator and log-log plot of the IEC 60255-151 and IEEE C37.112 curves, with the coordination margin.CT burdenLead resistance, relay burden and comparison with the rated burden of the current transformer.Short-circuit currentQuick estimate of the three-phase fault at the secondary of a transformer.COMTRADE viewerOpen .cfg/.dat or .cff fault records in your browser: waveforms, digital channels, cursor and RMS. The file is not uploaded.IEC 61850 SCL viewerOpen .scd, .cid or .icd files in your browser: IEDs, GOOSE and SV addresses, datasets, subscribers and checks. The file is not uploaded.GOOSE and SV addressesCheck IEC 61850 multicast MAC, APPID, VLAN and priority, find duplicates and export the table as CSV.Process bus networkSV and GOOSE bandwidth, worst-case latency, PRP, HSR or RSTP redundancy and PTP time error of an IEC 61850 network.Interlocking table and CILO equationsInterlocking matrix per device, IEC 61850 EnaOpn and EnaCls equations, GOOSE signals between bays and FAT/SAT test cases per configuration.Per-unit base conversionBase current and impedance, conversion between %, pu and ohms, and change of base for transformers, generators and lines.Harmonic distortion THD and TDDVoltage THD and current TDD against the IEEE 519-2022 limits, with the spectrum as a bar chart.Vector group compensation (87T)TAP of each winding, phase compensation matrix, zero-sequence removal and the HV-to-LV clock diagram.Primary and secondary impedance (21)Primary to secondary ohms with the CT and VT ratios, line Z1, Z0 and k0, and zone reaches on the R-X plane.CT saturationRequired versus available voltage (5P/10P, PX or C class), time to saturation and the saturated waveform.DGA interpretationIEEE C57.104-2019 DGA status, Duval triangles 1, 4 and 5, IEC 60599 ratios and CO₂/CO of your transformer.Insulation temperature correctionInsulation resistance at 40 °C (IEEE 43) or 20 °C, PI, DAR and power factor of transformers and bushings, with the trend.Capacitor bankkvar to correct the power factor, steps of the automatic bank, capacitance and resonance with the transformer.Cable voltage dropΔV and % with R and X per km, copper or aluminium, mm² or AWG/kcmil, and the short-circuit check of the cable size.Battery sizingAh, number of cells and charger of a DC battery bank from its duty cycle, per IEEE 485 and IEEE 1115.Grounding resistanceGround rods, horizontal conductor and grid (BS 7430, IEEE 80), and soil resistivity from Wenner measurements.Technical glossarySubstation, protection and communications terms, explained in one or two sentences.