Slow Fault Clearing at the Remote Line End: Causes

ANSI 85

Why one line end clears fast and the other in zone 2: failed teleprotection, weak source without echo, current reversal guard or a resistive fault.

By Shadai García, CEO and protection engineer at Tiza Group.

ABQ1Q221/8521/85channelQ321normal servicefault at 90 % of line A–BB sees it in Z1, trips, sends permissiveA: Z2 + permissive: trips at oncefast clearing at both endsrestorationfault behind B: B sends no permissiveA waits for Z2 time; Q3 clears firstnormal serviceZ2 at Apermissive from B&trip AZ2 at AZ1 at B and sendpermissive received at AA tripst Z2without permissive, A waits for Z2 timeIEC 61850PDISPSCHPTRCXCBR© tizagrp.comABQ1Q221/8521/85channelQ321normal servicefault at 90 % of line A–BB sees it in Z1, trips, sends permissiveA: Z2 + permissive: trips at oncefast clearing at both endsrestorationfault behind B: B sends no permissiveA waits for Z2 time; Q3 clears firstnormal serviceZ2 at Apermissive from B&trip AZ2 at AZ1 at B and sendpermissive received at AA tripst Z2without permissive, A waits for Z2 timeIEC 61850PDISPSCHPTRCXCBR© tizagrp.com
Teleprotection 85: POTT permissive trip over the channel. Connection, operating characteristic and IEC 61850. Illustrative: actual values come from the settings study.
Short answer

Distance zone 1 is set not to reach the opposite end, so a fault near one end is cleared instantly by that end and by the other only after the zone 2 time, unless a teleprotection scheme speeds up the trip. When the remote end clears slowly on a line that has teleprotection, the typical causes are a failed channel or a signal not received, a weak source without echo logic, an active current reversal guard, or a resistive fault the overreaching zone did not see.

Symptom

During a fault on a high or extra-high voltage line, the end closest to the fault opened in zone 1 time and the remote end did so well afterward, in zone 2 time or even through a backup protection. The fault stayed fed from one side during that interval, with an effect on stability, on equipment and on the users of the remote substation.

Distance protection 21 sets its zone 1 below the line length. Errors in the CTs (current transformers), the VTs (voltage transformers) and the line impedance do not allow a fault at the end of the line to be told apart with confidence from one just past the remote bus. That decision leaves at each end a strip in which the fault is seen only in zone 2, time-delayed. Teleprotection exists to close that gap: each end tells the other what it sees and both trip fast for internal faults. If the remote end cleared slowly, either the line has no teleprotection or it did not work for that fault.

Possible causes, from most to least likely

CauseWhy it happensWhat gives it away
Line without teleprotectionThe protection has only stepped zonesThe remote end’s time matches its zone 2 time
Failed channel or signal not receivedFailure of the teleprotection equipment, multiplexer or fiber; blocked signalChannel alarm; send recorded at one end with no receive at the other
Weak source at one end without echo logicThe weak end does not detect the fault and does not return permissionThe strong end sent permission and waited; the weak one tripped when the strong one opened
Current reversal guardAfter a fault on a parallel line, the guard blocks tripping for a timeFault on the parallel line just before, or current reversal recorded
Resistive fault outside the overreaching zoneFault resistance pushes the impedance outside the remote end’s characteristicThe remote end’s overreaching zone did not pick up
Scheme disabled or in testTest blocks open, function switched off after maintenanceNo send or receive in the events
CVT transientThe capacitor voltage transformer distorts the voltage in the first cyclesDelay of the distance element on close-in faults with low voltage
Slow remote breakerThe relay tripped on time, but the breaker was lateFast trip command and delayed opening; possible 50BF operation

What to check first

  1. Events from both ends aligned in time: pickup of each zone, teleprotection send and receive, trip and breaker opening. See event report and sequence of events.
  2. Teleprotection scheme of the line: POTT, PUTT, DCB, DCUB or other, and its echo and guard logic. See POTT scheme.
  3. Alarms from the channel and the teleprotection equipment before and during the fault.
  4. Current infeed from each end and the impedance seen by each relay, with the estimated fault resistance.
  5. Events on parallel lines immediately before the fault.
First check on slow clearing at the remote end
  • Does the line have teleprotection enabled?
    • No: Expected behavior: the remote end clears in zone 2
    • Yes: Did the remote end receive the signal from the other end?
      • No: Failed channel, teleprotection equipment or scheme in test
      • Yes: Did the remote end's overreaching zone pick up?
        • No: Weak source without echo or resistive fault outside its characteristic
        • Yes: Current reversal guard active or slow remote breaker

How to confirm

  • Reproducing the fault in both relays with the records from both ends, by synchronized injection. It shows whether the scheme should have tripped fast with those settings. See end-to-end tests.
  • Short-circuit calculation of the fault with its estimated location and resistance, to see what impedance each end should have measured and with what infeed.
  • Teleprotection channel test: transmission time, integrity and alarms.
  • Remote breaker timing if the relay issued the command on time. See circuit breaker operating time test.

How to keep it from coming back

  • Teleprotection on the lines where the required clearing times or stability demand it, with a scheme chosen for the line and the sources.
  • Echo and weak-infeed logic where one end has little source. See echo and weak-infeed logic.
  • Current reversal guard set with the real times of the channels and breakers. See current reversal guard.
  • Channel supervision with an alarm and automatic fallback to a backup scheme when it drops.
  • End-to-end testing after every change to the relays, the channel or the communications equipment.

How each scheme behaves when the channel fails

The choice of scheme determines what happens if the signal does not arrive. The difference explains why the same failed channel produces slow clearing on one line and an unwanted trip on another:

SchemeWhat each end sendsFast trip conditionWith the channel down
Direct underreaching transfer trip (DUTT)Trip command when its zone 1 picks upReceiving the commandNo acceleration; demands a very secure channel because a spurious signal trips
Permissive underreaching transfer trip (PUTT)Permission when its zone 1 picks upReceiving permission and seeing the fault in zone 2No acceleration; remote clearing stays in zone 2
Permissive overreaching transfer trip (POTT)Permission when its overreaching zone picks upReceiving permission and seeing the fault in that zoneNo acceleration; remote clearing stays in zone 2
Directional comparison blocking (DCB)Block when it sees the fault in the reverse directionNot receiving a block after a coordination timeMay overtrip on external faults, because the block is missing

In permissive schemes, loss of the channel degrades speed, and the backup is the stepped behavior of the zones; in the blocking scheme the degradation is in security. That is why blocking schemes are complemented with channel supervision and with logic that decides what to do if there is no guard signal. See POTT scheme.

Why zone 1 reach does not cover the whole line

Zone 1 reach is set to a fraction of the line impedance, usually around 80 to 90 %, to leave margin for CT and VT errors, zero-sequence impedance and calculation uncertainty. Up to 10 to 20 % of the line at each end falls outside zone 1, and in that strip each relay sees the fault only in zone 2. Faults in that strip are the ones that one end clears fast and the other slowly when there is no teleprotection or it is not available. It is a design limitation, not a relay defect, and it is solved with teleprotection or with line differential protection.

Capacitor voltage transformers and operating speed

CVTs include a ferroresonance suppression circuit that, on a sudden voltage collapse, produces a transient during the first cycles. When the ratio of source impedance to line impedance is high, the voltage during the fault is low and the transient can delay the impedance measurement. Relay manufacturers compensate for that condition with specific logic, whose behavior is described in their manual; if a distance relay trips slower on faults very close to the bus with a CVT, compare that delay with what the manufacturer declares before changing zones.

What not to do

  • Do not extend zone 1 beyond the line to “speed up” the remote end: selectivity with neighboring lines is lost.
  • Do not shorten the zone 2 time without reviewing coordination with adjacent lines.
  • Do not test the channel with teleprotection in service without coordinating the blocking of the outputs.
  • Do not analyze just one end: slow clearing is understood only with the records from both.

When to call us

If a line cleared slowly at one end, send us the records from both ends: we quote the trip analysis, a remote service available worldwide, and tell you why it was not accelerated. Our team reviews and adjusts the zones, the teleprotection, the echo and the guard through remote relay configuration; if the scheme and channel must be tested with both ends, we do it with end-to-end tests, in Colombia or elsewhere on request. Write to us.

References

  • IEEE C37.113-2025, Guide for Protective Relay Applications to Transmission Lines.
  • Blackburn and Domin, Protective Relaying: Principles and Applications.

Frequently asked questions

Why did one end of the line trip fast and the other take longer?

Because the fault was inside zone 1 of one end and outside that of the other. Without a working teleprotection scheme, the far end trips only when its zone 2 time expires. That is the expected behavior of distance protection without a channel, and it is exactly what teleprotection is meant to prevent.

What is sequential tripping on a line?

It is when one end does not detect the fault until the other one opens. It happens with weak sources or with faults that, seen from one end, fall outside its zones because of the infeed from the other end. When the strong end opens, the current distribution changes and the weak end sees the fault and trips, with a delay.

Is slow clearing at the remote end a compliance problem?

It can be. Grid codes and utility requirements set maximum fault clearing times, and the system operator reviews events. Clearing in zone 2 time on a line that was supposed to have accelerated tripping usually calls for an explanation.