Power Quality in Industry: Problems and Causes

Power quality problems in industrial plants: harmonics, sags, overvoltages, unbalance, flicker and reactive power. Causes, standards and measurement.

By Shadai García, CEO and protection engineer at Tiza Group.

utility gridconnection pointClass Aanalyzer=~MVFDMmotorsensitiveloadpickupmeasurement at the connection point with the utilityClass A measurement at the connection point12-cycle window at 60 Hz: 200 mseach window: Urms, THD and unbalancemotor starts: voltage sagUrms½ crosses 90 %: event recordedvoltage recovers10-min aggregation (IEC 61000-4-30)u(t)Urms90 %Urms½12-cycle valuemeasured in the windows and in the eventsIEC 61850TVTR / TCTRMMXUMHAIQVVR© tizagrp.comutility gridconnection pointClass Aanalyzer=~MVFDMmotorsensitiveloadpickupmeasurement at the connection point with the utilityClass A measurement at the connection point12-cycle window at 60 Hz: 200 mseach window: Urms, THD and unbalancemotor starts: voltage sagUrms½ crosses 90 %: event recordedvoltage recovers10-min aggregation (IEC 61000-4-30)u(t)Urms90 %Urms½12-cycle valuemeasured in the windows and in the eventsIEC 61850TVTR / TCTRMMXUMHAIQVVR© tizagrp.com
Power quality analyzer: 10/12-cycle windows, Urms½ and recording of a sag. Location in the system, operating principle and IEC 61850. Illustrative: actual values come from the nameplate and the manufacturer's manual.
Short answer

Power quality describes how close the voltage a plant receives is to an ideal sine wave, at nominal value and frequency, without interruptions. The most common problems in industry are harmonics, voltage sags, transient overvoltages, phase unbalance, flicker and low power factor. Some come from the grid and others are produced by the plant itself; telling them apart requires measuring with a Class A analyzer at the right points.

What power quality is

Plant equipment is designed for a voltage with a defined shape, value and frequency. Power quality measures how far the real voltage departs from that ideal, and how the currents the plant draws distort it.

A power quality problem is recognized by its effects: drives that trip for no reason, PLCs that reset, motors that overheat, capacitors that fail, lights that flicker, noisy transformers or a bill with reactive power charges. It is almost always diagnosed late, because the symptoms are blamed on the equipment and not on the power feeding it.

The problems, one by one

PhenomenonWhat it isTypical causeSymptom in the plant
HarmonicsComponents at multiples of the fundamental frequencyDrives, rectifiers, UPS, electronic lightingHeating of transformers and cables, failing capacitors, hot neutral
Voltage sagsBrief drops in RMS voltageFaults on the utility or plant network, large motor startsProcess stops, contactors dropping out, drives tripping
InterruptionsTotal loss of voltageGrid openings, reclosingTotal shutdown
Transient overvoltagesSpikes of microseconds to millisecondsLightning, switching of capacitor banks and breakersDamaged electronic boards, insulation failures
Slow voltage variationsHigh or low voltage for minutes or hoursWeak grid, transformer taps, variable loadHot motors, equipment out of range
UnbalanceDifferent phase voltagesPoorly distributed single-phase loads, a phase with a problemHot motors, unbalance trips
FlickerFast voltage fluctuations that make light flickerArc furnaces, welders, rapidly changing loadsComplaints about lighting from staff or neighbors
Low power factorMuch reactive power compared with activeMotors, transformers at no load, inadequate compensationReactive power charges, capacity occupied

Each phenomenon has its own guide:

Who produces them

Power quality is a shared responsibility. The utility must deliver a voltage within certain limits, and the plant must not distort it beyond what is allowed with its own loads.

  • They come from the grid: sags from faults on other circuits, interruptions, overvoltages from lightning on the lines, voltage variations and part of the background harmonic distortion.
  • The plant produces them: harmonics from its drives, flicker from its fluctuating loads, unbalance from its single-phase distribution, uncompensated reactive power, sags from starting its own motors.

Utilities and regulators set their own power quality rules, and we adapt the work to the local code and the utility requirements that apply to your project. Typically they measure voltage harmonic distortion against IEEE 519 or EN 50160, unbalance as the ratio of negative-sequence to positive-sequence voltage, sags and swells under IEC 61000-4-30 Class A, and flicker under IEC 61000-4-15. When a deficiency is found, they usually give the responsible party a period to correct it. To identify the source, the utility can install recorders on the network or at the customer boundary and require remedial measures to be designed.

Typical reference values

Reference values depend on the voltage level and on the document that applies. Two widely used references:

PhenomenonTypical reference
Steady-state voltageANSI C84.1 Range A: ±5 % of nominal at the service point. EN 50160 (low voltage): ±10 % for 95 % of the 10-minute values over a week
Voltage THD (IEEE 519-2022, at the PCC)8 % up to 1 kV; 5 % from 1 kV to 69 kV; 2.5 % from 69 kV to 161 kV; 1.5 % above 161 kV
FlickerShort-term severity Pst measured over 10 minutes, calculated under IEC 61000-4-15
Sags and swellsClassified under IEEE 1159 by duration: instantaneous (0.5 to 30 cycles), momentary (30 cycles to 3 s) and temporary (3 s to 1 min)

The IEEE 1159 classification distinguishes, for example, a sag of 0.5 to 30 cycles with a typical magnitude of 0.1 to 0.9 per unit from one of 3 seconds to 1 minute with the same magnitude. For that reason an event record must include its duration and not only its depth.

Reference standards

  • IEEE 1159: classifies the phenomena (transients, short- and long-duration variations, unbalance, distortion, fluctuations) and gives guidance to monitor them.
  • IEC 61000-4-30: defines how they are measured. A Class A analyzer gives results that are comparable and repeatable between instruments from different manufacturers. It is the one used when a measurement may end in a dispute with the utility.
  • IEEE 519: harmonic limits at the point of connection to the grid; see harmonic study under IEEE 519.
  • EN 50160: voltage characteristics delivered by public networks in Europe.
  • IEC 61000-2-4: compatibility levels in industrial networks.

What a Class A measurement does

IEC 61000-4-30 defines the measurement methods and classifies them by performance class. In Class A, the base measurement is made in windows of 10 cycles (50 Hz grid) or 12 cycles (60 Hz), about 200 ms, which are aggregated into intervals of 150/180 cycles (about 3 s) and 10 minutes. The 10-minute interval starts at an absolute clock boundary, and the long-term flicker interval is formed from twelve 10-minute intervals. A separate test standard, IEC 62586-2, covers conformity with Class A.

One principle of the standard is event flagging. When a sag occurs, the 10-minute values that contain it are flagged, and the other quantities, such as harmonics, unbalance and flicker, must reflect the normal condition of the grid. This way a single event is not counted twice in different parameters. Keep that flagging in mind when reading reports from a Class A analyzer, such as the Metrel MI 2892 and MI 2893.

How it is diagnosed

Power quality diagnosis in a plant
  1. Symptoms. What fails, when, on which equipment and since when
  2. Measurement. Class A analyzer at the boundary and at the suspect loads
  3. Correlation. Quality events against failures and plant operation
  4. Origin. Grid or plant, and which loads
  5. Solution. Filters, compensation, backup, protection or settings

The measurement is made with a power quality analyzer over a period that captures all shifts and days of the week, usually at least one week, at the grid boundary and at the suspect boards or loads. The most useful thing is an event log synchronized with what failed in the plant: if a drive tripped at 10:42, the analyzer must show what happened to the voltage at that time. To dig deeper into how to classify and monitor power quality phenomena, read power quality monitoring under IEEE 1159.

The most common mistake is to measure for a while with a clamp meter and conclude. Power quality problems are intermittent: a sag lasts tenths of a second and may happen twice a month.

How we help

Our team carries out the power quality study of your plant. We define where and how long to measure, analyze the records and events against your failures, identify the origin and design the solution, from filters and compensation to protection settings and backup for sensitive loads. We do the analysis and design remotely, worldwide, with your measurements. In Colombia, or elsewhere on request, we also measure on site. See our power quality service and write to us telling us what is failing.

References

  • IEEE 1159, Recommended Practice for Monitoring Electric Power Quality.
  • IEC 61000-4-30, Testing and measurement techniques – Power quality measurement methods.
  • IEC 61000-4-15, Flickermeter.
  • IEEE 519-2022, Standard for Harmonic Control in Electric Power Systems.
  • EN 50160, Voltage characteristics of electricity supplied by public electricity networks.
  • ANSI C84.1, Electric Power Systems and Equipment – Voltage Ratings (60 Hz).

Frequently asked questions

What are the most common power quality problems in an industrial plant?

Harmonics produced by drives and rectifiers, voltage sags from grid faults, transient overvoltages from lightning and switching, phase unbalance, flicker caused by fluctuating loads and low power factor. Each has different symptoms and solutions.

How do I know if the problem comes from the grid or from my plant?

By measuring at the same time at the grid boundary and at the suspect loads. If a disturbance appears first or stronger at the boundary and unrelated to what the plant runs, it comes from the grid; if it follows the start of certain machines, the plant produces it. The direction of harmonic power flow and the event logs help confirm it.

Which standard governs power quality?

IEEE 1159 classifies the phenomena and gives monitoring guidance; IEC 61000-4-30 defines how they are measured (Class A); IEEE 519 sets harmonic limits at the point of connection; EN 50160 describes the voltage characteristics of public networks in Europe. Grid codes and utility rules add the limits that apply locally.