Capacitor Bank Trips: Causes and Diagnosis

Why a capacitor bank trips: unbalance from failed elements, natural unbalance, harmonic resonance, overvoltage, inrush or undervoltage.

By Shadai García, CEO and protection engineer at Tiza Group.

busneutral CTstar 1star 260Nalarmtripbalanced bank: neutral I ≈ 0an element fails: neutral I risesunbalance alarmanother element of the same group failsthe healthy phases exceed 110 % voltagebank tripreset after replacing the unitsI neutraltalarmtripU on healthy ones110 %groupthe neutral I measures the unbalance between starsSchemeNeutral unbalanceAlarmTripbank 52© tizagrp.combusneutral CTstar 1star 260Nalarmtripbalanced bank: neutral I ≈ 0an element fails: neutral I risesunbalance alarmanother element of the same group failsthe healthy phases exceed 110 % voltagebank tripreset after replacing the unitsI neutraltalarmtripU on healthy ones110 %groupthe neutral I measures the unbalance between starsSchemeNeutral unbalanceAlarmTripbank 52© tizagrp.com
Capacitor bank trip: failed element, neutral unbalance and overvoltage. Location in the system and operating principle. Illustrative: real values come from the nameplate and the manufacturer's manual.
Short answer

The key protection of a capacitor bank is unbalance protection, which detects failed elements or units before the healthy ones are overstressed. If the bank trips on unbalance, first assume there is real internal damage. If there is none, the typical causes are poorly compensated natural unbalance, a problem with the neutral CT or VT, or unbalance in the system. Overcurrent or overvoltage trips are usually due to harmonic resonance, energization or high system voltage.

Symptom

A capacitor bank in a substation or industrial plant goes out of service on a protection trip. It may be on unbalance, overcurrent, overvoltage or undervoltage. Sometimes the bank returns to service without problem and trips again days later; other times the trip coincides with energization, with an hour of low demand or with the start of loads with drives.

A bank is made up of many units in series and parallel, and each unit of many elements. When an element fails, its internal fuse operates, a unit loses its external fuse or, in fuseless banks, the element is left shorted. In every case the capacitance of one branch changes, the voltage is redistributed and the healthy units are subjected to more voltage. Unbalance protection compares currents or voltages that, with a healthy bank, are nearly equal, and trips before the overvoltage on the healthy units exceeds the permissible limits, per IEEE C37.99 and IEC 60871-1. How that unbalance is measured and how alarm and trip are staged is explained in capacitor bank unbalance protection.

Possible causes, from most to least likely

CauseWhy it happensWhat gives it away
Failed elements or unitsAging, overvoltages, harmonics, temperatureUnbalance trip; earlier unbalance alarm that was growing
Poorly compensated natural unbalanceManufacturing tolerances; compensation not updated after units were replacedUnbalance present since energization with a healthy bank
Faulty neutral CT or VTWrong ratio, loose connection, saturationUnbalance measurement inconsistent with the phase currents
System unbalanceIn banks with a grounded neutral measured by current, system voltage unbalance and zero-sequence harmonics show up in the neutralUnbalance that follows the system load, not the bank
Harmonic resonanceThe bank capacitance and the system inductance resonate near a harmonic that is presentBank current with high harmonic content, overload or peak overvoltage
Inrush currentDischarged bank or energization with another bank already connected (back-to-back)Instantaneous overcurrent trip on closing
System overvoltageLow demand, transformer taps, the bank itself raising the voltage59 trip during low-load hours
UndervoltageVoltage sag or loss of supply; the 27 disconnects the bank on purpose27 trip coinciding with a system event
Restrike on openingA breaker that restrikes on opening and generates overvoltagesOvervoltages in the oscillography of the opening

What to check first

  1. Which function tripped: unbalance, overcurrent, overvoltage or undervoltage. Each points to a different group of causes.
  2. History of the unbalance measurement: whether it had been rising in steps (elements failing one by one) or appeared suddenly.
  3. Inspection of the bank de-energized and discharged: operated external fuses, bulged or leaking units, signs of heating.
  4. Harmonic content of the bank voltage and current in the oscillography or with an analyzer. See IEEE 519 harmonic study.
  5. Time of the trip: energization, low-load hours, start of other loads or system switching.
First check on a capacitor bank trip
  • Which function tripped?
    • Unbalance: Had the unbalance been rising, or are fuses operated?
      • Yes: Failed elements or units: do not re-energize without inspecting the bank
      • No: Poorly compensated natural unbalance, neutral CT or VT, or system unbalance
    • Overcurrent: Did it happen on energization?
      • Yes: Inrush current or back-to-back switching
      • No: Harmonic resonance: measure the harmonic content
    • Overvoltage or undervoltage: System voltage out of range or system event

How to confirm

  • Capacitance measurement of each unit or branch, compared with the nameplate and the manufacturer’s tolerances. It locates units with failed elements.
  • Natural unbalance measurement with a healthy bank and recalibration of the relay compensation, per the manufacturer.
  • Harmonic measurement with the bank connected and disconnected, and calculation of the resonance frequency using the short-circuit power of the bus. See active versus passive harmonic filter.
  • Tests on the neutral CTs and VTs and on the protection with secondary injection. See secondary injection.
  • Energization analysis: peak and frequency of the inrush current against the instantaneous setting.

How to keep it from coming back

  • Unbalance alarm ahead of the trip, to schedule unit replacement.
  • Re-compensate the natural unbalance every time a unit is replaced.
  • Harmonic study before installing or expanding the bank; if there is resonance risk, a detuned bank or a filter. See how to size a capacitor bank.
  • Current-limiting reactors or synchronized switching where back-to-back energization is frequent.
  • Bank control by voltage or by reactive power that takes it out at low demand.

Bank configurations and what each unbalance protection measures

How unbalance is measured depends on how the bank is connected, and it determines which fault is seen and which false alarm is likely:

ConnectionWhat is measuredNote
Ungrounded wyeVoltage between the bank neutral and groundNeutral voltage grows when a phase loses capacitance; sensitive to residual system voltage
Grounded wyeCurrent through the ground connectionNeutral current includes system unbalance and zero-sequence harmonics
Double wye (split wye)Current between the two neutralsCompensates a good part of the system unbalance, because both halves share it
H-bridge per phaseCurrent in the bridgeEach phase has its own measurement and the affected phase can be identified

IEEE C37.99 is the reference guide for choosing the connection and protection of shunt banks, and the selection depends on the voltage, the size of the bank and whether it has internal, external or no fuses. Each configuration brings its own alarm and trip thresholds, calculated from the number of units, the number of elements per unit and the permissible overvoltage on the remaining units.

Operating limits of the units

Capacitor standards set a limit for permanent overvoltage. IEEE 18 and, for medium and high voltage, IEC 60871-1 allow continuous voltage of up to 110 % of rated. They also set limits for peak voltage and for the resulting reactive power. Those limits are for contingencies and not a normal design criterion. The exact values are in the edition of the standard that applies to the contract. After the bank is opened, each unit must discharge through internal resistors to a low residual voltage, within a time defined by the standard. The bank must not be re-energized before that time, because the residual charge adds to the system voltage and produces a closing overvoltage. The controls of many banks include a discharge timer with that function; verify the manufacturer’s value, not a generic one.

Resonance: when the bank amplifies harmonics

A bank and the source inductance form a resonant circuit whose approximate harmonic order is the square root of the ratio between the bus short-circuit power and the bank rating. If that order falls near a harmonic produced by the loads, for example the 5th or 7th from drives and rectifiers, the bank current is amplified and can overload the units. That is why, when adding a bank or changing the system short-circuit power, the resonance order must be calculated again. Detuned banks with a series reactor move the resonance below the harmonics present; the detuning factor and the rated voltage of the units are chosen together, because the reactor raises the voltage across the capacitors.

What not to do

  • Do not re-energize a bank that tripped on unbalance without inspecting it: the overvoltage on the healthy units speeds up new failures and can end in a major fault.
  • Do not raise the unbalance setting to stop it from tripping.
  • Do not touch a de-energized bank without discharging, shorting and grounding each unit.
  • Do not add capacitance to a bus with harmonics without studying the resonance.

When to call us

If your capacitor bank trips and it is not clear why, send us the events and the oscillography: we quote the trip analysis, a remote service available worldwide. We test the bank and its protection on site with protection testing, in Colombia or elsewhere on request, run the power quality study to evaluate resonance, and our team sets the unbalance relay through remote relay configuration. Write to us.

References

  • IEEE C37.99, Guide for the Protection of Shunt Capacitor Banks.
  • IEC 60871-1, shunt capacitors for a.c. power systems having a rated voltage above 1 000 V.
  • IEEE 18, shunt power capacitors.
  • IEEE 519, recommended practice for harmonic control in electric power systems.

Frequently asked questions

Why does a capacitor bank trip on unbalance with no visible fault?

Because unbalance protection detects internal element failures or internal fuse operations that cannot be seen from outside. It can also operate from poorly compensated natural unbalance, a faulty neutral CT or VT, or a setting that does not match the real bank configuration.

Why does the bank trip on overcurrent without a fault?

The most common causes are inrush current, especially when a bank is energized with another already connected to the same bus, and harmonic currents. If the bank capacitance and the system inductance form a resonance near a harmonic that is present, the bank current and voltage rise sharply.

Can a bank be re-energized right after the trip?

Not until the residual voltage has dropped to the value the standard and the manufacturer allow. The discharge devices set that time, and many controls block closing meanwhile. In addition, if the trip was on unbalance, the bank must be inspected before re-energizing.