Chapter 54 of BS 7671 covers the earthing arrangements of a low-voltage installation: the earth electrode, the earthing conductor, the main earthing terminal, the circuit protective conductors and the main protective bonding conductors. Sizes follow from two checks: the protective conductor must survive the fault current for the disconnection time, and the main bonding conductor follows a rule tied to the earthing conductor or the supply neutral. Both are shown below with an illustrative calculation.
Earthing looks simple on a drawing: one terminal, a few green-and-yellow conductors. In practice, Chapter 54 of BS 7671 is where fault current, disconnection time and conductor size meet. For the wider framework of UK rules, see the UK electrical codes and grid connection guide. The current edition is BS 7671:2018+A4:2026.
Short answer: what does BS 7671 Chapter 54 require for earthing and bonding?
Chapter 54 of BS 7671 sets out how an installation connects to earth and how its metalwork is tied together. It has four building blocks. The earth electrode, or the distributor’s earth terminal, is the connection to the general mass of earth. The earthing conductor joins that connection to the main earthing terminal. Circuit protective conductors (CPCs) carry earth fault current back to the source. Main protective bonding conductors join extraneous conductive parts, such as metal service pipes, to the main earthing terminal so that they stay at nearly the same potential as exposed metalwork.
The building blocks of Chapter 54
Means of earthing. On TN-S and TN-C-S supplies, the distribution network operator (DNO) provides an earth terminal, and its terms are set by the ESQCR 2002. On a TT supply, the installation has its own electrode. The three families are explained in low-voltage system earthing: TT, TN and IT.
Earth electrodes. Chapter 54 accepts rods, tapes or wires, plates, and foundation or structural earths. Utility gas and water pipes are not allowed as electrodes. The design aim on a TT system is a resistance that, with the rating of the residual current device (RCD), keeps touch voltage under the limit. The arithmetic is in the Chapter 41 guide.
Earthing conductor. It must be sized for the fault current it may carry, protected against corrosion, and have mechanical protection where needed. The connection to the electrode needs a durable joint and a label that tells a later reader not to remove it.
Circuit protective conductors. A CPC is either a core of the cable, a separate conductor, or in some cases a metal enclosure or conduit that meets the rules for continuity. Two checks set its size, covered below.
Main protective bonding. Extraneous parts such as incoming metallic water and gas pipes, structural steel and central heating pipes are connected to the main earthing terminal. The connection is made close to where the service enters the building.
Main earthing terminal. All of these conductors meet here, and it must be accessible and arranged so that each conductor can be disconnected for testing.
Sizing a protective conductor: the adiabatic check
For a fault cleared within five seconds, the heating of the conductor is treated as adiabatic: all the heat stays in the conductor. The minimum cross-sectional area is the square root of the energy let through, divided by a factor k that depends on the conductor and insulation material. In symbols, S = √(I²t) / k, where I is the fault current in amperes, t is the disconnection time in seconds, and S is in mm². The factor k for each material combination is given in the standard’s tables, so use the current text.
The second route avoids the calculation. A table relates the protective conductor to the size of the line conductor of the circuit, so a designer picks the CPC from the table when the conductor is part of a cable or a standard run. Where the calculated value is higher than the table value, the calculation governs.
There is also a floor for conductors that are not part of a cable. The minimum is bigger when the conductor is not mechanically protected, because a small bare or single conductor is easily damaged.
Sizing main protective bonding
On a TN-C-S supply with protective multiple earthing (PME), the size is tied to the supply neutral conductor. For a copper neutral up to 35 mm², Table 54.8 gives 10 mm² copper bonding. Larger neutrals step up through the table. On TN-S and TT systems, the rule in Regulation 544.1.1 ties the bonding conductor to the earthing conductor: half its cross-section, not less than 6 mm² and not more than 25 mm² for copper. The reason PME gets a larger conductor is that a broken neutral on the network can put the whole installation at a voltage above earth, and the bonding conductor may carry load current in that case.
Worked example
The numbers are illustrative and the data are assumed.
Part A: a circuit protective conductor. A TN-S installation has a prospective earth fault current of 1,200 A in a circuit, and the protective device clears it in 0.4 s. The protective conductor is a copper core with 70 °C PVC insulation, where the factor k is taken as 115 for this example.
- Energy term: I²t = 1,200² × 0.4 = 576,000 A²s.
- Square root: √576,000 = 759 A·s^0.5.
- Minimum area: S = 759 / 115 = 6.6 mm².
- Next standard size above 6.6 mm² is 10 mm². A 6 mm² core would not pass.
If the CPC is a core of a multicore cable, a cable with a 6 mm² CPC would fail this check at 1,200 A. The designer would then raise the CPC size or cut the clearing time with a faster device.
Part B: main bonding. The installation has a 16 mm² earthing conductor on a TT supply. Half is 8 mm², which is above the 6 mm² floor and below the 25 mm² ceiling, so the bonding conductor must be at least 8 mm². The next standard size is 10 mm². On the same site, if the supply were TN-C-S with a 25 mm² copper neutral, Table 54.8 would require 10 mm² as well, so the answer is the same but for a different reason. Record the reason on the schedule, because it changes if the supply changes.
Figure: a single-line diagram of the main earthing terminal with the earthing conductor, the main bonding to water and gas services, and the circuit protective conductors.
Common problems in practice
- Applying the TN-S rule for bonding to a PME supply, and using a conductor that is too small.
- Using a CPC sized by the table when the real fault current is much higher than the table assumes. This happens close to a large transformer.
- Bonding clamps on painted or corroded pipes, with no label.
- A bonding conductor connected after a plastic insert in a pipe, so it bonds nothing.
- An earth electrode joint buried with no inspection pit, which nobody can test.
- Treating supplementary bonding as a substitute for proper disconnection times. It is a separate measure with its own conditions.
Checklist for the engineer
- Identify the earthing arrangement and who owns the means of earthing.
- Fix the prospective earth fault current and the disconnection time for each circuit type.
- Size the CPC by the table and by the adiabatic check, and take the larger.
- Size the main bonding conductor from the supply neutral or the earthing conductor.
- List the extraneous conductive parts that need bonding.
- For TT, estimate the electrode resistance and the seasonal range, and confirm the RCD choice.
- Specify labels, accessible joints and a test link at the main earthing terminal.
- For larger sites, read the ENA TS 41-24 earthing guide and the S34 guide for substations, as the installation earth may share a system with the substation.
- Record the results against the calculated limits using the methods in the guide to inspection and testing. The wider practice for electrodes is in the guide to the BS 7430 code of practice.
Legal frame
In the UK there is no statutory stamp for electrical designs. A chartered engineer or other competent person reviews the design and signs it under their own responsibility. The duty to keep the system safe sits in the Electricity at Work Regulations 1989. For industrial installations, see the guide on industrial earthing and the equipotential bonding network.
How Tiza can help
If your project needs an earthing and bonding design, Tiza prepares the engineering remotely and in English: fault current and conductor calculations, electrode estimates and the schedules that go with them. Tiza does not stamp, sign or certify designs in the UK; we deliver engineering ready for your chartered engineer to review and sign. Contact us with the supply data and the single-line diagram.
Frequently asked questions
What size is main protective bonding in BS 7671?
On a TN-C-S (PME) supply, the size follows the supply neutral conductor through Table 54.8: a neutral up to 35 mm² copper gives 10 mm² copper bonding. On TN-S and TT, the bonding is half the earthing conductor, with a 6 mm² minimum and no need to exceed 25 mm². Always check the table in the current text.
What is the difference between an earthing conductor and a protective conductor?
The earthing conductor joins the main earthing terminal to the means of earthing, which is the supply earth terminal or an earth electrode. A circuit protective conductor (CPC) runs with each circuit and joins exposed metal to the main earthing terminal. Bonding conductors are a third type: they join extraneous metal such as pipes to the same terminal.
Can I use the water pipe as the earth electrode?
No. Metal gas and water pipes of the utility must not be used as an earth electrode. Chapter 54 lists acceptable electrodes such as rods, tapes, plates and foundation earths. Metal services still get connected by main bonding, which is a different job.