Revenue Metering Point Panel: Design and Contents

What a revenue metering point panel contains: main and backup meter, test block, seals and communications, and how the accuracy tier drives the design.

By Shadai García, CEO and protection engineer at Tiza Group.

clientoperatorXM (ASIC)retailerdesigncalibrationinstallationverificationreceiptrecordobjectionssealingstaged processclassify the point and design the measuremeters and CT/VT calibratedassembly, wiring and communicationsinitial verification of the meteringthe OR verifies at the receiving visitASIC: study in 2 calendar dayspublication and 4 days for objectionscommissioning and sealingdesigncalibrationinstallationverificationreceiptrecordobjectionssealinggridkWhmeas.52loadMetering Code: class according to point typePartiesCustomerUtilityXM (ASIC)Retailer© tizagrp.comclientoperatorXM (ASIC)retailerdesigncalibrationinstallationverificationreceiptrecordobjectionssealingstaged processclassify the point and design the measuremeters and CT/VT calibratedassembly, wiring and communicationsinitial verification of the meteringthe OR verifies at the receiving visitASIC: study in 2 calendar dayspublication and 4 days for objectionscommissioning and sealingdesigncalibrationinstallationverificationreceiptrecordobjectionssealinggridkWhmeas.52loadMetering Code: class according to point typePartiesCustomerUtilityXM (ASIC)Retailer© tizagrp.com
Commercial boundary and metering system: class, verification and record. Location in the system and operating principle. Illustrative: real values come from the nameplate and the manufacturer's manual.
Short answer

A revenue metering point panel houses the metering system at a point where energy is transferred between parties and billed: main meter, backup meter where required, test block, seals and communications. The accuracy tier of the point, set by the monthly energy or the installed capacity, drives the classes, the backup, the clock tolerance and the maintenance interval.

The revenue metering point panel is the enclosure that houses the metering system where energy is transferred between parties and billed. It is one variant of types of electrical panels; depending on current and voltage level, its measurement is semi-direct or indirect.

Short answer

A revenue metering point panel brings together the main meter, the backup meter where required, the test block, the seals, the communications for remote reading and the protection of the wiring. What defines it is not the construction but the accuracy tier of the metering point, which fixes the classes, the backup, the clock tolerance and the maintenance interval.

What it contains

ComponentFunction in the panel
Active and reactive energy meterRecords the transaction; reactive may be built into the same device
Backup meterSecond measurement with the same signals and the same configuration
Test blockSeparates or replaces a device without taking the point out of service; on-site calibration; takes seals
Burden compensation loadsKeep the transformer burden inside its class
Security enclosureProtects against weather, tampering and physical damage
Communication deviceLocal and remote reading
Security and monitoring schemesProtect the devices and follow their alarm signals

Meters should have a local port to download measurements and parameters and a display with the registered quantities, date and time. Data are held in non-volatile memory with enough history for the reading cycle, and the configuration of main and backup meters is identical.

What the accuracy tier decides

The requirements can be organized by accuracy tier. The table is an illustration of how the design changes from one tier to the next; the actual limits come from the utility or the energy contract.

TierMeter classCTVTBackup meterClock toleranceMaintenance
High0.2S0.2S0.2YesTightestShortest interval
Medium0.5S0.5S0.5Yes or noTighterMedium interval
LowClass 10.50.5NoRelaxedLongest interval

The meter classes are defined in IEC 62053-22:2020 and the transformer classes in IEC 61869-2:2012 and IEC 61869-3:2011.

Worked example

A plant has a monthly consumption of 600 MWh and a 0.8 MVA transformer. The contract places the point in the medium tier by energy and by capacity; both criteria agree, and the contract requires a backup meter.

  1. Meter 0.5S, CT 0.5S, VT 0.5.
  2. Backup meter with the same signals and the same configuration as the main meter.
  3. Dedicated secondary windings on the transformers for the meters.
  4. Clock synchronized remotely to a common time reference.
  5. Consistency control by the data collection system: the difference between backup and main meter must not exceed a few times the class index. With class 0.5 meters and a limit of three times the index, that is 1.5 %: on an hourly reading of 1,000 kWh, up to 15 kWh of difference.

If the tier is set by two criteria that disagree, the design uses the more demanding one.

Physical and cyber security

  • Non-volatile memory for readings and configuration.
  • At least two access levels with a password per user: level 1 reads, level 2 sets the clock, calibration and parameters.
  • A log of every level 2 access, with date, person, purpose and activities.
  • Seals on meters, transformers, test blocks and other sensitive elements, with a record of each seal. Only the party that installed a seal removes it, jointly with the other party and with a written record.

The panel layout must leave seal points accessible without blocking meter reading.

Reading and reporting

A revenue metering panel is only useful if its data reach the party that bills. Four design points follow from that:

  • Hourly registers. The meter stores the energy of each hour with a time stamp, so any dispute can be settled against the record.
  • Remote reading. The communication device must allow a reading cycle without visiting the site, and the interrogation, consolidation and report should run automatically.
  • Time reference. The meter clock must be correctable remotely during normal reading operations, so a drifting clock does not misplace energy between hours.
  • Cross-check between meters. When a backup meter exists, the data system compares both readings and flags a difference beyond the allowed multiple of the class index, which is the first sign that one meter or one transformer circuit has a fault.

Common mistakes

  • Backup meter wired to different taps than the main meter, so it cannot confirm it.
  • Different configuration in the two meters (constants, ratios, demand intervals).
  • Test block without seal points, or with seals that block access to the reading port.
  • Shared transformer windings that add burden and degrade the class.
  • No record of who accessed the meter, which breaks the audit trail.

Checklist

  • Tier calculated with both variables (energy and capacity) and the projection from the connection study if the point is new.
  • Meter, CT and VT classes consistent with the tier.
  • Backup meter where required, with the same configuration.
  • Test block with seals; wiring marked and protected.
  • Voltage drop calculation in the voltage circuit, filed.
  • Clock that can be synchronized remotely; communications for automatic reading.
  • Access levels and passwords defined and recorded in the metering file.
  • Product certificates and calibration reports before commissioning.

How we help

We design revenue metering panels remotely, worldwide: tier classification, meter and transformer selection, test block, seals and communications layout, adapted to the local code and the utility requirements you give us. See our primary engineering service and write to us with your consumption, capacity and connection point.

References

  • IEC 62053-22:2020, static meters for AC active energy (classes 0.1S, 0.2S and 0.5S).
  • IEC 61869-2:2012, instrument transformers: current transformers.
  • IEC 61869-3:2011, instrument transformers: inductive voltage transformers.

Frequently asked questions

What does a revenue metering point panel contain?

The active and reactive energy meter, a backup meter where the accuracy tier requires it, the measuring transformers or their wiring, a test block with seals, the communication device for local and remote reading, and security and monitoring schemes.

Does a revenue metering point need a backup meter?

At the highest accuracy tiers, and at generation and transmission connection points, yes. The backup meter runs permanently, has the same technical characteristics as the main one and receives the same voltage and current signals, so a failure of one meter does not lose the energy record.

How often should a revenue metering system be maintained?

The interval is set by the accuracy tier, the utility and the energy contract: the higher the tier, the shorter the interval. Maintenance includes calibration of the meters and routine tests of the transformers, and every action is recorded in the metering file.