NEC Article 430 builds a motor circuit from separate parts, each sized on its own current. The branch circuit conductor uses 125 percent of the full-load current from the code tables, the short-circuit and ground-fault device is a percentage of that same table current, and the overload protection uses the nameplate current. Mixing the two bases is the most common error. Controllers, disconnects and drives have their own parts of the article.
NEC article 430 motors is the part of the National Electrical Code (NEC, NFPA 70) that governs motor circuits: the conductors, the short-circuit and overload protection, the controller and the disconnecting means. It is written as a chain of parts, and the sizing of each part uses a different current.
The wider framework is in the US electrical codes and grid interconnection guide. The general logic of protecting a motor circuit, in both NEC and IEC practice, is in the guide on motor circuit protection: fuses and conductor. Here the focus is the NEC structure and the way to use its tables.
Section numbers here follow the 2023 edition of the NEC. The 2026 edition is current, but the authority having jurisdiction (AHJ) decides which one applies. Confirm the numbering and local amendments in the adopted edition.
Short answer
Article 430 sizes each element of a motor circuit separately. The branch-circuit conductors for a single motor are at least 125 percent of the motor full-load current taken from the tables of the code (section 430.22). The short-circuit and ground-fault device is limited to a percentage of that same table current (section 430.52 and its table). The overload protection is sized from the nameplate current (section 430.32), not from the table. Tables are used for conductors and short-circuit protection. The nameplate is used for the overload.
The structure of the article
Article 430 is organized in parts. The main ones:
- General. Definitions, and the rule that tells which current to use where (430.6).
- Motor circuit conductors. Single motors, several motors, and some duty cycles.
- Motor and branch-circuit overload protection. Overload relays, thermal protectors and the settings allowed.
- Branch-circuit short-circuit and ground-fault protection. Fuses, breakers and the percentages by device type.
- Feeder protection. Where one feeder serves several motors.
- Control circuits and controllers. The control circuit and the starter or drive.
- Motor control centers. Assemblies of starters.
- Disconnecting means. The disconnect within sight of the motor and the controller, with a rating based on the horsepower.
Variable-speed drives and some other special cases have provisions of their own in the same article. The controllers themselves, including motor control centers and manual motor protectors, are selected to match.
Two currents, three results
This is where most errors arise:
| Element | Current used | Result |
|---|---|---|
| Branch-circuit conductor | Full-load current from the code table | At least 125 percent |
| Short-circuit and ground-fault device | Full-load current from the code table | Up to a percentage that depends on device type |
| Overload protection | Nameplate current | A percentage of it, higher with a service factor or temperature rise rating |
The code tables list a full-load current by horsepower, voltage and phase. Take the value from the table of the adopted edition. The nameplate is the real motor. If the nameplate current is higher than the table value, the overload follows the nameplate, and the conductor and short-circuit device still follow the table, unless the code says otherwise for the case at hand.
The short-circuit device and the starting current
The device that protects the circuit against short circuits and ground faults must carry the starting current of the motor without opening. That is why the code lets it be much larger than the running current. The percentage depends on the type of device: a time-delay fuse can be smaller than an inverse-time breaker, and an instantaneous-trip breaker is allowed only in specific arrangements. The table also says when the next higher standard size can be used if the calculated value is not a standard rating, and when a still higher value is allowed if the motor does not start with the first choice.
This device protects the branch circuit. It does not replace overload protection, which is a separate device or a built-in function. For the starting of large motors and its effect on the supply, see starting large motors and voltage dip, and for the comparison of start methods, motor starting methods compared.
Overload protection
The overload device follows the motor nameplate. The usual maximum is a percentage of the nameplate current, higher for motors with a service factor of 1.15 or more or a marked temperature rise below a limit. The code allows an increase, up to a ceiling, if the first choice trips during a normal start. The relay is set by the engineer, and the setting is part of the project record. Thermal behavior and protection functions are explained in motor protection in low-voltage systems.
Conductors and corrections
The 125 percent rule gives the minimum conductor ampacity. Then the usual steps follow: terminal temperature limits, correction for ambient temperature, adjustment for the number of current-carrying conductors and voltage drop at starting. The table-reading method is in the guide on conductor ampacity under Article 310. For cables in a plant, see also power cables.
Figure: single-line of a motor circuit with the disconnect, short-circuit device, controller with overload relay and the motor, and the base current of each.
Worked example: a 30 hp motor at 460 V
The data are illustrative. The values labelled “assumed” stand for numbers that must be read from the tables of the adopted edition.
- Motor: 30 hp, 460 V, three-phase, service factor 1.15.
- Nameplate current: 37.5 A (assumed).
- Table full-load current for this horsepower and voltage: 40 A (assumed).
- Short-circuit percentages: 250 percent for an inverse-time breaker and 175 percent for a dual-element time-delay fuse, the values of Table 430.52 for a squirrel-cage motor of this kind.
Steps:
- Conductor: 40 × 1.25 = 50 A minimum ampacity, then the terminal and installation corrections.
- Short-circuit device, inverse-time breaker: 40 × 2.5 = 100 A maximum.
- Short-circuit device, time-delay fuse: 40 × 1.75 = 70 A maximum.
- Overload: with a service factor of 1.15 the usual ceiling is 125 percent of the nameplate current, so 37.5 × 1.25 = 46.9 A.
- Check that the device chosen in step 2 or 3 does not exceed what the starter and the conductor can take under fault, and that its interrupting rating covers the available fault current.
- Check the disconnect rating, which follows the horsepower, and the voltage drop at starting.
Notice that the conductor, the breaker and the relay use three different numbers, and two of them come from a table that does not look at the nameplate.
Common mistakes
- Sizing the conductor from the nameplate current, or the overload from the table current.
- Choosing a short-circuit device above the table percentage.
- Setting the overload at the short-circuit device value.
- Ignoring the manufacturer’s data when the circuit has a drive or a combination starter.
- Forgetting the disconnect within sight of the motor, or the arrangement the AHJ accepts instead.
Checklist for the engineer
- Confirm the NEC edition and amendments adopted by the AHJ.
- Take the table full-load current and the nameplate current for each motor.
- Conductor at 125 percent of the table current, then corrections and terminal rating.
- Short-circuit device within the percentage for its type, with the right interrupting rating.
- Overload device set from the nameplate within the allowed limit.
- Controller, disconnect and rating by horsepower.
- Start-up voltage drop and the effect on the rest of the system.
- For drives, follow both the code and the drive manufacturer.
Who signs and seals
In the United States a design normally has to be signed and sealed by a professional engineer licensed in the state of the project.
From the rules to a design your engineer can stamp
Tiza provides engineering design for motor circuits and motor control: calculations, single-line and control diagrams and protection settings, ready for your engineer of record to review and stamp. Tiza does not sign, seal or certify work in the United States. Contact us with the motor list, the supply data and the controller type.
Frequently asked questions
Why does NEC Article 430 use a table current and the nameplate current?
The conductors and the short-circuit device are sized from the full-load current in the tables of the code, so that two motors of the same horsepower get the same circuit. The overload protection is sized from the nameplate current, because it must follow the actual motor. Section 430.6 sets which one applies to each part.
How is the conductor to a single motor sized under 430.22?
The ampacity is at least 125 percent of the full-load current from the table, before the usual corrections for temperature, grouping and terminal rating. Then the short-circuit device, the overload device and the voltage drop are checked as separate steps.
Does Article 430 cover motors with variable frequency drives?
Yes. The article has provisions for adjustable-speed drive systems, and the drive manufacturer's instructions and listing also apply. Drive input and output circuits are sized with their own rules, so check them in the adopted edition.