UL 1741 SB grid support: the advanced inverter functions a utility-interactive unit offers and how settings work, with a worked example and a checklist.

By Shadai García, CEO and protection engineer at Tiza Group.

gridlocal bus 1.08 pu=~100 kWVvoltageutilitysettings tablePowerVoltageCommsslope 1.06 to 1.10 pu is 0.04 wideat 1.08 pu: 0.02 / 0.04 = 0.50drop 80 kW x 0.50 = 40 kW100 kW - 40 kW = 60 kW40 kW for one hour = 40 kWh lostV (pu)1.001.061.10100 %20 %1.0840 kW curtailed60 kWGrid supportVoltageVolt-watt curveSettingsPower© tizagrp.comgridlocal bus 1.08 pu=~100 kWVvoltageutilitysettings tablePowerVoltageCommsslope 1.06 to 1.10 pu is 0.04 wideat 1.08 pu: 0.02 / 0.04 = 0.50drop 80 kW x 0.50 = 40 kW100 kW - 40 kW = 60 kW40 kW for one hour = 40 kWh lostV (pu)1.001.061.10100 %20 %1.0840 kW curtailed60 kWGrid supportVoltageVolt-watt curveSettingsPower© tizagrp.com
UL 1741 SB grid support: a 100 kW inverter that reads the local voltage and reduces power by its volt-watt curve, with the utility settings table over the communications link, and the curtailment at 1.08 per unit. Location in the system and operating principle. Illustrative: real values come from the nameplate and the manufacturer's manual.
Short answer

UL 1741 SB grid support covers the advanced functions that let a utility-interactive inverter help regulate voltage and frequency instead of only following the grid. The functions are tested against IEEE 1547.1-2020, and the utility chooses which are enabled and with which settings.

UL 1741 SB grid support is the reason a modern inverter is described as utility-interactive or smart. Older inverters followed the grid and tripped when it moved outside narrow limits. A listed unit can now stay connected through disturbances and actively help the voltage and frequency recover.

This guide is based on the third edition of UL 1741 including Supplement SB, together with IEEE 1547-2018 and IEEE 1547.1-2020.

Short answer

UL 1741 SB grid support is the set of advanced functions that a listed inverter must be able to perform, tested to the procedures of IEEE 1547.1-2020. They are ride-through of voltage and frequency disturbances, voltage regulation by reactive power and by active power, frequency response, and defined behavior when the grid is lost. The listing proves capability. The utility decides which functions are on and what curves they use.

Figure: a voltage axis with the regions where an inverter rides through, regulates with reactive power or reduces active power, drawn as a single curve set.

How this listing relates to IEEE 1547 is in UL 1741 SB vs IEEE 1547: who certifies what. The wider framework is in the US electrical codes and grid interconnection guide.

The functions in plain words

  • Ride-through. The inverter stays connected and keeps operating during a voltage or frequency excursion for a defined time instead of tripping at once. IEEE 1547-2018 groups equipment into performance categories that differ in how much ride-through is required.
  • Voltage-reactive power (volt-var). The inverter absorbs or supplies reactive power as the local voltage changes, which pulls the voltage back toward normal.
  • Voltage-active power (volt-watt). When voltage is high, the inverter reduces its real power output to avoid pushing the voltage higher.
  • Frequency-active power (frequency-watt). When frequency is high, the inverter reduces real power, which helps the system recover.
  • Constant power factor and constant reactive power. Fixed modes that the utility can choose instead of a curve.
  • Anti-islanding and reconnection. The inverter stops energizing when the grid is lost and waits before it reconnects.

Several state programs publish their own settings, and those values apply in their territory.

Capability, enablement and settings

Three separate questions are often mixed up.

QuestionAnswered by
Can the inverter do the function?The listing and the datasheet
Is the function turned on?The utility requirement and the commissioning record
Which curve or limit does it use?The utility or state program settings table

An inverter can be fully listed and still leave the site with all functions off, because the factory default may not be the utility’s choice. The commissioning check in IEEE 1547 commissioning tests is where this is caught.

What it does to the plant design

Grid support affects the design in four places.

  • Reactive power capability. Absorbing reactive power uses part of the inverter’s apparent power, so real power may be limited at high reactive output.
  • Voltage limits at the connection. Volt-watt can curtail energy on a feeder with high voltage, which changes the production estimate.
  • Protection. Ride-through delays the trip. The interface protection settings and the coordination with upstream devices must allow for it. See short-circuit and protection coordination in solar plants.
  • Communications. Many programs expect the settings to be readable and changeable by the utility or an aggregator. See inverter integration with SunSpec and the cybersecurity notes in IEEE 1547.3.

Where inverters share a plant controller, see also power plant controller testing.

Worked example (illustrative)

A 100 kW inverter has a volt-watt function with these illustrative settings: full output up to 1.06 per unit voltage, falling in a straight line to 20 percent of rated power at 1.10 per unit. The local voltage reaches 1.08 per unit at midday.

Step 1. Position on the slope. The slope runs from 1.06 to 1.10, which is 0.04 per unit wide. The voltage is 0.02 per unit past the start. The fraction is 0.02 / 0.04 = 0.50.

Step 2. Total drop along the slope. From 100 percent to 20 percent is 80 percent of rated power, or 80 kW.

Step 3. Power at 1.08 per unit. 100 kW − 0.50 × 80 kW = 60 kW.

Step 4. Energy effect. If the unit would have produced 100 kW, 40 kW is curtailed during that hour. For one hour the lost energy is 40 kWh.

The same arithmetic with a different curve is how the production estimate is adjusted for a feeder that runs at high voltage. The curve values here are chosen for the illustration.

Checklist for the engineer

  • Obtain the utility or state program settings table for the territory.
  • Confirm that the listed model and firmware support each required function.
  • Check which functions are enabled by default and which must be turned on.
  • Check the reactive capability against the real power at the site.
  • Estimate the curtailment from volt-watt on the feeder voltage profile.
  • Allow for ride-through in the interface protection settings.
  • Confirm how the utility will read or change the settings remotely.
  • Record the loaded settings and the firmware version at commissioning.

Who signs and seals

In the United States a design is normally signed and sealed by a professional engineer licensed in the state of the project. Our engineering and settings documents are delivered ready for your engineer of record to review and stamp. Tiza does not sign, seal or certify work in the United States.

How Tiza can help

If the inverter settings have to be planned, loaded and recorded across many units, Tiza provides remote relay and inverter configuration: a settings plan, remote loading with a record of every value, and a verification report ready for your engineer of record to review. Contact us with the inverter models and the settings table.

Frequently asked questions

What does grid support mean for an inverter?

It means the inverter does more than inject power. It can ride through voltage and frequency disturbances, absorb or supply reactive power as voltage changes, and reduce active power when voltage or frequency is high. The utility selects the functions and the settings.

Are the advanced functions always enabled?

No. A listed inverter is able to perform them. Which ones are enabled, and with which curves, depends on the utility's requirements. The commissioning check confirms that each required function is on.

Does UL 1741 SB replace the utility's settings?

No. The listing shows the inverter can perform the functions within the ranges of IEEE 1547. The settings still come from the utility or the state program and must be loaded and recorded for each site.